Loading...
400MockingbirdLn_75019_74359 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-46964 Test Date: 7/24/2019 Result: Passed Reason for Test: Existing Account Name : Current Water Customer Address of Assembly : 400 Mockingbird Ln Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Domestic Manufacturer :Watts ByPass : Model No :LF909 ByPass : Size :2 1/2 ByPass : Serial No :003641 ByPass : Location At:Riser room Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Type II Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Bypass Check Air Inlet Check Valve Initial Test Date:7/24/2019 Time:10:10 AM Held at 8.8 psid Closed Tight Leaked Held at 8 psid Closed Tight Leaked Opened at 2.8 psid Did not open Held at psid Closed Tight Leaked Opened at psid Did it fully open Yes No Held at psid Leaked Repairs andMaterialsUsed ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Held at psid Closed Tight Leaked Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: MacAuthur G Model: 844-0005 Serial No.: 04021122 Date Tested for Accuracy: 9/14/2018 Remarks : Firm Name : Stacy's Backflow Licensed Tester : Brandy Stacy Firm Address : 2633 Jewett Road BPAT License # : BP0005606 Firm Phone No : 817-293-3803 License Expiration Date : 02/08/2021 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.