Amberpoint BP-LR020520CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021029.0225
ServiCe Date: April 19, 2002
Client: Transwestem Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd. Suite 600W
Dallas TX 75244
8901 Carpenter Finny., Suite #100
Dallas, Texas 75247
(214) 630-1010
Report Date: May 20, 2002
Project: Amberpoint Building No. 1
Amberpoint Bus. Pk. (~ Coppell
Coppell, Texas
Project Number: 94021029
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 4:40am
Supplier: Potter
Track No: 110
Mix I.D. No.: 9349
Plant: 16
Field Test Data
Test
Slump, inches:
Air Content, %:
Concrete Temperature,° F:
Ambient Temperature, o F:
Plastic Unit Weight, pcf:
Laboratory Test Data
Set Specimen
No. ID
I 1
I 2
Result
5.00
1.4
80
Diameter Area
(inches) (sq. inches)
6.00 28.27
6.00 28.27
1 3
I 4
6.00 28.27
6.00 28.27
Services -
Ticket No: 613066
Sample Information
Sample Time: 4:40am Date Cast:April 19, 2002
Technician: Marvin Arandia
Weather Conditions: Cloudy
Accumulative Yards: 40
Placement Method: Direct Discharge
Sample Locations: Grid line 1.6/M.8
Placement Location: Slab at lines I to 3 and A to N
Specification Test Method
ASTM C-143
ASTM C-231
ASTM C1064
ASTM C-1064
Age at Maximum Compressive
Date Test Load Strength
Tested (days) (lbs) (psi)
04~26/2002 7 122,140 4,320
04/26~2002 7 121,870 4,310
Average 4,320
05/17/2002 28 142,750 5,050
05/17/2002 28 146,600 5,180
Average 5,120
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test meflxxts. This repo~ is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Ten'acon. Test results transmitted herein are only applicable
to the actual samples tested at the Iocetion(s) referenced and are not n~_ __~_rily indicative of the properties of other apparently similar or identical
materials.
Page I of 9
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021029.0225
Service Date: April 19, 2002
Client: Transwestem Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd. Suite 600W
Dallas TX 75244
8901 Carpenter FnNy., Suite #100
Dallas, Texas 75247
(214) 63o-lo10
Report Date: May 20, 2002
Project: Amberpoint Building No. 1
Amberpoint Bus. Pk. @ Coppell
Coppell, Texas
Project Number: 94021029
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 4:54am
Supplier: Potter
Truck No: 114
Mix I.D. No,: 9349
Plant: 16
Field Test Data
Test
Slump, inches:
Air Content, %:
Concrete Temperature, o F:
Ambient Temperature, o F:
Plastic Unit Weight, pcf:
Laboratory Test Data
Result
5.75
1.6
80
73
Ticket No: 613074
Sample Information
Sample Time: 5:25am Date Cast:April 19, 2002
Technician: Marvin Arandia
Weather Conditions: Cloudy
Accumulative Yards: 120
Placement Method: Direct Discharge
Sample Locations: Grid line L.2/1.9
Placement Location: See page 1
Specification
Set Specimen Diameter Area Date
No. ID (inches) (sq. inches) Tested
2 1 6.00 28.27 04/26/2002
2 2 6.00 28.27 04~26/2002
2 3 6.00 28.27 05/17/2002
2 4 6.00 28.27 05/17/2002
Test Method
ASTM C-143
ASTM C-231
ASTM C1064
ASTM C-1064
Age at Maximum Compressive
Test Load Strength
(days) (lbs) (psi)
7 110,290 3,900
7 114,440 4,050
Average 3,980
28 141,890 5,020
28 138,300 4,890
Average 4,960
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted heroin are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 2 of 9
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021029.0225
Service Date: April 19, 2002
Client: Transwestem Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd. Suite 600W
Dallas TX 75244
8901 Carpenter Fmty., Suite #100
Dallas, Texas 75247
(214) 630-1010
Report Date: May 20, 2002
Project: Amberpoint Building No. 1
Amberpoint Bus. Pk. (~ Coppell
Coppell, Texas
Project Number: 94021029
Material Information
Specified Strength: 4000 psi (~ 28 Days
Batch Time: 5:45pm
Supplier: Potter
Truck No: 116
Mix I.D. No.: 9349
Plant: 16
Field Test Data
Test
Slump, inches:
Air Content, %:
