Westbury Manor-LR 990505FUGRO SOUTH, INC. 2880 Virgo Lane: Dallas, Texas 75229 Ph (972) 484-8301; Fax (972) 620-7328 COMPRESSIVE STRENGTH OF CONCRETE REPORT CLIENT: Ryland Homes REPORT DATE: May 5, 1999 PROJECT: Castlebury Drive, Coppell, Texas PROJECT NO: 0791-2019 SAMPLE DATE: April 6, 1999 CONTRACTOR: Site TICKET NO.: CONCRETE SUPPLIER: On Site Plant AMBIENT TEMP. (°F): 65 PLANT/TRUCK: CONCRETE TEMP. (°F) (ASTM C-1064): 68 MIX ID NUMBER: TIME BATCHED: 10:35 AIR (%) (ASTM C-231): TIME SAMPLED: 10:50 WATER ADDED (gal): 0 WEATHER CONDITION: Sunny SLUMP (in.) (ASTM C.t43): 5.50 LOCATION OF PLACEMENT: Pavement, sampled at station 2+50, alley CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS Standard 6" x 12", 28.27 square inches TOTAL COMPRESSIVE SPECIFIED COMPRESSIVE CYLINDER AGE DATE LOAD STRENGTH STRENGTH NUMBER (days) TESTED (pounds) (psi) (psi) CBC 5 7 04/13/99 82000 2900 3600/28 days . CRC 8 28 05/04/99 105000 3710 CBC 7 28 05/04/99 104000 3680 CBC 8 Hold Fracture mode is (A) unless otherwise noted Specifications: Making & ASTM C-31 Testing ASTM C-143, Typesof ~ ~"~ r~ ~-'-] Cudng: Methods: ASTM C-39 Fracture: AF',J I/__.~ I/I I lB C D REMARKS: Technician: Mike Flute FUGRO SOUTH INC. Reviewed By: SMH/rm Distribution: Ryland Homes - Mark Gaines., City of Coppell - Larry Davis / Goodwin & Marshall - David Gregory Site Concrete - Melissa Uselding FUGRO SOUTH, INC. 2880 Virgo Lane; Dallas. Texas 75229 Ph (972) 484-8301; Fax (972) 620-7328 COMPRESSIVE STRENGTH OF CONCRETE REPORT CLIENT: Ryland Homes REPORT DATE: May 5, 1999 PROJECT: Castlebury Drive, Coppell, Texas PROJECT NO: 0791-2019 SAMPLE DATE: April 6, 1999 CONTRACTOR: Site TICKET NO.: CONCRETE SUPPLIER: On Site Plant AMBIENT TEMP. (°F): 75 PLANT/TRUCK: CONCRETE TEMP. (°F) (ASTM C.10~4): 81 MIX ID NUMBER: TIME BATCHED: 12:10 AIR (%) (ASWa C-231): TIME SAMPLED: 12:35 WATER ADDED (gal): 0 WEATHER CONDITION: Sunny SLUMP (in.) (ASTM C-143): 7 LOCATION OF PLACEMENT: Pavement, Castlebury Court, sampled at station 0+25 CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS Standard 6" x 12", 28.27 square inches TOTAL COMPRESSIVE SPECIFIED COMPRESSIVE CYLINDER AGE DATE LOAD STRENGTH STRENGTH NUMBER (days) TESTED (pounds) (psi) (psi) CBC 9 7 04/13/99 76000 2690 3600/28 days CBC 10 28 05/04199 103000 3640 CBC 11 28 05t04/99 106000 3750 Fracture mode is (A) unless othen~ise noted Specifications: Making & ASTM C-31 Testing ASTM C-143. Typesof [~] [~] ~ ~ Cudng: Methods: ASTM C-39 Fracture: A e c D REMARKS: Technician: Mike Flute FUGRO SOUTH INC. Reviewed By: ~ SMH/rm Distribution: Ryland Homes - Mark Gaines City of Coppell - Larry Davis Goodwin & Marshall - David Gregory Site Concrete - Melissa Uselding