Loading...
NEW_150WStateHwy121_75019_115558 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-87095 Test Date: 8/21/2020 Result: Passed Reason for Test: New Account Name : Hat Creek Burger Company Address of Assembly : 150 W State Hwy 121 : Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Carbonator Manufacturer :Watts ByPass : Model No :SS009M3 ByPass : Size :1/2"ByPass : Serial No :26939 ByPass : Location At:Kitchen Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Type II Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Bypass Check Air Inlet Check Valve Initial Test Date:8/21/2020 Time:7:25 AM Held at 9.3 psid Closed Tight Leaked Held at 9.1 psid Closed Tight Leaked Opened at 4.2 psid Did not open Held at psid Closed Tight Leaked Opened at psid Did not open Did it fully open Yes No Held at psid Leaked Repairs andMaterialsUsed ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Held at psid Closed Tight Leaked Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: Mid-West Model: 845-5 Serial No.: 11161416 Date Tested for Accuracy: 2/4/2020 Remarks : Firm Name : North Texas Backflow Licensed Tester : John Davis Firm Address : P.O.Box 597 BPAT License # : BP0003132 Firm Phone No : 469-231-6623 License Expiration Date : 06/12/2023 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.