Concrete Temperature,o F:
Ambient Temperature, o F:
Plastic Unit Weight, pcf:
Laboratory Test Data
Result
5.50
1.3
79
73
Ticket No: 613085
Sample Information
Sample Time: 6:05am Date Cast:April 19, 2002
Technician: Marvin Arandia
Weather Conditions: Cloudy
Accumulative Yards: 230
Placement Method: Direct Discharge
Sample Locations: Grid line J.5/2.1
Placement Location: See page 1
Specification Test Method
Set Specimen Diameter Area Date
No. ID (inches) (sq. inches) Tested
3 1 6.00 28.27 04/26/2002
3 2 6.00 28.27 04/26/2002
3 3 6.00 28.27 05/17/2002
3 4 6.00 28.27 05/17/2002
ASTM C-143
ASTM C-231
ASTM C1064
ASTM C-1064
Age at Maximum Compressive
Test Load Strength
(days) (lbs) (psi)
7 123,220 4,360
7 121,540 4,300
Average 4,330
28 147,610 5,220
28 150,450 5,320
Average 5,270
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were perfm'med in general accordance with applicable ASTM, AASHTO, or DOT test methods. This repr~t is exotusiveiy for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicab~
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar o~ identical
materials.
Page 3 of 9
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021029.0225
Service Date: April 19, 2002
Client: Transwestem Commemial Services
Attn: Jim Gaspard
5001 Spring Valley Rd. Suite 600W
Dallas TX 75244
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Report Date: May 20, 2002
Project: Amberpoint Building No. 1
Amberpoint Bus. Pk. ~ Coppell
Coppell, Texas
ProjeCt Number: 94021029
Material Information
Specified Strength: 4000 psi (~ 28 Days
Batch Time: Plant: 16
Supplier: Potter
Truck No: 115 Ticket No:
Mix I.D. No.: 9349
Field Test Data
Test
Slump, inches:
Air Content, %:
Concrete Temperature,o F:
Ambient Temperature, o F:
Plastic Unit Weight, pcf:
Laborator~ Test Data
Result
4.00
1.6
80
72
Sample Information
Sample Time: 7:00am Date Cast: April 19, 2002
Technician: Marvin Arandia
Weather Conditions: Cloudy
Accumulative Yards: 320
Placement Method: Direct Discharge
Sample Locations: Grid line H.8/2.3
Placement Location: See page 1
Specification
Set Specimen Diameter Area Date
No. ID (inches) (sq. inches) Tested
4 I 6.00 28.27 04/26/2002
4 2 6.00 28.27 04/26/2002
4 3 6.00 28.27 05/17/2002
4 4 6.00 28.27 05/17/2002
Test Method
ASTM C-143
ASTM C-231
ASTM C1064
ASTM C-1064
Age at Maximum Compressive
Test Load Strength
(days) (lbs) (psO
7 136,720 4,830
7 124,760 4,410
Average 4,629
28 169,450 5,990
28 156,130 5,520
Average 5,760
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is e~clusiveiy for the use of the client
indicated above and shall not be reproduced except in full w~thout the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the Iocetion(s) referenced and are not necessarily indicatk~ of the properties of other apparently slmilar or identical
materials,
Page 4 of 9
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021029.0225
Service Date: Apd119, 2002
Client: Transwestem Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd. Suite 600W
Dallas TX 75244
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Report Date: May 20, 2002
Project: Amberpoint Building No. 1
Amberpoint Bus. Pk. (~ Coppell
Coppell, Texas
Project Number: 94021029
Material Information
Specified Strength: 4000 psi ~ 28 Days
Batch Time: 7:40am Plant: 16
Supplier: Potter
Truck No: 112
Mix I.D, No.: 9349
Ticket No: 613101
Sample Information
Sample Time: 8:15am Date Cast:April 19, 2002
Technician: Marvin Arandia
Weather Conditions: Cloudy
Accumulative Yards: 400
Placement Method: Direct Discharge
Sample Locations: Grid line G.3/1.9
Placement Location: See page I
Field Test Data
Test Result Specification Test Method
Slump, inches: 4.00 ASTM C-143
Air Content, %: 1.2 ASTM C-231
ConCrete Temperature,o F: 80 ASTM C1064
Ambient Temperature, o F: 71 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at
Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
5 I 6.00 28.27 04/26/2002 7 154,720 5,470
5 2 6.00 28.27 04126/2002 7 147,930 5,230
Average 5,350
5 3 6.00 28.27 05/17/2002 28 175,770 6,220
5 4 6.00 28.27 05/17/2002 28 183,940 6,510
Average . 6,370
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT te~t methods. This report is exclusively for the usa of the client
indicated above and shall not be reproduced excel~ in full without the written approval of Ten'acon. Test results ~,,,,rsmitted herein are only applicable
to the actual sarnples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 5 of 9
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021029.0225
Service Date: April 19, 2002
Client: Transwestem Commemial Services
Attn: Jim Gaspard
5001 Spdng Valley Rd. Suite 600W
Dallas TX 75244
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Report Date: May 20, 2002
Project: Amberpoint Building No. 1
Amberpoint Bus. Pk. (~ Coppell
Coppell, Texas
Project Number: 94021029
Material Information
Specified Strength: 4000 psi ~ 28 Days
Batch Time: 9:00am
Supplier: Potter
Truck No: 110
Mix I.D. No.: 9349
Plant: 16
Ticket No: 613114
Sample Information
Sample Time: 9:50am Date Cast:April 19, 2002
Technician: Marvin Arandia
Weather Conditions: Cloudy
Accumulative Yards: 520
Placement Method: Direct Discharge
Sample Locations: Grid line E.9/1.2
Placement Location: See page 1
Field Test Data
Test Result Specification
Slump, inches: 5.00
Air Content, %: 1.4
Concrete Temperature, o F: 80
Ambient Temperature, o F: 71
Plastic Unit Weight, pcf:
Laboratory Test Data
Set Specimen Diameter Area Date
No. ID (inches) (sq. inches) Tested
6 I 6.00 28.27 04/26/2002
6 2 6,00 28.27 04/26/2002
6 3 6.00 28.27 05/17/2002
6 4 5.00 28.27 05/17/2002
Test Method
ASTM C-143
ASTM C-231
ASTM C1064
ASTM C-1064
Age at
Maximum Compressive
Test Load Strength
(days) (lbs) (psi)
7 121,660 4,300
7 114,670 4,060
Average 4,180
28 151,450 5,360
28 157,300 5,560
Average 5,460
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This repod is exclusively for the use of the client
indicated above and shall not he reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 6 of 9 o,~_w,~.~.. Kw
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021029.0225
Service Date: April 19, 2002
Client: Transwestem Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd. Suite 600W
Dallas TX 75244
8901 Carpenter Fn~y., Suite #100
Dallas, Texas 75247
(214) 63O-lOm
Report Date: May 20, 2002
Project: Amberpoint Building No. 1
Amberpoint Bus. Pk. @ Coppell
Coppell, Texas
Project Number: 94021029
Material Information
Specified Strength: 4000 psi (~ 28 Days
Batch Time: 9:39am Plant: 16
Supplier: Potter
Truck No: 111
Mix I.D. No.: 9349
Field Test Data
Test
Ticket No: 613123
Sample Information
Sample Time: 10:25am Date Cast:^pril 19, 2002
Technician: Marvin Arandia
Weather Conditions: Cloudy
Accumulative Yards: 610
Placement Method: Direct Discharge
Sample Locations: Grid line D.5/2.7
Placement Location: See page 1
Result Specification Test Method
Slump, inches: 5.50 ASTM C-143
Air Content, %: 1.4 ASTM C-231
Concrete Temperature, o F: 81 ASTM C1064
Ambient Temperature, o F: 70 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratorl/ Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (ps~
7 I 6.00 28.27 04/26/2002 7 118,400 4,190
7 2 6.00 28.27 04/26/2002 7 108,930 3,850
Average 4,020
7 3 6.00 28.27 05/17/2002 28 142,720 5,050
7 4 6.00 28.27 05/17/2002 28 142,710 5,050
Average 5,050
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests wore performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exc~ for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are oaly applicable
to the actual samples tested et the location(s) referenced and ara net necessarily indicative of the properties of other apparently similar or identical
materials.
