Amberpoint BP-LR020129 (2)WATER INJECTION OBSERVATION
Date of Service:
Client No.:
Client:
01/29/O2
3181
Transwestern Commercial Services
5001 Spring Valley Rd., Suite 600 W
Dallas, TX 75244
Report No.:
Project No.:
Project:
94021029.0025
94021029
Amberpoint Building No. 1
Amberpoint Bus. Pk ~ Coppell
Coppell, Texas
Location:
Building Pad at lines 5.2 tol 1
and M to J.5
General Contractor: HilI& Wilkinson
Injector: Jowell
Procedure:
On this date, a representative of HBC Engineering, Inc. observed the injection of water at this
site. During the injection process, the following observations were recorded.
Pass No.: 2nd No. of Probes: 4 Probe Length: 18 feet
OBSERVATION
SPECIFICATION Yes No N/A
Surfactant added to each load. X
Iniection pressure 50 to 200 psi at manifold. X
Iniection downward in 18 inch intervals. X
Total depth of injection was 10 feet. X
Spacing ofiniection was 5 feet maximum X
I~iection to refusal at each location. X
Comments:
Technician: S.Long
Report Distribution:
( 1 ) Tramwestem Conunercial Services
(1) O'Brien & ~sociates, Inc.
(1) TechniStractures, Inc.
(1) City of Coppell - Cormr. Insp.
99[Iw
I-fiG Engineering, Inc.
(1) City of Coppell - Bldg. h~sp.
(l) Hill & Wilkinson, Ltd. ~
Eugene Harbour
Principal
This repori is exclusively for the use of the clienl indicated above and shall not be reproduced in full without written approval of HEIC Engineer
WATER INJECTION OBSERVATION
ENGINEEPdNG, INC.
Date of Service:
Client No.:
Client:
01/28/02
3181
Transwestem Commercial Services
5001 Spring Valley Rd, Suite 600 W
Dallas, TX 75244
Report No.:
Project No.:
Project:
94021029.0019
94021029
Amberpoint Building No. 1
Amberpoint Bus. Pk. @ Coppell
Coppell, Texas
Location:
Building Pad
General Contractor: Hill & Wilkinson
Injector: Jowell
Procedure:
On this date, a representative of HBC Engineering, Inc. observed the injection of water at this
site. During the injection process, the following observations were recorded.
Pass No.: 1st No. of Probes: 4 Probe Length: 10 feet
OBSERVATION
SPECIFICATION Yes No N/A
Surfactant added to each load. X
Injection pressure 50 to 200 psi at manifold. X
Injection downward in 18 inch intervals. X
Total depth of injection was 10 feet. X
Spacing of injection was 5 feet maximum. X
Injection to refusal at each location. X
Comments:
Technician: S. Long
Report Distribution:
( 1 ) Transwestem Commercial Services
(1) O'Brien & Associates, Inc.
(1) TechniStructures, Inc.
(1) City of Coppell - Constr. lnsp.
(1) City of Coppell - Bldg. Insp.
(1) Hill & Wilkinson. Ltd
(1) Halff Associates
(1) State Farm Insurance
~ Engineering, Inc.
Eugene Harbour
Principal
99ss This report is exclusively for the use of the client indicated above and shall not be reproduced in full without written approval of HBC Engineer