NEW_455NFREEPORTPKWY_75019_104654 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT
Name of PWS:Coppell
PWS I.D.:0570040
Address:816 S.Coppell Road
Coppell,Texas 75019
Phone:972-462-5150
Contact Person:Jerry Davis
Catalog No: TXTCOP-80463
Test Date: 6/5/2020
Result: Passed
Reason for Test: New
Account Name : QUICK TRIP
Address of Assembly : 455 N FREEPORT PKWY : Address Type : Commercial
Inspection
The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within
acceptable parameters.
Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Domestic
Manufacturer :Watts ByPass : Model No :LF009M2QT ByPass : Size :1 ByPass : Serial No :193112 ByPass :
Location At:Riser room
Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes
Is the assembly installed on a non-potable water supply (auxiliary)?No
Reduced Pressure Principle Assembly Type II
Assembly
Pressure Vacuum Breaker
Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly
1st check 2nd check Relief Valve Bypass Check Air Inlet Check Valve
Initial Test
Date:6/5/2020
Time:2:00 PM
Held at 8.6 psid
Closed Tight
Leaked
Held at 8.6 psid
Closed Tight
Leaked
Opened at 3.3
psid
Did not open
Held at psid
Closed Tight
Leaked
Opened at psid
Did not open
Did it fully open
Yes No
Held at psid
Leaked
Repairs and
Materials Used **
Test After Repair
Date:
Time:
Held at psid
Closed Tight
Leaked
Held at psid
Closed Tight
Leaked
Opened at psid Held at psid
Closed Tight
Leaked
Opened at psid Held at psid
***2nd check:numeric reading required for DCVA only
Test gauge used: Potable Make: Mid-West Instrument Model: 845-5 Serial No.: 08191248
Date Tested for Accuracy: 8/14/2019
Remarks :Initial test was fail from leaking checks,cleaned debris and retested for passing test.
Firm Name : Wise Water Solutions Licensed Tester : David Rodenburgh
Firm Address : 309 W Hobbs st BPAT License # : BP0019401
Firm Phone No : (817)988-3791 License Expiration Date : 08/13/2022
The above is certified to be true at the time of testing.
* Test Records must be kept for at least three years.[30 TAC §290.46(B)]
** Use only manufacturer's replacement parts.