ST0001-LR020501 (2)ineers" 8908 Ambassador Row Dallas, Texas 7S247-4510 (214) 630-974S (214] 630-9819 (fax) CONCRETE COMPRESSIVE STRENGTH TEST Client: Proje~t: Services: City of Coppell Attn: Ms. Susan Taylor - Engineering Dept PO Box 478 Copper TX 75019 Report No.: 148255 Project No.: 015729 Date of Service: 04/23/2002 Report Date: 05/01/2002 Creek-view Drive and Freeport Parkway CoppeR, TX Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA STRENGTH: SLUM1· (in): Am (%): T~qT METHOD: cotcraAcro~: Infrastructure Services, Inc. CONCi~T~ SUPPLIER: LRttimor~ l't,A~: 7 Sr~Clr~CATION REQUn~ME~rrs 3000 psi ~ 28 Days 3" - 5" 3% - 5% ASTM C-172 ASTM C-31 ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 MIX DESIGN LD.: 38 rt. ACEMEtCr DATE: 04/23/2002 w~x~nm con~mons: Cloudy ~ s~D: 8:00~ ~T~: 7;15~m ~~-~ 63 r coN~: 78 r ~c~no: 758 ~C~T~O: 7115705 ~ co~ (%): 4.1 u~ wz~a~ ~0: NA Pang ~m ~fi~ 17+50 W S~n 2~50 (C~i~) ~ ~c ~ SAMPI~ LOCATION: Station 18+50 REPORT OF TESTS Coma~ C, omp,~ive Cylinder 6" x 12" (ama 28.27 sq. in.) CYLINDER MEASURED MAXIMUM COMPRESSIVE MARKED SLUMP DATE AGE LOAD ~TRENGTH FRACTURE ~ (inche~) TESTED (days) (lbs. foree) (psi) TYPE 1 1 2.0 04/26/2002 3 86655 3060 Unbonded Cap 1 2 2.0 04/30/2002 7 91305 3230 Unbonded Cap 1 3 2.0 05/21/2002 28 Unbonded Cap I 4 2.0 05/21/2002 28 Unbonded Cap 1 5 Hold LIMITATIONS: The t~t resul~ presented bo~in were ~u~d based upon the specific sample~ provided for testing We as~xtme no responsibility for variation in quality (Ooui~tion. appesnmoe, perfonnan~, et~,) or any other feato~ of similar subject matter provided by peri. ns or conditions over which we have no ooniroL Our lettem and ~pom Are for the exclusive use of thc clients to whom they m'e .dtlres~exl mad shall not bo I~fod~ gd excb~pt in f~ Withotlt ~ w~tt~l &~i~v~l of Rone Engineers, Xnc. 01DK Page I of 7 Report No.: 148255 Project No.: 015729 Client: City of Coppell RoneEngineers Water added at site: 5 gallons LIMITATIONS: The test results lx~sent~l herein w~e vi'abated based upon the speelflc samples provided for te~tin~ We a~tlmc Iio fc~ponst~oillt)' for Val~t~oa in qtlalit~ (composition, appem,u.ce, performance, etc.) or my o~her __~a_.~e of similar subject matter provided by pet-~ons or conditions over which we have no control. Our letters nnd rcpom a~e for the exclusivc usc of the clicnts to whom thcy ar~ addresscd and shall not be ,~vwduced except in full without the wrirten av/nsval of Rone Engineers, Inc. 01DK Page 2 of 7 RoneEn ineers 8908 Ambassador Dslhs, Texas 7S247-4510 (214) 630-974S (214) 6309819 (fax) CONCRETE COMPRESSIVE STRENGTH TEST Client: Project: Services: City of Coppell Ama: Ms. Susan Taylor - Engineering Dept PO Box 478 Coppell TX 75019 Report No.: 148255 Project No.: 015729 Date of Service: 04/23/2002 Report Date: 05/01/2002 Creekview Drive and Frecpon Parkway Coppell, TX Obtain samples of fresh concrete at thc placemant locations, perform required field testing, cast compr~sivc strength samples and bring samples back to tl{e laboratory for curing and testing in accordance with applicable standards. PROJECT DATA ~-fI~NGTH: SLUMP (in): AIR (%): TEST METHOD: conTEACrO~: Infrastructure Services, Inc. CONCRKTE SUPPLIER: ~flttimore rt.