Loading...
157SouthMooreRd_75019_89422 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-23047 Test Date: 1/27/2020 Result: Passed Reason for Test: Existing Account Name : Arts Center Address of Assembly : 157 South Moore Rd : Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Double Check Valve Frequency :Annual What does this serve? FireLine Manufacturer :Hersey ByPass : Model No :DDC2 ByPass : Size :4 ByPass : Serial No :9813950 ByPass : Location At:NW corner of bldg in vault Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Type II Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Bypass Check Air Inlet Check Valve Initial Test Date:1/27/2020 Time:9:45 AM Held at 1.8 psid Closed Tight Leaked Held at 2 psid Closed Tight Leaked Opened at psid Did not open Held at psid Closed Tight Leaked Opened at psid Did not open Did it fully open Yes No Held at psid Leaked Repairs and Materials Used ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Held at psid Closed Tight Leaked Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: MID-WEST Model: 845-3 Serial No.: 01200225 Date Tested for Accuracy: 1/6/2020 Remarks : Firm Name : Texas Fire &Sound Licensed Tester : Jerry Watson Firm Address : 10451 brockwood Road BPAT License # : BP0003334 Firm Phone No : (214)390-9282 License Expiration Date : 10/07/2020 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.