Loading...
951BethelRd_75019_99691 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-21265 Test Date: 4/27/2020 Result: Passed Reason for Test: Existing Account Name : US Postal Service Address of Assembly : 951 Bethel Rd : Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? FireLine Manufacturer :Watts ByPass : Model No :009 ByPass : Size :1 ByPass : Serial No :59725 ByPass : Location At:small cooling tower Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Type II Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Bypass Check Air Inlet Check Valve Initial Test Date:4/27/2020 Time:1:00 PM Held at 9 psid Closed Tight Leaked Held at 8.8 psid Closed Tight Leaked Opened at 3 psid Did not open Held at psid Closed Tight Leaked Opened at psid Did not open Did it fully open Yes No Held at psid Leaked Repairs and Materials Used ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Held at psid Closed Tight Leaked Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: Apollo Model: 40-200-TK5U Serial No.: 09142374 Date Tested for Accuracy: 11/22/2019 Remarks : Firm Name : Cintas Fire Protection Licensed Tester : James Steven Mitchell Firm Address : 751 109th St.BPAT License # : BP0010924 Firm Phone No : 817-640-2223 License Expiration Date : 11/12/2022 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.