NEW_1201Creekview_75019_80603 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT
Name of PWS:Coppell
PWS I.D.:0570040
Address:816 S.Coppell Road
Coppell,Texas 75019
Phone:972-462-5150
Contact Person:Jerry Davis
Catalog No: TXTCOP-46668
Test Date: 10/22/2019
Result: Passed
Reason for Test: New
Account Name : Samaritain's Purse
Address of Assembly : 1201 Creekview : Address Type : Commercial
Inspection
The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within
acceptable parameters.
Type of Assembly :Reduced Pressure Detector Assembly Frequency :Annual What does this serve? Domestic
Manufacturer :Watts ByPass : Model No :LF009M2QT ByPass : Size :2 ByPass : Serial No :135548 ByPass :
Location At:NE WALL
Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes
Is the assembly installed on a non-potable water supply (auxiliary)?No
Reduced Pressure Principle Assembly Type II
Assembly
Pressure Vacuum Breaker
Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly
1st check 2nd check Relief Valve Bypass Check Air Inlet Check Valve
Initial Test
Date:10/22/2019
Time:9:06 AM
Held at 9.4 psid
Closed Tight
Leaked
Held at 8.3 psid
Closed Tight
Leaked
Opened at 3.4
psid
Did not open
Held at psid
Closed Tight
Leaked
Opened at psid
Did not open
Did it fully open
Yes No
Held at psid
Leaked
Repairs andMaterialsUsed **
Test After Repair
Date:
Time:
Held at psid
Closed Tight
Leaked
Held at psid
Closed Tight
Leaked
Opened at psid Held at psid
Closed Tight
Leaked
Opened at psid Held at psid
***2nd check:numeric reading required for DCVA only
Test gauge used: Potable Make: Mid-West Model: 845-5 Serial No.: 08160372
Date Tested for Accuracy: 8/13/2019
Remarks :
Firm Name : A.C.E.Companies Licensed Tester : Marcus Ruiz
Firm Address : 150 East Highway 67 Ste 210 BPAT License # : BP0016108
Firm Phone No : 469-899-6050 License Expiration Date : 10/23/2020
The above is certified to be true at the time of testing.
* Test Records must be kept for at least three years.[30 TAC §290.46(B)]
** Use only manufacturer's replacement parts.