Amberpoint BP-LR020328FIELD DENSITY TESTING
Report Number: 94021029.0131
Service Date: March 16, 2002
Client: Transwestem Commercial Services
Ar[n: Jim Gaspard
5001 Spring Valley Rd. Suite 600W
Dallas TX 75244
Report Date:
8901 Carpenter Fn,W., Suite #100
Dallas, Texas 75247
(214) 630-1010
March 28, 2002
Project: Amberpoint Building No. 1
Amberpoint Bus. Pk. @ Coppell
Coppell, Texas
Project Number: 94021029
Material Information
Matedal Laboratory
No. Test Method
Description and Classification
Lab Test Data Project Requirements
Optimum Max. Lab Water
Water Dry Unit Content Minimum Dry
Content Weight Range Unit Weight
(%) (pcf) (%) (% compaction)
1. 210290004 ASTM D-698 Dk brown clay
Field Test Data
Test
No. Test Location
22.4 99.9 -1/+3 95
S Parking Lot Subgrade
170 45' S of grid line BI1
171 50' S of grid line D/1
172 75' S of grid line G/1
173 90' S of grid line J/1
174 110' S of grid line M/1
175 70' S of grid line O/1
176 50' S of grid line P.5/1
Probe Water Dry Unit
Lift/ Mat. Depth Content Weight
Elevation No. (inches) (%) (pcf)
at Grade I 6 23.1 96.3
at Grade 1 6 24.9 95.8
at Grade 1 6 22.6 97.8
at Grade 1 6 21.9 97.2
at Grade 1 6 22.7 96.1
at Grade 1 6 23.6 96.8
at Grade 1 6 24.1 97.3
Dry Unit
Weight
(% compaction)
96
96
98
97
96
97
97
Comments:
Test results on this report meet project specification.
Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture
condition.
Field Test Method:ASTM D2922, ASTM D3017
Gauge ID:
Field Results Reported To: Contractor/Brian
Technician: Brad Rengstorff
Report Distribution:
(1) Transwestem Commercial Services
(1) O'Bden & Associates Inc
(1) TechniStructures I nc
(1) City of Coppell - Constr Insp
(1) City of Coppell- Bldg Insp
(1) Hill & Wilkinson Ltd
(1) Halff Associates
(1) State Farm Insurance
Reviewed by:
Principal
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not bo reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page I of I 0,~os.~7.-~,..,~