Loading...
NEW_149W_StateHwy121Bypass_75019_118098 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-46480 Test Date: 9/15/2020 Result: Passed Reason for Test: New Account Name : Current Water Customer Address of Assembly : 149 W.State Hwy 121 Bypass : Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Irrigation Manufacturer :Watts ByPass : Model No :LF009M3QT ByPass : Size :3/4 ByPass : Serial No :280607 ByPass : Location At:WATER METER CLOSET Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?Yes Reduced Pressure Principle Assembly Type II Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Bypass Check Air Inlet Check Valve Initial Test Date:9/15/2020 Time:2:00 PM Held at 8.8 psid Closed Tight Leaked Held at 8.8 psid Closed Tight Leaked Opened at 3 psid Did not open Held at psid Closed Tight Leaked Opened at psid Did not open Did it fully open Yes No Held at psid Leaked Repairs andMaterialsUsed ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Held at psid Closed Tight Leaked Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Non-Potable Make: Midwest Model: 845-5 Serial No.: 11130531 Date Tested for Accuracy: 1/3/2020 Remarks : Firm Name : .01 Accuracy Backflow Licensed Tester : Brian Cox Firm Address : P.O.Box 6832 BPAT License # : BP0017066 Firm Phone No : 972.699.7156 License Expiration Date : 02/23/2022 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.