Loading...
CF-Coppell Rd SC-LR011203 (2)Hooper Engineering Laboratories, Construction Materials Testing Inc. REPORT OF CONCRETE TESTS JOB NO.: 01.1054 CLIENT: Texas Unified Constructors, Inc. DATE: 3 December 2001 PROJECT: Field Service Offices & Maint. Fac., Coppell SUPPLIER: Lattimore LOCATION OF POUR SET 1: Grade beam for service center building, grid C to C.6 between 7 & 8 lines LOCATION OF POUR SET 2: SAMPLE DATA: SET I SET 2 MIX NO. Truck No. 806 Cement Ticket No. 6165256 Flyash Time Batched 9:13am Sand Time Sampled 10:05am in. Concrete Temp. (ASTM C1064i 65°F 1.0 in. Air Content (ASTM C231) Water Unit Weight (ASTM C138) Admix #1 Admix //2 AEA 54 COMPRESSIVE STRENGTH TESTS (ASTM C39) (Standard 6 inch x 12 inch cylinder) Cylinder Slump Age Test Number Inches Days Date (ASTM C143) Total Load Compressive Required Pounds Strength 28-Day psi Strength 69 6.25 7 12/10/01 70 6.25 28 12/31/01 71 6.25 28 12/31/0i 72 6.25 56 01/28/02 96,6O0 342O 28-Day Average 3000 TECHNICIAN: DISTRIBUTION: RJW (9:15am-11:15am) (3) City of Coppell (1) Vidaud & Associates (1) Doyle Engineering Group (1) Texas Unified Constructors, Inc. 2870 Walnut Hill Lane Dallas, Texas 75229 (214) 351-6419 Fax (214) 351-5148