1717E_BeltLineRd__75019_86053 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-22404 Test Date: 12/20/2019 Result: Passed Reason for Test: Existing Account Name : St.Marin Apartments Address of Assembly : 1717 E.Belt Line Rd. : Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? FireLine Manufacturer :Watts ByPass : Model No :009M2QT ByPass : Size :2 ByPass : Serial No :122450 ByPass : Location At:Riser rm.Bldg.#22 Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Type II Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Bypass Check Air Inlet Check Valve Initial Test Date:12/20/2019 Time:10:10 AM Held at 9.2 psid Closed Tight Leaked Held at 9.2 psid Closed Tight Leaked Opened at 2 psid Did not open Held at psid Closed Tight Leaked Opened at psid Did not open Did it fully open Yes No Held at psid Leaked Repairs and Materials Used ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Held at psid Closed Tight Leaked Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: Mid-West Model: 845-5 Serial No.: 07180126 Date Tested for Accuracy: 8/28/2019 Remarks : Firm Name : Metro Communication Systems Inc.Licensed Tester : Tiffany Patrick Firm Address : PO Box 1267 BPAT License # : BP0018610 Firm Phone No : 972-621-8700 License Expiration Date : 08/23/2021 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.