Northpoint Dr-LR020521CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021061.0032 Service Date: April 22, 2002 Client: Transwestem Commercial Services Attn: Jim Gaspard 5001 Spring Valley Rd Suite 600W Dallas TX 75244 Report Date: May21,2002 Project: Northpoint Drive & Associated Utilities Coppell, Texas Project Number: 94021061 8901 Carpenter Fnt~y., Suite #100 Dallas, Texas 75247 (214) 630-1010 Material Information Specified Strength: 3000 psi (~ 28 Days Batch Time: N/A Plant: N/A Supplier:. LMC Truck No: N/A Mix I.D. No.: 38 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laborator~ Test Data Result N/A N/A N/A Ticket No: N/A Sample Information Sample Time: N/A Date Cast:April 22, 2002 Technician: Contractor Made Weather Conditions: N/A Accumulative Yards: N/A Placement Method: N/A Sample Locations: See placement location Placement Location: Headwall- S side retention Specification Test Method N/A ASTM C-143 N/A ASTM C1064 ASTM C-1064 Set Specimen Diameter Area Date No. ID (inches) (sq. inches) Tested I 1 6.00 28.27 04/29/2002 I 2 6.00 28.27 04/29/2002 I 3 6:00 28.27 - 05/20/2002 I 4 6.00 28.27 05/20/2002 Age at Maximum Compressive Test Load Strength (days) (lbs) (psi) 7 80,390 2,840 7 91,490 3,240 Average 3,040 28 114,860 4,060 28 118,700 4,200 Average 4,130 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples, Technician: Contractor Made Report Distn.'bution: (1) Transwestem Commercial Services (1) Glenn Thurman Inc (1) Halff Associates (1) City of Col3pell - Engineering (1) City of Coppell - Bldg Insp (1)'State Farm Insurance (1) Moss Construction Reviewed by: HBC Eng~ Eugone Harbour Pr~dml The tnsts were performed in general accordance with apprmable ASTM, AASHTO, or DOT tnst mathods. This report is e~a=~-~ for the use of the ctte~ indicated above and shall n~ be reproduced excel~ in full without the vwitton approval of Tea"econ. Test results transmitted herein are only apl0iicatfle to the actual sarnpies tested at ~he location(s) referenced and are not necessarily indicative of the properties of oiher apparently sim~r or identical materials. Page 1 of 1