Amberpoint BP-LR020204WATER INJECTION OBSERVATION Date of Service: Client No.: Client: 02/04/02 3181 Transwestern Commercial Services 5001 Spring Valley Rd., Suite 600W Dallas, Texas 75244 Report No.: Project No.: Project: 94021029.0035 94021029 Ambe~point Building No. 1 Amberpoint Bus. Pk @ Coppell Coppell, Texas Location: Building Pad, lines 0.5 to Q and General Contractor: Hill & Wilkinson 5.5 to 11 injector: Jowell Procedure: On this date, a representative of HBC Engineering, Inc. observed the injection of water at this site. During the injection process, the following observations were recorded. Pass No.: 2nd No. of Probes: 4 Probe Length: 10 feet OBSERVATION SPECIFICATION Yes No N/A Surfactant added to each load. X Injection pressure 50 to 200 psi at manifold. X Injection downward in 18 inch intervals. X Total depth of injection was 10 feet. X Spacing of injection was 5 feet maximum. X In, iection to refusal at each location. X Comments: Technician: S. Long Report Distribution: (1) Transwestem Commercial Services (1) O'Bfien & Associates, Inc. (1) TcchniStmctures. Inc. (1) City of Coppcll - Constr. Insp. (1) City of Coppcll - Bldg. Insp. (1) Hill & Wilkinson, Ltd. ( 1 ) Halff Associates (1) State Farm Insurance Engineering, Inc. Eugene Harbour Principal 99SS This report is exclusively for the use of the client indicated above and shall not be reproduced in full without written approval of HBC Engineer ?? ?? ?? i i -4-- I_1_ I_ WATER INJECTION OBSERVATION Date of Service: Client No.: Client: 02/04/02 3181 Transwestem Commercial Services 5001 Spring Valley Rd., Suite 600W Dallas, Texas 75244 Report No.: Project No.: Project: 94021029.0034 94021029 Amberpoint Building No. 1 Amberpoint Bus. Pk @ Coppell Coppell, Texas Location: Building Pad General Contractor: Hill & Wilkinson Injector: Jowell Procedure: On this date, a representative of I-IBC Engineering, Inc. observed the injection of water at this site. During the injection process, the following observations were recorded. Pass No.: 3rd No. of Probes: 4 Probe Length: 12 feet OBSERVATION SPECIFICATION Yes No N/A Suffactant added to each load. X Injection pressure 50 to 200 psi at manifold. X Injection downward in 18 inch intervals. X Total depth of injection was 10 feet. X Spacing of injection was 5 feet maximum. X Injection to refusal at each location. X Comments: Technician: S. Campbell Report Distribution: (1) Transwe.stem Commercial Services (1) O'Brien & Associates, (1) TeclmiStxuetures, Inc, (1) City of Coppell - Constx. lnsp. (1) City of Coppell - Bldg. [nsp. (1) Hill & Wilkinson, Ltd. (1) Halff Associates (1) State Farm Insurance Engineering, Inc. Eugene Harbour Principal 99SS This report is exclusively for the use of the client indicated above and shall not be reproduced in full without written approval of HBC Engineer