Northpoint Dr-LR020513CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021061.0030 Service Date: May 2, 2002 Client: Transwestem Commercial Services Attn: Jim Gaspard 5001 Spring Valley Rd Suite 600W Dallas TX 75244 Report~a~ay 13, 2002 Projec'- I~lr~rfhnniqt Drive & Associated ut,roes Coppell, Texas Project Number: 94021061 ENC~N~ 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 10:58am Supplier: Potter Truck No: 107 Mix I.D. No.: 7752 Plant: 16 Ticket No: 613578' Sample Information Sample Time: 11:50am Date Cast: May 2, 2002 Technician: Marvin Arandia Weather Conditions: Cloudy Accumulative Yards: 10 Placement Method: Direct Discharge Sample Locations: Canal W side Placement Location: Canal Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Result Specification Test Method 5.00 3 - 5" ASTM C-143 5.4 4 - 6% ASTM C-231 85 950 ASTM C 1064 73 ASTM C:1064 Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) I I 6.00 28.27 05/09/2002 /~7 139,920 J 4,950 1 2 6.00 28.27 05/09/2002~ 137,180 / 4,850w Average 1 3 05/30/2002 28 I 4 05/30/2002 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Marvin Arandia Report Distribution: (1) Transwestem Commemial Services (1) Glenn Thurman Inc (1) Halff Associates (1) City of Coppell - Engineering (1) Cityof Coppell- Bldg Insp (1) State Farm Insurance Reviewed by: (1) Moss Construction HBC En~ Eugene Harbour Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the wdtten approval of Tenacon. Test resuIts bansmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently sireilar or identical materials. Page 1 of 1