Loading...
Coppell Cross L5-CS000929~Michael Martin - Coppell C~0ssing ~ .... From: Travis Crump To: Michael Martin Date: Fri, Sep 29, 2000 9:45 AM Subject: Coppell Crossing Mike, It is okay to release Coppell Crossing IV and V. The Fire Department concerns have been addressed. Thanks Travis COPPELL FIRE PREVENTION PLAN REVIEW COMMENTS FIRE LINES COPPELL CROSSING SHOPPING CENTER JULY 24, 2000 THE ABOVE LISTED PLANS HAVE BEEN DENIED FOR THE FOLLOWING REASON(S): The Fire Department Connection (FDC) can not be located on the building. Locate between 3 - 6 from a fire lane and within 50 feet from a fire hydrant. Locate on the same side of the fire lane as the fire hydrant. The line from the FDC to the sprinkler riser shall be isolated from any hydrant through the use of an approved check valve. At no time shall the FDC increase the pressure to any fire hydrant.