Loading...
Amberpoint BP-LR020228WATER INJECTION OBSERVATION ENGINFEP. II~, INC. Date of Service: Client No.: Client: Location: Procedure: 02/28/02 3181 Transwestern Commercial Services 5001 Spring Valley Rd., Suite 600W Dallas, Texas 75244 Report No.: Project No.: Project: 94021029.0080 94021029 Amberpoint Building No. 1 Amberpoint Bus. Pk @ Coppell Coppell, Texas Building Pad, see attached sketch General Contractor: Hill & Wilkinson Injector: Jowell On this date, a representative of HBC Engineering, Inc. observed the injection of water at this site. During the injection process, the following observations were recorded. Pass No.: 3rd & 4th No. of Probes: 4 Probe Length: 12 feet OBSERVATION SPECIFICATION Yes No N/A Surfactant added to each load. X Injection pressure 50 to 200 psi at manifold. X Injection downward in 18 inch intervals. X Total depth of injection was 10 feet. X Spacin~ of injection was 5 feet maximum. X Iniection to refusal at each location. X Comments: Technician: S. Campbell Report Distribution: (I) Transwestern Commercial Services {1) O'Brien &Asscciates, Inc. ( I ) TechniStructures, lac. (1) City of Coppell - Constr. Insp (1) City of Coppell - Bldg Insp (I) Hill & Wilkinson, Ltd. ( 1 ) Halff Associates (I) State Farm Insurance I-~ Engineering, Inc. Eugene Harbour Principal 99sks This report is exclusively for the use of the client indicated above and shall not be reproduced in full without written approval of HBC Engineer WATER INJECTION OBSERVATION Date of Service: Client No.: Client: Location: Procedure: 02/28/02 3181 Transwestem Commercial Services 5001 Spring Valley Rd., Suite 600W Dallas, Texas 75244 Report No.: Project No.: Project: 94021029.0070 94021029 Amberpoint Building No. 1 Amberpoint Bus. Pk @ Coppell Coppell, Texas Building Pad, see attached sketch General Contractor: Hill & Wilkinson Injector: Jowell On this date, a representative of HBC Engineering, Inc. observed the injection of water at this site. During the injection process, the following observations were recorded. Pass No.: 3rd & 4th No. of Probes: 4 Probe Length: 12 feet OBSERVATION SPECIFICATION Yes No N/A Surfactant added to each toad. X Injection pressure 50 to 200 psi at manifold. X Iniection downward in 18 inch intervals. X Total depth of injection was 10 feet. X Spacing of injection was 5 feet maximum. X Injection to refusal at each location. X Comments: Technician: K. Douglas Report Distribution: ( I ) Transwestern Commercial Services ( I ) O'Brien & Associates, Inc. (I) TechniStructures, Inc. (l)CityofCoppell Constr. Insp. (I) City of Coppell - Bldg lnsp. (1) Hill & Wilkinson, Ltd. ( 1 ) Halff Associates (I) Stale Farm Insurance I-DC Engineering, Inc. Eugene Harbour Principal 99sks This report is exclusively for the use of the client indioated above and shall not be reproduced in full without written approval of HBC Engineer