Coppell Cross L5-CS000706July 6, 2000 COPPELL. TEXAS 75019 P.O. Box 478 , Coppell. Texas 75019 972-462-0022 Russell E. Spiars, P.E. Dunnaway Associates, Inc. 2351 West N.W. Highway, Suite 3280 Dallas, Texas 75220 RE: Coppell Crossing Addition, Lot 5, Block 1 Dear Mr. Spiars: The City of Coppell has reviewed the referenced plans and has the following comments to offer: Provide a dimension control plan sheet. Will the proposed 2' wall on the east side of the building be constructed with the initial site development.'? If so, provide a detail. The proposed wall should be a minimum of 2' offthe curb. On the grading plan provide a note that the existing manhole for the storm sewer to be adjusted to match the proposed paving. Should consider providing bollards in the middle of the proposed 5' curb opening, 2' of the curb. Offsite grading could be necessary to ensure that the water proposed to drain through the curb opening will drain south towards the existing box culvert. This will require a letter of permission to grade from TXU. All fire hydrant locations must be approved by the Fire Marshal, Travis Crump. He can be reached at 972-304-3503. All public meters must be installed adjacent to MacArthur Blvd. It is my understanding that service lines have been constructed to allow for future meters for this site to be set adjacent to MacArthur Blvd. There are various other minor comments throughout the plans. When all comments have been addressed, please return these marked plans and two sets of revised plans to the City for review. If you have any questions, please contact me at (972) 304-368 l. Sincerely, Michael A. Martin, P.E. Assistant City Engineer