Windsor Estates-LR010821CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94011150.0014 Service Date: May 15, 2001 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Client: Excel Group, Inc. Attn: Kelly Jordan 2639 Walnut Hill Ln #218 Dallas TX 75229 Report Date: June 21,2001 Project: Jordan Residence Lot 14, DeForest Road Coppell, Texas Project Number: 94011150 Material Information Specified Strength: 3000 psi ~ 28 Days Batch Time: Supplier: Redi-Mix Truck No: 230 Mix I.D. No.: 914-9265 Plant: 1 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature,O F: Ambient Temperature, 0 F: Plastic Unit Weight, pcf: Laboratory Test Data Result 5.00 84 80 Ticket No: 16603 Sample Information sample Time: 11:30am Date Cast: May 15, 2001 Technician: Terry L. Smith Weather Conditions: Clear Accumulative Yards: 10 Placement Method: Truck Sample Locations: 69, 50, 67, 51,80 Placement Location: Piers- 69, 50, 67, 51,80, 79, 64, 66, 54, 44, 45 Specification Test Method 5.0 Max ASTM C-143 N/A ASTM C-172 ASTM C-39 Set Specimen Diameter Date No. ID (inches) Tested 1 1 600 05/22/2001 1 2 6.00 05/22/2001 1 3 6.00 06/12/2001 1 4 6.00 06/12/2001 Age at Maximum Compressive Test Load Strength (days) (lbs) (psi) 7 79,250 2,800 7 81,340 2,880 Average 2,840 28 96,080 3,400 28 94,320 3,340 Average 3,370 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Terry L. Smith Report Distribution: (1) Excel Group, Inc. (1) City of Coppell - Constr Insp (1) City of Coppell - Bldg Insp Reviewed by: Senior Project Engineer The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94011150.0012 Service Date: May 14, 2001 8901 Carpenter Frwy,, Suite #100 Dallas, Texas 75247 (214) 630-1010 Client: Excel Group, Inc. Attn: Kelly Jordan 2639 Walnut Hill Ln #218 Dallas TX 75229 Report Date: June 21, 2001 Project: Jordan Residence Lot 14, DeForest Road Coppell, Texas Project Number: 94011150 Material Information Specified Strength: 3000 psi ~ 28 Days Batch Time: Supptier: Redi-Mix Truck No: 235 Mix I.D. No.: 914 Plant: 1 Field Test Data Test Ticket No: 16564 Sample Information Sample Time: 3:30pm Date Cast: May 14, 2001 Technician: Terry L. Smith Weather Conditions: Hot & partly cloudy Accumulative Yards: 10 Placement Method: Truck Sample Locations: 91,90, 89, 85, 84 P~acement Location: Piers: 98, 105, 95, 94, 86, 91, 90, 89, 85, 84, 87 Test Method Result Specification Slump, inches: 5.00 5.0 Max ASTM C-143 Air Content, %: N/A ASTM C-172 Concrete Temperature,° F: 93 ASTM C-39 Ambient Temperature, o F: 90 Plastic Unit Weight, pcf: Laboratorl~ Test Data Age atMaximum Compressive Set Specimen Diameter Date Test Load Strength No. ID (inches) Tested (days) (lbs) (psi) 1 I 6.00 05/21/2001 7 81,310 2,880 1 2 6.00 05/21/2001 7 79,240 2,800 Average 2,840 1 3 6.00 06/11/2001 28 96,170 3,400 1 4 6.00 06/11/2001 28 99,080 3,500 Average 3,450 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Terry L. Smith Report Distribution: (1) Excel Group, Inc. (1) Ciiy of Coppell - Constr Insp (1) City of Coppell - Bldg Insp Reviewed Eric J. Cleveland, P.E. Senior Project Engineer The tests were performed in general accordance with applicable ASTM, AASHTO. or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.