230NDentonTapRd#115_75019_79260 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-22023 Test Date: 10/4/2019 Result: Passed Reason for Test: Existing Account Name : Coppell Modern Dentistry Address of Assembly : 230 N Denton Tap Rd #115 Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Domestic Manufacturer :Watts ByPass : Model No :009 ByPass : Size :1/2 ByPass : Serial No :357226 ByPass : Location At:equipment room Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Type II Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Bypass Check Air Inlet Check Valve Initial Test Date:10/4/2019 Time:11:53 AM Held at 7.9 psid Closed Tight Leaked Held at 8.3 psid Closed Tight Leaked Opened at 4 psid Did not open Held at psid Closed Tight Leaked Opened at psid Image: check.gif Did not open Did it fully open Yes No Held at psid Leaked Repairs andMaterialsUsed ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Held at psid Closed Tight Leaked Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: Mid-West Model: 845-5 Serial No.: 08160372 Date Tested for Accuracy: 8/13/2019 Remarks :Complete rubber kit was used to repair device Firm Name : A.C.E.Companies Licensed Tester : Marcus Ruiz Firm Address : 150 East Highway 67 Ste 210 BPAT License # : BP0016108 Firm Phone No : 469-899-6050 License Expiration Date : 10/23/2020 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.