COPPELL FIRE PREVENTION
PLAN REVIEW COMMENTS
FIRE LINES
COPPELL CROSSING SHOPPING CENTER
JULY 24, 2000
THE ABOVE LISTED PLANS HAVE BEEN DENIED FOR THE FOLLOWING REASON(S):
The Fire Department Connection (FDC) can not be located on the building. Locate between 3 - 6
from a fire lane and within 50 feet from a fire hydrant. Locate on the same side of the fire lane as
the fire hydrant.
The line from the FDC to the sprinkler riser shall be isolated from any hydrant through the use of
an approved check valve. At no time shall the FDC increase the pressure to any fire hydrant.