Page 7 of 9
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021029.0225
Service Date: April 19, 2002
Client: Transwestem Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd. Suite 600W
Dallas TX 75244
8901 Carpenter Finny., Suite #100
Dallas, Texas 75247
(214) 630-1010
Report Date: May 20, 2002
Project: Amberpoint Building No. 1
Amberpoint Bus. Pk. @ Coppell
Coppell, Texas
Project Number: 94021029
Material Information
Specified Strength: 4000 psi (~ 28 Days
Batch Time: 10:43am Plant: 16
Supplier: Potter
Truck No: 108
Mix I.D. No.: 9349
Ticket No: 613136
Sample Information
sample Time: 11:20am Date Cast:April 19, 2002
Technician: Marvin Arandia
Weather Conditions: Cloudy
Accumulative Yards: 730
Placement Method: Direct Discharge
Sample Locations: Grid line C.1/2.7
Placement Location: See page 1
Field Test Data
Test Result Specification Test Method
Slump, inches: 5.00 ASTM C-143
Air Content, %: 1.4 ASTM C-231
Concrete Temperature,o F: 81 ASTM C1064
Ambient Temperature, o F: 75 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
8 1 6.00 28.27 04/26/2002 7 126,880 4,490
8 2 6.00 28.27 04~26~2002 7 132,210 4,680
Average 4,590
8 3 6.00 28.27 05/17/2002 28 169,440 5,990
8 4 6.00 28.27 05/1712002 28 161,840 5,720
Average 5,860
Services o Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general ac, cordanca with applicable ASTM, AASHTO. or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 8 of 9
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021029.0225
Service Date: April 19, 2002
Client: Transwestern Commercial Services
Attn: Jim Gaspard
5001 Spdng Valley Rd. Suite 600W
Dallas TX 75244
8901 Carpenter Fnvy.. Suite #100
Dallas, Texas 75247
(214) 630-1010
Report Date: May 20, 2002
Project: Amberpoint Building No. 1
Amberpoint Bus. Pk. @ Coppell
Coppell, Texas
Project Number: 94021029
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 11:44am
Supplier: Potter
Track No: 108
Mix I.D. No.: 9349
Plant: 16
Field Test Data
Test
Result
Slump, inches: 6.00
Air Content, %: 1.4
Concrete Temperature, o F: 81
Ambient Temperature, o F: 78
Plastic Unit Weight, pcf:
Laboratory Test Data
Ticket No: 613149
Sample Information
Sample Time: 12:15pm Date Cast:April 19, 2002
Technician: Marvin Arandia
Weather Conditions: Cloudy
Accumulative Yards: 850
Placement Method: Direct Discharge
Sample Locations: Grid line A.2/1.3
Placement Location: See page 1
Specification Test Method
ASTM C-143
ASTM C-231
ASTM C1064
ASTM C-1064
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
9 I 6.00 28.27 04~26/2002 7 115,530 4,090
9 2 6.00 28.27 04/26/2002 7 110,260 3,900
Average 4,000
9 3 6.00 28.27 05/17/2002 28 140,730 4,980
9 4 6.00 28.27 05/17/2002 28 139,680 4,940
Average 4,960
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Marvin Arandia
Report Distribution:
(1) Transwestem Commercial Services
(1) O'Brien & Associates Inc
(t) TechniStructures Inc
(1) City of Coppell - Constr Insp
(1) City of Coppell - Bldg Insp
(1) Hill & Wilkinson Ltd
(1) Halff Associates
(1) State Farm Insurance
Reviewed by:
HBC Engi~gj
Eugene Harbour
Principal
The tests were performed in general accordarme with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall no{ be reproduced except in full without the written approval of Terraces. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently simi~r or identical
materials.
