NEW_110WSandyLakeRd_Ste_150_75019_136412 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT
Name of PWS:Coppell
PWS I.D.:TX0570040
Address:816 S.Coppell Road
Coppell,Texas 75019
Phone:972-462-5150
Contact Person:Jerry Davis
Catalog No: TXTCOP-104246
Test Date: 1/21/2021
Result: Passed
Reason for Test: New
Account Name : TEA LATTE BAR
Address of Assembly : 110 W Sandy Lake Rd.Ste.150 : Address Type : Commercial
Inspection
The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within
acceptable parameters.
Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Domestic
Manufacturer :Watts ByPass : Model No :LF009QT ByPass : Size :1/2 ByPass : Serial No :275144 ByPass :
Location At:BEHIND ICE MACHINE
Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes
Is the assembly installed on a non-potable water supply (auxiliary)?No
Reduced Pressure Principle Assembly Type II
Assembly
Pressure Vacuum Breaker
Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly
1st check 2nd check Relief Valve Bypass Check Air Inlet Check Valve
Initial Test
Date:1/21/2021
Time:11:25 AM
Held at 7.8 psid
Closed Tight
Leaked
Held at 8.1
psid
Closed Tight
Leaked
Opened at 3.6
psid
Did not open
Held at psid
Closed Tight
Leaked
Opened at psid
Did not open
Did it fully open
Yes No
Held at psid
Leaked
Repairs andMaterialsUsed **
Test After Repair
Date:
Time:
Held at psid
Closed Tight
Leaked
Held at psid
Closed Tight
Leaked
Opened at psid Held at psid
Closed Tight
Leaked
Opened at psid Held at psid
***2nd check:numeric reading required for DCVA only
Test gauge used: Potable Make: Midwest Model: 845-5 Serial No.: 11130531
Date Tested for Accuracy: 1/6/2021
Remarks :
Firm Name : .01 Accuracy Backflow Licensed Tester : Brian Cox
Firm Address : P.O.Box 6832 BPAT License # : BP0017066
Firm Phone No : 972.699.7156 License Expiration Date : 02/23/2022
The above is certified to be true at the time of testing.
* Test Records must be kept for at least three years.[30 TAC §290.46(B)]
** Use only manufacturer's replacement parts.