CF-Coppell Rd SC-CS010129 EVENTIO
~f PLAN REVIEW COMMENTS
I COURTESY REVIEW
I SERVICE CENTER
I S. COPPELL ROAD
~ JANUA~
1. Radius on C 15 (Plat) to be changed to 30 feet.
2. Fire line to be looped system.
3. Add fire hydrant at West side of project.
4. Main building and maintenance building to be protected with a fully automatic fire sprinkler
system.
5. A fire alarm system is required on both buildings.
6. Provide a list of all chemicals used and stored. Include:
a. Type of chemical
b. Quantities
c. Type of storage containers, including size and construction of containers.
d. Type of storage
e. MSDS
f. Spill protection
7. Provide details on chemical wash down. Include purpose, type of traps and containment.
Please keep in mind that this is only a courtesy review. Additional comments may be required once a
permit set has been submitted. If you have any questions on this review, please contact Travis Cromp at
(972) 304-3503.