Freeport NIP(2.2)-LR011227CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94011204.0074 Service Date: November 27, 2001 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Client: TNA Nodh American, Inc. Attn: Terry Raley 1321 Valwood Parkway, Suite 440 Carmllton TX 75006 Report Date: December 27, 2001 Project: Sales Office & Warehouse Fac. Coppell, Texas Project Number: 94011204 Material Information Specified Strength: 3600 psi ~ 28 Days Batch Time: 6:05am Plant: 41 Supplier: TXI Truck No: 837 Mix I.D. No.: 8273 Water Added Onsite Before Test: 10 Gallons Field Test Data Test Ticket No: 3030874 Sample Information sample Time: 7:16am Date Cast: November 27, 2001 Technician: Barry Cuble Weather Conditions: Cloudy, cool, windy Accumulative Yards: 40 Placement Method: Direct Discharge Sample Locations: See placement location Placement Location: Paving- N firelane & parking, bldg. slab leaveout: Lines A/3-6 Sample location: 12' S of N curb, 25' E of Royal Lane (See attached sketch) Result Specification Test Method Slump, inches: 5.75 3-5 ASTM C-143 Air Content, %: 5.1 3-6 ASTM C-231 Concrete Temperature,° F: 59 ASTM C1064 Ambient Temperature, 0 F: 40 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 1 1 6.00 28.27 12/04/2001 7 108,340 3,830 1 2 6.00 28.27 12/04/2001 7 109,700 3,880 Average 3,860 1 3 6.00 28.27 12/25/2001 28 135,190 4,780 1 4 6.00 28.27 12/25/2001 28 135,550 4,790 Average 4,790 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not bo reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not nesessadly indicative of the properties of ether apparently similar or identical materials. Page 1 of 5 CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94011204.0074 Service Date: November 27, 2001 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Client: TNA North American, Inc. Attn: Terry Raley 1321 Valwood Parkway, Suite 440 Carrollton TX 75006 Report Date: December 27, 2001 Project: Sales Office & Warehouse Fac. Coppell, Texas Project Number: 94011204 Material Information Specified Strength: 3600 psi ~ 28 Days Batch Time: 7:35am Supplier: TXI Truck No: 65 Mix I.D. No.: 8273 Plant: 41 Field Test Data Test Ticket No: 3030989 Sample Information sample Time: 8:09am Date Cast: November 27, 2001 Technician: Barry Cuble Weather Conditions: Partly cloudy, cool, windy Accumulative Yards: 90 Placement Method: Direct Discharge Sample Locations: See placement location Placement Location: See page 1 Sample location: 120' E of W, 30' N of S curb Result Specification Test Method Slump, inches: 5.50 3-5 ASTM C-143 Air Content, %: 3-6 ASTM C-231 Concrete Temperature,° F: 59 ASTM C1064 Ambient Temperature, o F: 40 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 2 1 6.00 28.27 12/04/2001 7 107,800 3,810 2 2 6.00 28.27 12/04/2001 7 106,710 3,770 Average 3,790 2 3 6.00 28.27 12/25/2001 28 143,210 5,060 2 4 6.00 28.27 12/25/2001 28 148,420 5,250 Average 5,160 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This rupert is exclusively for the usa of the client indicated above and shall not bo reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 of 5 CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94011204.0074 Service Date: November 27, 2001 89Ol Carpenter Frw¥., Suite #100 Dallas, Texas 75247 (214) 630-1010 Client: TNA North American, Inc. Attn: Terry Raley 1321 Valwood Parkway, Suite 440 Carrollton TX 75006 Report Date: December 27, 2001 Project: Sales Office & Warehouse Fac. Coppell, Texas Project Number: 94011204 Material Information Specified Strength: 3600 psi ~ 28 Days Batch Time: 8:19am Supplier: TXI Truck No: 68 Mix I.D. No.: 8273 Plant: 41 Ticket No: 3031046 Sample Information Sample Time: 10:13am Date Cast: November 27, 2001 Technician: Barry Cuble Weather Conditions: Cloudy, cool Accumulative Yards: 140 Placement Method: Direct Discharge Sample Locations: 25' N of S curb, 15' W of E Placement Location: See page 1 Field Test Data Test Result Specification Test Method Slump, inches: 6.00 3-5 ASTM C-143 Air Content, %: 5.2 3-6 ASTM C-231 Concrete Temperature,o F: 59 ASTM C1064 Ambient Temperature, o F: 39 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 3 1 6.00 28.27 12/04/2001 7 96,110 3,400 3 2 6.00 28.27 12/04/2001 7 94,710 3,350 Average 3,380 3 3 6.00 28.27 12/25/2001 28 124,000 4,390 3 4 6.00 28.27 12/25/2001 28 128,800 4,550 Average 4,470 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were pedormed in general accordance with applicable ASTM, AASHTO, or DOT test methods. Tills report is exclusively for the use of the client indicated above and shetl net be reproduced except in full without the written approval of Terracon. Test resutis transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94011204.0074 Service Date: November 27, 2001 8901 Carpenter Fi'wy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Client: TNA North American, Inc. Attn: Terry Raley 1321 Valwood Parkway, Suite 440 Carrollton TX 75006 Report Date: December27, 2001 Project: Sales Office & Warehouse Fac. Coppell, Texas Project Number: 94011204 Material Information Specified Strength: 3600 psi (~ 28 Days Batch Time: 8:54am Supplier: TXI Truck No: 836 Mix I.D. No.: 8273 Plant: 41 Field Test Data Test Ticket No: 3031100 Sample Information sample Time: 11:44am Date Cast: November 27, 2001 Technician: Barry Cuble Weather Conditions: Cloudy, cool, light winds Accumulative Yards: 180 Placement Method: Direct Discharge Sample Locations: See placement location Placement Location: See page 1 Sample location: 20' N of S curb, 10' E of bldg. Result Specification Test Method Slump, inches: 4.50 3-5 ASTM C-143 Air Content, %: 4.6 3-6 ASTM C-231 Concrete Temperature,° F: 63 ASTM C1064 Ambient Temperature, 0 F: 39 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 4 1 6.00 28.27 12/04/2001 7 108,310 3,830 4 2 6.00 28.27 12/04/2001 7 113,360 4,010 Average 3,920 4 3 6.00 28.27 12/25/2001 28 138,620 4,900 4 4 6.00 28.27 12/25/2001 28 139,860 4,950 Average 4,930 Note: Loads 150-180 were placed @ 2 1/2 hours old, contractor notified of time, temperature & slump prior to placement. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not he reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CONCRETE COMPRESSIVE STRENGTH TEST client: TNA North American, Inc. Project Number:94011204 Report Number: 94011204.0074 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Barry Cuble Report Distribution: (1) TNA North Arcedcan, Inc. (1) Carrell Poo~e & Yost Architecture (1) R L Goedson Consulting Engineers (1) Pacific Builders Inc (1) FACServices Inc (1) David Kent (1) City of Coppell - Bldg Insp (1) City of Coppetl - Constr Insp Reviewed by: ~enng, Inc. Eric J. Cleveland, P.E. Senior Project Engineer The tests were perfermed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terraces. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently sircilar or identical materials.