Windsor Estates-LR010131CONCRETE COMPRESSIVE STRENGTH TEST
Client: Excel Group, Inc.
Attn: Bryan Peck
2639 Walnut Hill Ln #218
Dallas TX 75229
Report Date:
Project:
8,901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
(214) 630-1010
January 31, 2001
Windsor Estates
Coppell, Texas
Service Date: January 22, 2001
Project Number: 94001501
Report Number: 94001501.0003
Material Information
Specified Strength: 3500 psi ~ 28 Days
Batch Time: 9:27am
Supplier: TXI Plant: 41
Track No: 59 Ticket No: 2810659
Mix I.D. No.: 8204
Sample Information
sample Time: 9:51 am
Technician: Da[Tin Phillips
Weather Conditions: Sunny, clear
Accumulative Yards: 50
Placement Method: Direct discharge
Sample Locations: Sta. 2+04
Placement Location: St. James Street
Field Test Data
Test Result Specification
Slump, inches: 2.50 2 max
Air Content, %: 4.3 3-5
Concrete Temperature,° F: 51
Ambient Temperature, o F: 40
Plastic Unit Weight, pcf:
Laboratory Test Data Age at Maximum Compressive
Set Specimen Diameter Date Test Load Strength
No. ID (inches) Tested (days) (lbs) (psi)
2C 1 6.00 01/29/2001 7 107,550 3,800
2C 2 6.00 01129/2001 7 117,320 4,150
Average 3,980
2C 3 02/1912001 28
2C 4 02/19/2001 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM test methods. This report is exclusively fo~ the use of the clla~ indicated above
aed shall no~ he reproduced except in futl withoet the written approval of Terracon- Test results transmitted herein are only applicable to the aetual
samplas tested et the location(s) referenced and are not necessarily indicative of the properties of other apparently similar o~ identical materials.
CONCRETE COMPRESSIVE STRENGTH TEST
Client:
Excel Group, Inc.
Attn: Bryan Peck
2639 Walnut Hill Ln #218
Dallas TX 75229
Report Date:
Project:
8901 Carpenter Fn,/y., Suite #100
Dallas, Texas 75247
(214) 630-1010
January 31,2001
Windsor Estates
Coppell, Texas
Service Date: January 22, 2001
Project Number: 94001501
Report Number: 94001501.0003
Material Information
Specified Strength: 3500 psi ~ 28 Days
Batch Time: 11:48am
Supplier: TXI
Truck No: 38
Mix I.D. No.: 8204
Plant: 41
Ticket No: 2810897
Sample Information
Sample Time: 12:30pm
Technician: Darrin Phillips
Weather Conditions: Sunny, clear
Accumulative Yards: 250
Placement Method: Direct discharge
Sample Locations: Sta. 13+69
Placement Location: DeForest Street
Field Test Data
Test Result Specification
Slump, inches: 2.00 2 max
Air Content, %: 4.2 3-5
Concrete Temperature, o F: 59
Ambient Temperature, 0 F: 53
Plastic Unit Weight, pcf:
Laboratory Test Data Age at Maximum Compressive
Set Specimen Diameter Date Test Load Strength
No. ID (inches) Tested (days) (lbs) (psi)
3C I 6.00 01/29/2001 7 89,040 3,150
3C 2 6.00 01/29/2001 7 94,290 3,330
Average 3,240
3C 3 02/19/2001 28
3C 4 02/19/2001 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
TI~ tests were performed in general accordance with applicable ASTM test methods. This repert is exclusively for the use of the client indicated above
and shall noel be reproduced except in full witbout the wntten approval of Tenacon. Teat results transmitted herein are enly applicable to the actual
semp~se tested at the lscation(s) referenced and are not necessarily indicative of the properties of athef apparently sirniisr o,4 identical materials.
CONCRETE COMPRESSIVE STRENGTH TEST
Client: Excel Group, Inc.
Attn: Bryan Peck
2639 Walnut Hill Ln #218
Dallas TX 75229
Report Date:
Project:
8901 Carpenter Frwy., Suite #100
Dallas, Te~s 75247
(214) 630-1010
January 31,2001
Windsor Estates
Coppell, Texas
Service Date: January 22, 2001
Project Number: 94001501
Report Number: 94001501.0003
Material Information
Specified Strength: 3500 psi @ 28 Days
Batch Time: 1:34pm
Supplier: TXI
Truck No: 712
Mix I.D. No.: 8204
Plant: 41
Ticket No: 2811123
Sample Information
Sample Time: 2:21 pm
Technician: Dan'in Phillips
Weather Conditions: Sunny, clear
Accumulative Yards: 400
Placement Method: Direct discharge
Sample Locations: Sta. 11+52
Placement Location: DeForest Street
Field Test Data
Test Result Specification
Slump, inches: 2.50 2 max
Air Content, %: 4.4 3-5
Concrete Temperature, o F: 58
Ambient Temperature, o F: 56
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Date Test Load Strength
No. ID (inches) Tested (days) (lbs) (psi)
4C I 6.00 01/29/2001 7 90,330 3,190
4C 2 6.00 01/29/2001 7 84,410 2,980
Average 3,090
4C 3 02/19/2001 28
4C 4 02219/2001 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM test methods. This report is exclusively for the use of the client indicated above
and shall net be reproduced except in full without the written approval of Terracon. Teat results transmitted heroin are only applicable to the aetual
samples tested at the Iocofk~(s) referenced and are not necessarily indicative of the properties of ethe~ apparently similar or identical materials.
