Windsor Estates-LR011010CONCRETE COMPRESSIVE STRENGTH TEST Report Number: Service Date: 94001501.0027 September 11, 2001 Client: Excel Group, Inc. Attn: Bryan Peck 2639 Walnut Hill Ln #218 Dallas TX 75229 .eport~Nl~e.; October 10]~j2.001 Projejlt: Windsor Fstat~ Project Number: 94001501 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Material Information Specified Strength: 3000 psi @ 28 Days Batch Time: 1:04pm Supplier: TXI Truck No: 65 Mix I.D. No.: 8206 Plant: 41 Ticket No: 2877138 Sample Information Sample Time: 1:35pm Date Cast: September 11,2001 Technician: HBC Fort Worth Office Weather Conditions: Clear Accumulative Yards: 20 Placement Method: Direct Discharge Sample Locations: See placement location Placement Location: Paving Field Test Data Test Result Specification Test Method Slump, inches: 4.00 3-5 ASTM C-143 Air Content, %: 4.5 3-6 ASTM C-231 Concrete Temperature,° F: 87 ASTM C1064 Ambient Temperature, o F: 80 ASTM C-1064 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) I 1 6.00 28.27 09/18/2001 7 138,250 4,890 1 2 6.00 28.27 09/18/2001 7 147,880 5,230 Average 5,060 1 3 6.00 28.27 10/09/2001 28 170,400 6,030 1 4 6.00 28.27 10/09/2001 28 170,290 6,020 Average 6,030 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 2 o~<Lwmo~,~, CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94001501.0027 Service Date: September 11, 2001 Client: Excel Group, Inc. Attn: Bryan Peck 2639 Walnut Hill Ln #218 Dallas TX 75229 Report Date: October 10, 2001 Project: Windsor Estates Coppell, Texas Project Number: 94001501 89Ol Carpenter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Material Information Specified Strength: 3000 psi @ 28 Days Batch Time: 2:45pm Supplier: TXI Truck No: 713 Mix I.D. No.: 8206 Plant: 41 Field Test Data Test Ticket No: Sample Information Sample Time: Date Cast: September 11,2001 Technician: HBC Fort Worth Office Weather Conditions: Clear Accumulative Yards: 100 Placement Method: Direct Discharge Sample Locations: 15' S of N line/10' E Placement Location: See page 1 Result Specification Test Method Slump, inches: 4.00 Air Content, %: 5.0 Concrete Temperature, o F: 78 Ambient Temperature, o F: 82 Plastic Unit Weight, pcf: Laboratory Test Data 3-5 ASTM C-143 3-6 ASTM C-231 ASTM C1064 ASTM C-1064 Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 2 I 6.00 28.27 09/18/2001 7 132,900 4,700 2 2 6.00 28.27 09/18/2001 7 135,410 4,790 Average 4,750 2 3 6.00 28.27 10/09/2001 28 169,890 6,010 2 4 6.00 28.27 10/09/2001 28 159,430 5,640 Average 5,830 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: HBC Fort Worth Office ~B~~~'/~ ~ "~~n Report Distribution: c. (1) Excel Group, Inc. (1) City of Coppell - Engr Dept Reviewed by: (1) city of Coppell - Bldg Insp ~ ~ J. Cleveland, P.E. Senior Project Engineer The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 of 2 ~ '~CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94001501.0026 Service Date: September 11, 2001 Client: Excel Group, Inc. Attn: Bryan Peck 2639 Walnut Hill Ln #218 Dallas TX 75229 Material Information Specified Strength: 3000 psi @ 28 Days Batch Time: 7:55am Supplier: TXI Truck No: 67 Mix I.D. No.: 8204SF Plant: 41 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Ticket No: 2976559 .<eport Date: October 10, 2001 Project: Windsor Estates Texas t/~ Coppell, J P~umber: ~40~/'~001 Sample Information Sample Time: 8:30am Technician: Roy Montgomery Weather Conditions: Clear Accumulative Yards: 40 Placement Method: Sample Locations: Sta. 5+90 Placement Location: Paving- DeForest Result Specification 3.50 3.0 Max 87 73 Set Specimen Diameter Area Date No. ID (inches) (sq. inches) Tested 1 1 6.00 28.27 09/18/2001 1 2 6.00 28.27 09/18/2001 I 3 6.00 28.27 10/09/2001 I 4 6.00 28.27 10/09/2001 Services - 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Date Cast: September 11,2001 Test Method ASTM C-143 ASTM C-173 ASTM C1064 ASTM C-1064 Age at Maximum Compressive Test Load Strength (days) (lbs) (psi) 7 94,410 3,340 7 91,360 3,230 Average 3,290 28 113,030 4,000 28 115,940 4,100 Average 4,050 Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracen. