201NDentonTap_75019_80128 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-22237 Test Date: 10/14/2019 Result: Passed Reason for Test: Existing Account Name : Sonic Address of Assembly : 201 N Denton Tap : Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Domestic Manufacturer :Watts ByPass : Model No :009M3QT ByPass : Size :1/2 ByPass : Serial No :19608 ByPass : Location At:CO2 tank Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Type II Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Bypass Check Air Inlet Check Valve Initial Test Date:10/14/2019 Time:8:16 AM Held at 8.7 psid Closed Tight Leaked Held at 8.5 psid Closed Tight Leaked Opened at 2 psid Did not open Held at psid Closed Tight Leaked Opened at psid Did not open Did it fully open Yes No Held at psid Leaked Repairs andMaterialsUsed ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Held at psid Closed Tight Leaked Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: Midwest Model: 845-5 Serial No.: 02171602 Date Tested for Accuracy: 6/17/2019 Remarks : Firm Name : All Test Service Solutions Licensed Tester : Kyle Mihalovich Firm Address : 600 Henrietta Creek Rd.#100 BPAT License # : BP0017367 Firm Phone No : 817-379-0856 License Expiration Date : 06/22/2022 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.