Page 3 of 5 "~"~
CONCRETE COMPRESSIVE STRENGTH TEST
Client: Excel Group, Inc.
Attn: Bryan Peck
2639 Walnut Hill Ln #218
Dallas TX 75229
Report Date:
Project:
8901 Carpenter Fn~y., Suite #100
Dallas, Texas 75247
(214) 630-1010
January 31,2001
Windsor Estates
Coppell, Texas
Service Date: January 22, 2001
Project Number: 94001501
Report Number: 94001501.0003
Material Information
Specified Strength: 3500 psi @ 28 Days
Batch Time: 3:14pm
Supplier: TXI
Track No: 66
Mix I.D. No.: 8204
Plant: 41
Ticket No: 2811307
Sample Information
Sample Time: 4:00pm
Technician: Darrin Phillips
Weather Conditions: Sunny, clear
Accumulative Yards: 550
Placement Method: Direct discharge
Sample Locations: Sta. 8+51
Placement Location: DeForest Street
Field Test Data
Test Result Specification
Slump, inches: 2.00
Air Content, %: 4.5
Concrete Temperature, o F: 59
Ambient Temperature, o F: 57
Plastic Unit Weight, pcf:
Laboratory Test Data
2 max
3-5
Age at Maximum Compressive
Set Specimen Diameter Date Test Load Strength
No. ID (inches) Tested (days) (lbs) (psi)
5C 1 6.00 01/29/2001 7 111,140 3,930
5C 2 6.00 01/29/2001 7 112,650 3,980
Average 3,960
5C 3 02/19/2001 28
5C 4 02/19/2001 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples·
The tests were performed in general accordance with applicable ASTM test methods. This report is exclusively for the use of the client indicated above
and shall nut be reproduced ex~cef~ in full without the written appmvat of Terrace. Test results transmitted herein are only applicable to the actual
samples tested at the location(s) referenced and are not necessarily indicative of the pmpe[ties of other apparently similar or identical materials.
CONCRETE COMPRESSIVE STRENGTH TEST
Client:
Excel Group, Inc.
Attn: Bryan Peck
2639 Walnut Hill Ln #218
Dallas TX 75229
Report Date:
Project:
8901 Carpenter Fnvy., Suite #100
Dallas, Texas 75247
(214) 630-1010
January 31, 2001
Windsor Estates
Coppell, Texas
Service Date: January 22, 2001
Project Number: 94001501
Report Number: 94001501.0003
Material Information
Specified Strength: 3500 psi @ 28 Days
Batch Time:
Supplier: TXI
Truck No: 804
Mix I.D. No.: 8204
Plant: 41
Ticket No: 2811435
Sample Information
Sample Time: 5:50pm
Technician: Dardn Phillips
Weather Conditions: Cloudy, cool
Accumulative Yards: 700
Placement Method: Direct discharge
Sample Locations: Sta. 6+00
Placement Location: DeForest Street
Field Test Data
Test
Result
Slump, inches: 2.00
Air Content, %: 4.4
Concrete Temperature, o F: 59
Ambient Temperature, o F: 51
Plastic Unit Weight, pcf:
Laboratory Test Data
Specification
2 max
3-5
Age at Maximum Compressive
Set Specimen Diameter Date Test Load Strength
No. ID (inches) Tested (days) (lbs) (psi)
6C I 6.00 01/29/2001 7 117,320 4,150
6C 2 6.00 01/29/2001 7 113,080 4,000
Average 4,080
6C 3 02/19/2001 28
6C 4 02/19/2001 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Dan*in Phillips
Report Distdbution:
(1) Excel Group, Inc.
(1) City of Copbell - Engr Dept
(1) City of Coppell- Bldg Insp
Reviewed by:
Edc J. Cleveland, P.E.
Senior Project Engineer
Tbe tests were performed in general aceordance with applicatfle ASTM test mathods. This repo,'t is exclusively for U~e uce of the client indicated above
and shall not be reproduced excep~ in full without the written approval of Terracon. Test results transmitted herein are only applk:abla to the acfual
sempies tested at the location(s) referenced and aro not necessarily indicative of the properties of other apparently similar or identical materials.