Loading...
171NDentonTap_75019_69862 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-34535 Test Date: 5/13/2019 Result: Passed Reason for Test: Existing Account Name : Dr Dudly Address of Assembly : 171 N Denton Tap Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Domestic Manufacturer :Watts ByPass : Model No :009QT ByPass : Size :1/2 ByPass : Serial No :168129 ByPass : Location At:thru the back door on pillar to the left Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?Yes Reduced Pressure Principle Assembly Type II Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Bypass Check Air Inlet Check Valve Initial Test Date:5/13/2019 Time:8:00 AM Held at 8.2 psid Closed Tight Leaked Held at 8 psid Closed Tight Leaked Opened at 3 psid Did not open Held at psid Closed Tight Leaked Opened at psid Did it fully open Yes No Held at psid Leaked Repairs andMaterialsUsed ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Held at psid Closed Tight Leaked Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Non-Potable Make: Midwest Model: 845-5 Serial No.: 11130531 Date Tested for Accuracy: 3/11/2019 Remarks : Firm Name : .01 Accuracy Backflow Licensed Tester : Brian Cox Firm Address : P.O.Box 6832 BPAT License # : BP0017066 Firm Phone No : 972.699.7156 License Expiration Date : 02/23/2022 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.