PA9702-LR 991014GROUT COMPRESSI STRENGTH TEST ENGIN~.i~I3, INC. 8901 Carpenter Frwy., Suite Dallas, Texas 75247 Date of Service: 09/15/1999 Report No.: 9925022 Report Date 10/14/1999 Client No.: COPPELL Project No.: 94991118 Client: City of Co pell Project: Coppell Aquatic/Recreation Ctr Attn: Bra~PReid 732 DeForest 300 Block of Parkway Blvd Coppell TX 75019 Coppell, Texas/Prj. ~96051 Services: Sample grout from delivery vehicle, cast 3" x 3" x 6" prisms in accordance with the recommendations of ASTM C 1019. PROJECT DATA CONTRACTOR: Hisaw & Assoc. GROUT CLASS: N/A GROUT SUPPLIER: On-Site pLACEMENT DATE: 09/15/1999 BATCH TIME: 8:50am PLANT: On-Site TnVtE SAMPLED: 9:00am BY: Del Ratlift SPECIFICATION REQUIREMENTS WEATHER CONDITIONS: Warm, clear, calm STRENGTH: 2500 psi @ 28 Days TEMPERATURE (F) - AIR 73 F GROUT: 75 F TRUCK NO: N/A TICKer NO: N/A TF~TMETHOD: ASTMC1019 PLACEMENTLOCATION: Gynmasiura east wall SAMPLE LOCATION: See below SAMPLE SIZE: 3" x 3" X 6" REPORT OF TESTS PRISM MEASURED MAXIMUM COMPRESSIVE MARKED SLUMP DATE AGE LOAD STRENGTH SET NO. (inches) TESTED (days) (Ibs. force) (psi) I 1 6.00 09/22~1999 7 32580 3150 1 2 6.00 10/13/1999 28 26740 3 180 1 3 6.00 10/13/1999 28 34750 3330 Average 3260 Sample location: 10' S northeast building corner, 5 course from top Technician Time: See Report #9925023 Report Distribution: (1) City of Coppell (1) City ofCoppsll - Engineering (I) BrinkIcy Sargent Architects (1) City ofCoppell - Bldg. [nsp. E (1) Turner Engineers (1) City of Coppell - Leisure Serv Dept Vice President (1) Hisaw & Associates This report is exclusively for the use of the client indicated above and shall not be reproduced except hi full without the written approval of HBC Engineering, Inc. 09LLW Page I of 1