Freeport NIP(2.2)-LR011227CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94011204.0074
Service Date: November 27, 2001
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Client: TNA Nodh American, Inc.
Attn: Terry Raley
1321 Valwood Parkway, Suite 440
Carmllton TX 75006
Report Date: December 27, 2001
Project: Sales Office & Warehouse Fac.
Coppell, Texas
Project Number: 94011204
Material Information
Specified Strength: 3600 psi ~ 28 Days
Batch Time: 6:05am Plant: 41
Supplier: TXI
Truck No: 837
Mix I.D. No.: 8273
Water Added Onsite Before Test: 10 Gallons
Field Test Data
Test
Ticket No: 3030874
Sample Information
sample Time: 7:16am Date Cast: November 27, 2001
Technician: Barry Cuble
Weather Conditions: Cloudy, cool, windy
Accumulative Yards: 40
Placement Method: Direct Discharge
Sample Locations: See placement location
Placement Location: Paving- N firelane & parking, bldg. slab
leaveout: Lines A/3-6
Sample location: 12' S of N curb, 25' E of
Royal Lane (See attached sketch)
Result Specification Test Method
Slump, inches: 5.75 3-5 ASTM C-143
Air Content, %: 5.1 3-6 ASTM C-231
Concrete Temperature,° F: 59 ASTM C1064
Ambient Temperature, 0 F: 40 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
1 1 6.00 28.27 12/04/2001 7 108,340 3,830
1 2 6.00 28.27 12/04/2001 7 109,700 3,880
Average 3,860
1 3 6.00 28.27 12/25/2001 28 135,190 4,780
1 4 6.00 28.27 12/25/2001 28 135,550 4,790
Average 4,790
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not bo reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not nesessadly indicative of the properties of ether apparently similar or identical
materials.
Page 1 of 5
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94011204.0074
Service Date: November 27, 2001
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Client: TNA North American, Inc.
Attn: Terry Raley
1321 Valwood Parkway, Suite 440
Carrollton TX 75006
Report Date: December 27, 2001
Project: Sales Office & Warehouse Fac.
Coppell, Texas
Project Number: 94011204
Material Information
Specified Strength: 3600 psi ~ 28 Days
Batch Time: 7:35am
Supplier: TXI
Truck No: 65
Mix I.D. No.: 8273
Plant: 41
Field Test Data
Test
Ticket No: 3030989
Sample Information
sample Time: 8:09am Date Cast: November 27, 2001
Technician: Barry Cuble
Weather Conditions: Partly cloudy, cool, windy
Accumulative Yards: 90
Placement Method: Direct Discharge
Sample Locations: See placement location
Placement Location: See page 1
Sample location: 120' E of W, 30' N of S
curb
Result Specification Test Method
Slump, inches: 5.50 3-5 ASTM C-143
Air Content, %: 3-6 ASTM C-231
Concrete Temperature,° F: 59 ASTM C1064
Ambient Temperature, o F: 40 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
2 1 6.00 28.27 12/04/2001 7 107,800 3,810
2 2 6.00 28.27 12/04/2001 7 106,710 3,770
Average 3,790
2 3 6.00 28.27 12/25/2001 28 143,210 5,060
2 4 6.00 28.27 12/25/2001 28 148,420 5,250
Average 5,160
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This rupert is exclusively for the usa of the client
indicated above and shall not bo reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 2 of 5
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94011204.0074
Service Date: November 27, 2001
89Ol Carpenter Frw¥., Suite #100
Dallas, Texas 75247
(214) 630-1010
Client: TNA North American, Inc.
Attn: Terry Raley
1321 Valwood Parkway, Suite 440
Carrollton TX 75006
Report Date: December 27, 2001
Project: Sales Office & Warehouse Fac.
Coppell, Texas
Project Number: 94011204
Material Information
Specified Strength: 3600 psi ~ 28 Days
Batch Time: 8:19am
Supplier: TXI
Truck No: 68
Mix I.D. No.: 8273
Plant: 41
Ticket No: 3031046
Sample Information
Sample Time: 10:13am Date Cast: November 27, 2001
Technician: Barry Cuble
Weather Conditions: Cloudy, cool
Accumulative Yards: 140
Placement Method: Direct Discharge
Sample Locations: 25' N of S curb, 15' W of E
Placement Location: See page 1
Field Test Data
Test Result Specification Test Method
Slump, inches: 6.00 3-5 ASTM C-143
Air Content, %: 5.2 3-6 ASTM C-231
Concrete Temperature,o F: 59 ASTM C1064
Ambient Temperature, o F: 39 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
3 1 6.00 28.27 12/04/2001 7 96,110 3,400
3 2 6.00 28.27 12/04/2001 7 94,710 3,350
Average 3,380
3 3 6.00 28.27 12/25/2001 28 124,000 4,390
3 4 6.00 28.27 12/25/2001 28 128,800 4,550
Average 4,470
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were pedormed in general accordance with applicable ASTM, AASHTO, or DOT test methods. Tills report is exclusively for the use of the client
indicated above and shetl net be reproduced except in full without the written approval of Terracon. Test resutis transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94011204.0074
Service Date: November 27, 2001
8901 Carpenter Fi'wy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Client: TNA North American, Inc.
Attn: Terry Raley
1321 Valwood Parkway, Suite 440
Carrollton TX 75006
Report Date: December27, 2001
Project: Sales Office & Warehouse Fac.
Coppell, Texas
Project Number: 94011204
Material Information
Specified Strength: 3600 psi (~ 28 Days
Batch Time: 8:54am
Supplier: TXI
Truck No: 836
Mix I.D. No.: 8273
Plant: 41
Field Test Data
Test
Ticket No: 3031100
Sample Information
sample Time: 11:44am Date Cast: November 27, 2001
Technician: Barry Cuble
Weather Conditions: Cloudy, cool, light winds
Accumulative Yards: 180
Placement Method: Direct Discharge
Sample Locations: See placement location
Placement Location: See page 1
Sample location: 20' N of S curb, 10' E of
bldg.
Result Specification Test Method
Slump, inches: 4.50 3-5 ASTM C-143
Air Content, %: 4.6 3-6 ASTM C-231
Concrete Temperature,° F: 63 ASTM C1064
Ambient Temperature, 0 F: 39 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
4 1 6.00 28.27 12/04/2001 7 108,310 3,830
4 2 6.00 28.27 12/04/2001 7 113,360 4,010
Average 3,920
4 3 6.00 28.27 12/25/2001 28 138,620 4,900
4 4 6.00 28.27 12/25/2001 28 139,860 4,950
Average 4,930
Note:
Loads 150-180 were placed @ 2 1/2 hours old, contractor notified of time, temperature & slump prior to placement.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not he reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
CONCRETE COMPRESSIVE STRENGTH TEST
client: TNA North American, Inc.
Project Number:94011204
Report Number: 94011204.0074
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Barry Cuble
Report Distribution:
(1) TNA North Arcedcan, Inc.
(1) Carrell Poo~e & Yost Architecture
(1) R L Goedson Consulting Engineers
(1) Pacific Builders Inc
(1) FACServices Inc
(1) David Kent
(1) City of Coppell - Bldg Insp
(1) City of Coppetl - Constr Insp
Reviewed by:
~enng, Inc.
Eric J. Cleveland, P.E.
Senior Project Engineer
The tests were perfermed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terraces. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently sircilar or identical
materials.