400MockingbirdLn_75019_74360 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-46964 Test Date: 7/24/2019 Result: Passed Reason for Test: Existing Account Name : Current Water Customer Address of Assembly : 400 Mockingbird Ln Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Domestic Manufacturer :Watts ByPass : Model No :LF009QT ByPass : Size :2 ByPass : Serial No :119892 ByPass : Location At:Football field concession stand janitorial room Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Type II Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Bypass Check Air Inlet Check Valve Initial Test Date:7/24/2019 Time:10:15 AM Held at 8.4 psid Closed Tight Leaked Held at 8 psid Closed Tight Leaked Opened at 3 psid Did not open Held at psid Closed Tight Leaked Opened at psid Did it fully open Yes No Held at psid Leaked Repairs andMaterialsUsed ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Held at psid Closed Tight Leaked Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: MacAuthur G Model: 844-0005 Serial No.: 04021122 Date Tested for Accuracy: 9/14/2018 Remarks : Firm Name : Stacy's Backflow Licensed Tester : Brandy Stacy Firm Address : 2633 Jewett Road BPAT License # : BP0005606 Firm Phone No : 817-293-3803 License Expiration Date : 02/08/2021 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.