Page 9 of 9 o,-~w~.~,~
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021029.0276
Service Date: May 11, 2002
Client: Transwestem Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd. Suite 600W
Dallas TX 75244
8901 Carpenter Fnvy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Report Date: May 20, 2002
Project: Amberpoint Building No. 1
Amberpoint Bus. Pk. (~ Coppell
Coppell, Texas
Project Number: 94021029
Material Information
Specified Strength: 3000 psi ~ 28 Days
Batch Time: 7:30am
Supplier: Potter
Truck No: 115
Mix I.D. No.: 9337
Plant: 16
Ticket No: 613718
Sample Information
Sample Time: 7:50am Date Cast: May 11, 2002
Technician: Brad Rengstorff
Weather Conditions: Cloudy
Accumulative Yards: 50
Placement Method: Pump
Sample Locations: Panel #50
Placement Location: Panels- 39-52, 91, SW1-SW8, Panel 92A,
B,C
Field Test Data
Test Result Specification Test Method
Slump, inches: 5.25 4-6 ASTM C-143
Air Content, %: 1.6 N/A ASTM C-231
Concrete Temperature,° F: 83 ASTM C1064
Ambient Temperature, o F: 72 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
1 I 6.00 28.27 05/14/2002 3 98,970 3,500
1 2 6.00 28.27 05/18/2002 7 124,160 4,390
1 3 6.00 28.27 05/18/2002 7 123,860 4,380
Average 4,390
I 4 06/08/2002 28
1 5 06/08/2002 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compiesslve
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not bo reproduced except in full without the written approval of Terrecon. Test results trensmltted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of 5
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021029.0276
Service Date: May 11, 2002
Client: Transwestem Commemial Services
Attn: Jim Gaspard
5001 Spring Valley Rd. Suite 600W
Dallas TX 75244
8901 Carpenter Rwy., Suite #100
Dallas, Texas 75247
(214) 630-f 010
Report Date: May 20, 2002
Project: Amberpoint Building No, 1
Amberpoint Bus. Pk. (~ Coppell
Coppell, Texas
Project Number: 94021029
Material Information
Specified Strength: 3000 psi ~ 28 Days
Batch Time: 8:25am
Supplier: Potter
Truck No: 115
Mix I.D. No.: 9337
Plant: 16
Field Test Data
Test
Ticket No: 613727
Slump, inches:
Air Content, %:
Concrete Temperature? F:
Ambient Temperature, o F:
Plastic Unit Weight, pcf:
Sample Information
Sample Time: 8:35am Date Cast: May 11, 2002
Technician: Brad Rengstorff
Weather Conditions: Cloudy
Accumulative Yards: 50
Placement Method: Pump
Sample Locations: Panel 42
Placement Location: Panel 39-43, 46-52, 91, 92, A, B, C,
SWI-SW8
Result Specification Test Method
5.50 4-6 ASTM C-143
1.7 N/A ASTM C-231
83 ASTM C1064
73 ASTM C-1064
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
2 1 6.00 28.27 05/14/2002 3 93,650 3,310
2 2 6.00 28.27 05/1812002 7 120,290 4,250
2 3 6.00 28.27 05/18/2002 7 115,500 4,080
Average 4,170
2 4 06/08/2002 28
2 5 06/08/2002 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not bo reproduced except in full without the written approval of Tenacon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the pmpedies of other apparently similar or identical
materials.