~rr: 7 s~cnncA~nOn REQ~mZMENTs 3000 psi ~ 21{ Days 3% - 5% ASTM C-172 ASTM C-31 ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 MIX DESIGN I.D.: 38 r~AC~MENT DATE: 04/23/2002 WEATHER CONDmON$: Partly cloudy TIME SAMPLED: 10:lSam BATCHTIME: 9:47am TEMPERATURE (F)- AIR 70 r CONC~TE: 90 r xaoc~ NO: 1039 XI¢~T NO: 7115725 Ant co~rrz~T {%): 4.0 U~Tr W~lG~rr (~: NA OVERALL PLACEMENT LOCATION: Paving from Station 17+50 to Stalion 26+50 (Cre~kvimv) aoulh lane mmtbound SAMPLE LOCATION: Station 21+50 REPORT OF TESTS Concrc~ Compressive Cylinder 6" x 12" (area 28.27 scl. in.) CYLINDER MEASURED MAXIMUM COMPRESSIVE bfARK~D SLUMP DATE AGE LOAD b-i'KENGTH FRACTURE SET NO. 0nches) TESTED (days) (lbs. force) (psi) TYPE 2 1 2.0 04/26/2002 3 92755 3280 Unbonded Cap 2 2 2.0 04/30/2002 7 103700 3670 Unbonded Cap 2 3 2.0 05/21/2002 28 Unbonded Cap 2 4 2.0 05/21/2002 28 Unbonded Cap 2. 5 Hold LIMITATIONS: The t~t results presented herein wcre prcpm'ed based upon the specific p,mpl~ provided for testing. We assmne no responsibility for variation in quality (composition, appearance, pedonnance, e~c.) or any other feature of similar subject matter provided by pcrsom or conditions over which we have no coatn)l. Our leV. ers and reports are for the exclusive use of the clients to whom they a~ addrcssed and shall no~ bc rcpwduccd cxccpt in full without lhe writmn ~roval of Ronc F.a~incers, Inc. 01DK Page 3 of 7 8908 Ambamdor Row Dellas, Texas 75247-4510 (214) 630-9745 (214) 630-9819 (fax) CONCRETE COMPRESSIVE STRENGTH TEST CHeat: Project: Services: City of Coppell At'm: Ms. Susan Taylor - Engiae~n'ing Dept PO Box 478 Coppell TX 75019 Report No.: 148255 Project No.: 015729 Date of Service: 04/23/2002 Report Date: 05/01/2002 Cr~ekview Drive and Freeport Parkway CoppeH, TX Obtain samples of fresh concrete at the placameot locations, perform required field te~ting, east compr~sive strength ~amples and bring samples back to thc laboratory for curing and tinting in accordencc with applicable standards. PRO3ECT DATA STRENGTH: SLUMP On): AIR (%): TEST METIiOD: co~rRAcrom Infrastructure Services, Inc. CONCRETE SUPPLIER: Lattimore PLANT: 7 SPECIFICATION REQUIREMENTS 3000 psi ~ 28 Days 3" - 5" 3% - 5% ASTM C-172 ASTM C-31 ASTM C-143 ASTM C-231 ASTM C-1064 ASTIVI C-138 MIX DESIGN I.D.: 38 rL~CgME~rr DATE: 04/23/2002 WEATIIRR CONDmONS: Clo~y T~S~LED: 11:40~ BATCH~: ll:02am TE~E~-~ 71 r co~: 90 r ~uc~ so: 1039 T~C~T SO: 7115737 ~ co~ (%): 4.5 ~ ~o~ ~: NA O~L P~ ~ATION: ~g ~m S~on 17+50 m Sm~ 2~50 (C~) ~ ~ ~ SAMPLE LOCATION: Station 23+00 ASTM C-39 REPORT OF TESTS Con~'t~ Comprmsive Cylindor 6" x 12" (arm 28.27 sq. in.) CYLINDER MEASURED MAXIMUM MARKED SLUMP DATE AGE LOAD SET NO. ' 0nches) TESTED (days) (lbs. force) 3 1 2.5 04/26/2002 3 75595 3 2 2.5 ~ · 04/30/2002 7 ' 86515 3 3 Z5 05/21/2002 28 3 4 2.5 05/21/2002 28 3 5 Bold COMPRESSIVE STRENGTH 2670 3060 FRACTIJIEg TYPE Unbonded Cap Unbonded Cap Unbonded Cap Unbonded Cap LIMITATIONS: The test results pr~nted h~m~-in wine prepared based upon thc speoific samplm provided for tmllng. We assum~ no rmgousibility for variation in quality (composition, appennmoe, perfonnnnee, em.) or any other feature of similnr subjec~ malter p~vided by pe~ous.°r conditions ..... over which we have no control. Our. iett. ets and. re~ arc for the exclusive use of the clients to whom they arc add~ssed and shah not be reproduced ex?pt m full vnthout the wnRm ~i~l~ oval of Pone Engmce~, 01DK Page 4 of 7 Repo~ No.: 148255 Project No.: 015729 Client: City of Coppell ROneEn~ineers Water added at site: 5 gallons LIMITATIONS: The trot results presented he,in were prepared basod upon the specific sam?les provided fur testing. We assume no r~sponsibility for vnriation in quality (comlx~ition, appearance, performance, et~.