IN-PLACE DENSITY TESTING
Client:
Project:
Services:
City of Coppell
Attn: Ms. Susan Taylor - Engineering Dept
PO Box 478
Coppell TX 75109
CoppelI, TX
Perform In-Place Density Test in accordance with ASTM Standards.
PROJECT DATA
Report No.: 146683
Project No.: 015729
Date of Service: 03/28/2002
Report Date: 04/02/2002
CONTRACTOR: Infrastructure Services, Inc. Standard Counts
Gauge: Troxlcr-3430 Moisture Density
Test Methods: ASTM D-2922
ASTM D-3017 Gauge Serial No: 32685 Current: 677 Current: 3172
Test Mode: DT
Previous: 679 Previous: 3092
MOISTURE DENSITY RELATIONS
Maximum Project Requirements
M/D No. Description Moisture % Density pcf Moisture Density
1 Dark Brown, Gray and Tan Clay
25.5 94.5 Optimum +5 95 min
FIELD DENSITY TESTS
TEST PROBE
NO TEST LOCATION DEPTH
M/D MOISTURE WET DENSITY DRY DENSITY DENSITY
No. (%) (pcO (pcf) (% max)
Backfill
1 Cabin Wall station 2+25, -3' below grade 6" I 29.6 118.2 91.2 97
Backfill
2 Cabin Wall station 2+25, -2' below grade 6" 1 28.3 116.9 91.1 96
Backfill
3 Cabin Wall station 2+25, -1' below grade 6" 1 29.4 122.9 95.0 10I
Backfill
4 Cabin Wall station 2+25, grade 6" 1 27.1 120.6 94.9 100
Test results on this report meet project specification.
Technician: Joe Jernigan
Report Distribution:
(1) City of Coppell
(1) City of Coppell
(1) City of Coppcll
(1) Infrastructure Services, Inc.
Started: 3:00pm Finished: 4:30pm
(I) City of Coppell
(1) Schrickel, Rollins & Assoc., Inc.
Rom
Clay Stark
Droject Manager