Loading...
110WSandyLake_75019_98999 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-22049 Test Date: 4/12/2020 Result: Passed Reason for Test: Existing Account Name : Sprouts Address of Assembly : 110 W Sandy Lake : Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Domestic Manufacturer :Watts ByPass : Model No :009 ByPass : Size :1/2 ByPass : Serial No :A84426 ByPass : Location At:mop sink Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Type II Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Bypass Check Air Inlet Check Valve Initial Test Date:4/12/2020 Time:12:00 PM Held at 7.1 psid Closed Tight Leaked Held at 7.1 psid Closed Tight Leaked Opened at 2.5 psid Did not open Held at psid Closed Tight Leaked Opened at psid Did not open Did it fully open Yes No Held at psid Leaked Repairs and Materials Used ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Held at psid Closed Tight Leaked Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: APOLLO Model: 40-200-TK5U Serial No.: 10051040 Date Tested for Accuracy: 1/6/2020 Remarks : Firm Name : AUTOMATIC SPRINKLER OF TEXAS,INC Licensed Tester : LARRY WHEELER Firm Address : PO BOX 382091 BPAT License # : BP0009464 Firm Phone No : 972-670-2662 License Expiration Date : 12/19/2020 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.