} or any othe~ fenture of similar subject mater provided by persons or conditions over which we have no conlml. Our letters and repo~ are for ~he exclusive use of the clients to whom they are *tldre~sed and shall not be,~,,oduced except in full without the written approval of Pone Enginee~, Inc. OlDK Page $ of 7 8908 Ambassador Row Dallas, Texas 7S247-4510 (214) 630-9745 (214) 630-9819 (fax) CONCRETE COMPRESSIVE STRENGTH TEST Client: Projeet: Services: City of Coppell Arm: Ms. Susan Taylor - Engineering Dept PO Box 478 Coppell TX 75019 Report No.: 148255 Project No.: 015729 Date of Service: 04/23/2002 Report Date: 05/01/2002 Cre~kview Drive and Freeport Parkway Coppell, TX Obtain samples of fresh concrem at the placement locations, perform required field testing, ca~t compressive strength samples and'bring samples back to the laborato~ for curing and ~ting in accordance with applicable ~tandards. PROJECT DATA S'rRENGrH: SLUMI' On): AIR (%): TEST METHOD: CONTRACTOR: Infrastructure Services, Inc. CONCRETE SUPPLIER: Lattimore PLANT: 7 SPECIFICATION REQUIREMENTS 3000 psi ~ 28 Days 3" - 5" 3% - 5% ASTM C-172 ASTM C-31 ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 MIX DESIGN I.D.: 38 PLACEMENT DATE: 04/23/2002 WEATHER CONDITIONS: Cloudy rmmSASn'L~D: 1:45pm a~TCaTIM~: l:lSpm TE~E~-~ 80 F CONC~: ~ F ~UCK NO: 1092 TIC~T NO: 7115755 ~ CO~ frO: 4.1 UN~ WgIG~ ~: NA O~L P~ L~A~ON: ~g ~m S~on 17+50 m Sm~ 2~50 (C~) m~ ~ ~ SAMPLE LOCATION: Station 25+00 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12' (a~a 28.27 sq. in.) CYLINDER MEASURED MAXIMUM COMPRESSIVE MARKED SLUMP DATE AGE LOAD STRENGTH -FRACTURE SET NO. (inches) TESTED (days) Obs. for~e) (p~l) TYPE 4 1 2.25 04/26/2002 3 62970 2230 Unbonded Cap 4 2 2.25 04/30/2002 7 75120 2660 Unbonded Cap 4 3 2.25 05/21/2002 28 Unbonded Cap 4 4 2.25 05/21/2002 28 Unbonded Cap 4 5 Hold LIMITATIONS: The test results presented he.in were prepa~cl based upon tho ~citlc ~-?les Inovi~l for testing. We assume no r~ponsibilit~ for variation,in quality (composition. appearance, performan~, eW.) or any other f~ature of similar subjeot maV~ provided by persons or conditions over which we have no controL Our lette~ and reports are for the exclusive use of the clicnts to whom they are *d,~ressed and shall not be lvproduced exccpt in full without the wrltton approval of Ron¢ F. ngincers, Inc. OlDK Page 6 of 7 RoneEngineers Report No.: 148255 Project No.: 015729 Client: City of Coppcll Water added at site: 5 gallons T~w. hniclan: Alltholay Maldonado Report Distribution: (1) Cit~ of Copp~ll (1) city of coppeU (1) City of Copp~ll (I) Infra~Iru~ur~ S~vlcez, In~. Started: 9:00~m Finished: 4:3~m (1) City of Coppell (1) S~hr/~kel~ Rollins & ~c., Inc. Clay Projo~t Manager LIMITATIONS: The test results pr--~cated herein wac ~n~pa~d based upon the specific samples provided for test/ng. We assume no rcsponsi~ for varintion in quality (composition, appearance, pcrformance, etc.) or any other feature of similar subject mattcr provided by pcrsom or c~litiom ovcr which we have no conu~l. Our Icttc~ and reports nrc for thc exclusive use of the clicnts to whom they nrc addressed and shall not be r~uccd exccpt in full without thc written ,al..~ oval of Rone Engineer, Inc. 01DK Page 7 of 7