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 4 CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94001501.0026 Service Date: September 11,2001 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Client: Excel Group, Inc. Attn: Bryan Peck 2639 Walnut Hill Ln #218 Dallas TX 75229 Report Date: October 10, 2001 Project: Windsor Estates Coppell, Texas Project Number: 94001501 Material Information Specified Strength: 3000 psi @ 28 Days Batch Time: 9:07am Supplier: TXI Truck No: 67 Mix I.D. No.: 8204SF Plant: 41 Ticket No: 2976674 Sample Information sample Time: 9:35am Date Cast: September 11,2001 Technician: Roy Montgomery Weather Conditions: Clear Accumulative Yards: 120 Placement Method: Sample Locations: Sta. 4+60 Placement Location: See page 1 Field Test Data Test Result Specification Test Method Slump, inches: 3.00 3.0 Max ASTM C-143 Air Content, %: ASTM C-173 Concrete Temperature,° F: 86 ASTM C1064 Ambient Temperature, o F: 82 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 2 1 6.00 28.27 09/18/2001 7 104,480 3,690 2 2 6.00 28.27 09/18/2001 7 103,840 3,670 Average 3,680 2 3 6.00 28.27 10/09/2001 28 128,310 4,540 2 4 6.00 28.27 10/09/2001 28 124,240 4,390 Average 4,470 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 of 4 ~<~w~., CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94001501.0026 Service Date: September 11, 2001 Client: Excel Group, Inc. Attn: Bryan Peck 2639 Walnut Hill Ln #218 Dallas TX 75229 Report Date: October 10, 2001 Project: Windsor Estates Coppell, Texas Project Number: 94001501 8~Ol Cacpanter F~., Suite #100 Dallas, Texas 7§247 (214) Material Information Specified Strength: 3000 psi @ 28 Days Batch Time: 10:39am Supplier: TXI Truck No: 39 Mix I.D. No.: 8204SF Plant: 41 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Ticket No: 2976839 Sample Information sample Time: 11:00am Date Cast: September 11,2001 Technician: Roy Montgomery Weather Conditions: Clear Accumulative Yards: 220 Placement Method: Sample Locations: 2+90 Placement Location: See page 1 Result Specification Test Method 2.50 3.0 Max ASTM C-143 4.9 ASTM C-173 77 ASTM C1064 80 ASTM C-1064 Age at Maximum Compressive Date Test Load Strength Tested (days) (lbs) (psi) 28.27 09/18/2001 7 95,140 3,360 28.27 09/1812001 7 100,310 3,550 Average 3,460 28.27 10/09/2001 28 123,860 4,380 28.27 10/09/2001 28 125,210 4,430 Average 4,410 Set Specimen Diameter Area No. ID (inches) (sq. inches) 3 1 6.00 3 2 6.00 3 3 6.00 3 4 6.00 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 3 of 4 o~<~,~,~,. CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94001501.0026 Service Date: September 11, 2001 Client: Excel Group, Inc. Attn: Bryan Peck 2639 Walnut Hill Ln #218 Dallas TX 75229 Report Date: October 10, 2001 Project: Windsor Estates Coppell, Texas Project Number: 94001501 89Ol Carpenter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Material Information Specified Strength: 3000 psi @ 28 Days Batch Time: 11:46am Supplier: TXI Truck No: 67 Mix I.D. No.: 8204SF Plant: 41 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Set Specimen Diameter No. ID (inches) Ticket No: 2976979 Sample Information Sample Time: 12:35pm Date Cast: September 11, 2001 Technician: Roy Montgomery Weather Conditions: Clear Accumulative Yards: 330 Placement Method: Sample Locations: Sta. 0+90 Placement Location: See page 1 Result Specification Test Method 4 I 6.00 4 2 6.00 4 3 6.00 4 4 6.00 Services - 2.50 3.0 Max ASTM C-143 5.0 ASTM C-173 90 ASTM C1064 ASTM C-1064 Age at Maximum Compressive Area Date Test Load Strength (sq. inches) Tested (days) (lbs) (psi) 28.27 09/18/2001 7 103,370 3,660 28.27 09/18/2001 7 109,490 3,870 Average 3,770 28.27 10/09/2001 28 129,360 4,570 28.27 10/09/2001 28 125,280 4,430 Average 4,500 Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Roy Montgomery Report Distribution: (1) Excel Group, Inc. (1) City of Coppell - Engr Dept (1) City of Coppell ~ Bldg Insp Reviewed by: ng, Inc. Edc J. Cleveland, P.E. Senior Project Engineer The tests were performed in general accordance with applicable ASTM, MSHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 4 of 4