Loading...
NEW_137TX-121Ste_110_75019_82927 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-69196 Test Date: 11/25/2019 Result: Passed Reason for Test: New Account Name : Coppell Pediatric Dentistry Address of Assembly : 137 TX-121 Ste.110 : Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Other Manufacturer :Watts ByPass : Model No :LF009QT ByPass : Size :1/2"ByPass : Serial No :237594 ByPass : Location At:In utility closet Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?Yes Reduced Pressure Principle Assembly Type II Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Bypass Check Air Inlet Check Valve Initial Test Date:11/25/2019 Time:8:00 AM Held at 7.2 psid Closed Tight Leaked Held at 7.4 psid Closed Tight Leaked Opened at 2.9 psid Did not open Held at psid Closed Tight Leaked Opened at psid Did not open Did it fully open Yes No Held at psid Leaked Repairs andMaterialsUsed ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Held at psid Closed Tight Leaked Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Non-Potable Make: Midwest Model: 845-5 Serial No.: 11130531 Date Tested for Accuracy: 3/11/2019 Remarks : Firm Name : .01 Accuracy Backflow Licensed Tester : Brian Cox Firm Address : P.O.Box 6832 BPAT License # : BP0017066 Firm Phone No : 972.699.7156 License Expiration Date : 02/23/2022 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.