137W_StateHwy121Bypass_75019_112613 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person: Catalog No: TXTCOP-46481 Test Date: 7/27/2020 Result: Passed Reason for Test: Existing Account Name : Current Water Customer Address of Assembly : 137 W.State Hwy 121 Bypass : Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Domestic Manufacturer :Watts ByPass : Model No :LF009M2QT ByPass : Size :2 ByPass : Serial No :128195 ByPass : Location At:#D Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Type II Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Bypass Check Air Inlet Check Valve Initial Test Date:7/27/2020 Time:1:00 PM Held at 9 psid Closed Tight Leaked Held at 8.4 psid Closed Tight Leaked Opened at 3 psid Did not open Held at psid Closed Tight Leaked Opened at psid Did not open Did it fully open Yes No Held at psid Leaked Repairs and Materials Used ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Held at psid Closed Tight Leaked Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: Mid-West Model: 845-5 Serial No.: 01181926 Date Tested for Accuracy: 1/22/2020 Remarks : Firm Name : Hunter Fire Protection Licensed Tester : Jeff Denney Firm Address : P.O.Box 2580 BPAT License # : BP0014844 Firm Phone No : 469-366-8311 License Expiration Date : 02/06/2022 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.