Page 2 of 5
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number.- 94021029.0276
Service Date: May 11, 2002
Client: Transwestem Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd. Suite 600W
Dallas TX 75244
8901 Carpenter Fnvy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Report Date: May 20, 2002
Project: Amberpoint Building No. 1
Amberpoint Bus. Pk. @ Coppell
Coppeli, Texas
Project Number: 94021029
Material Information
Specified Strength: 3000 psi (~ 28 Days
Batch Time: 9:43am
Supplier: Potter
Truck No: 103
Mix I.D. No.: 9337
Plant: 16
Field Test Data
Test
Result
Slump, inches: 5.00
Air Content, %: 1.3
Concrete Temperature, o F: 83
Ambient Temperature, o F: 74
Plastic Unit Weight, pcf:
Laboratory Test Data
Ticket No: 613738
Sample Information
Sample Time: 10:20am Date Cast: May 11, 2002
Technician: Brad Rengstorff
Weather Conditions: Cloudy
Accumulative Yards: 250
Placement Method: Pump
Sample Locations: Panel #39
Placement Location: Panel 39-43, 46-52, 91, 92, A, B, C,
SW1 -SW8
Specification
Test Method
4-6 ASTM C-143
N/A ASTM C-231
ASTM C1064
ASTM C-1064
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
3 1 6.00 28.27 05/14/2002 3 108,950 3,850
3 2 6.00 28.27 05/18~2002 7 125,360 4,430
3 3 6.00 28.27 05/18~2002 7 130,640 4,620
Average 4,$30
3 4 06/08/2002 28
3 5 06/08/2002 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This repal is exclusively fer the use of the client
indicated above and shall not be reproduced except in fuil without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 3 of 5
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021029.0276
Service Date: May 11, 2002
Client: Transwestem Commercial Services
Attn: Jim Gaspard
5001 Spdng Valley Rd. Suite 600W
Dallas TX 75244
8901 Carpenter F~vy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Report Date: May 20, 2002
Project: Amberpoint Building No. 1
Amberpoint Bus. Pk. (~ Coppell
Coppell, Texas
Project Number: 94021029
Material Information
Specified Strength: 3000 psi (~ 28 Days
Batch Time: 10:30am
Suppliec Potter
Truck No: 115
Mix I.D. No.: 9337
Plant: 16
Field Test Data
Test
Result
Slump, inches: 4.75
Air Content, %: 1.2
Concrete Temperature, o F: 84
Ambient Temperature, o F: 79
Plastic Unit Weight, pcf:
Laboratory Test Data
Ticket No: 613746
Sample Information
Sample Time: 11:15am Date Cast:May 11, 2002
Technician: Brad Rengstorff
Weather Conditions: Cloudy
Accumulative Yards: 330
Placement Method: Pump
Sample Locations: Panel 92B
Placement Location: Panel 39-43, 46-52, 91, 92, A, B, C,
SW1-SW8
Specification Test Method
4-6 ASTM C-143
N/A ASTM C-231
ASTM C1064
ASTM C-1064
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
4 I 6.00 28.27 05/14/2002 3 94,610 3,350
4 2 6.00 28.27 05/18/2002 7 116,840 4,130
4 3 6.00 28.27 05/18/2002 7 120,900 4,280
Average 4,210
4 4 06/08/2002 28
4 5 06/08/2002 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test me~hnds. This report is exclusNeiy for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracen. Test results.transmitted herein are ordy aplflicable
to the actual samples tested at t~e location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 4 of 5 o,~w~,~o
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021029.0276
Service Date: May 11, 2002
Client: Transwestem Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd. Suite 600W
Dallas TX 75244
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Report Date: May 20, 2002
Project: Amberpoint Building No. 1
Amberpoint Bus. Pk. ~ Coppell
Coppell, Texas
Project Number: 94021029
Material Information
Specified Strength: 3000 psi @ 28 Days
Batch Time: 11:37am
Supplier: Potter
Truck No: 102
Mix I.D. No.: 9337
Plant: 16
Field Test Data
Test
Result
Slump, inches: 5.50
Air Content, %: 1.4
Concrete Temperature? F: 86
Ambient Temperature, o F: 82
Plastic Unit Weight, pcf:
Laboratory Test Data
Ticket No: 613758
Sample Information
Sample Time: 12:20pm Date Cast: May 11, 2002
Technician: Brad Rengstorff
Weather Conditions: Clear
Accumulative Yards: 450
Placement Method: Pump
Sample Locations: Panel SW7
Placement Location: Panel 39-43, 46-52, 91, 92, A, B, C,
SW1-SW8
Specification Test Method
4-6 ASTM C-143
N/A ASTM C-231
ASTM C1064
ASTM C-1064
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No: ID (inches) (sq. inches) Tested (days) (lbs) (psi)
5 1 6.00 28.27 05/14/2002 3 90,300 3,190
5 2 6.00 28.27 05/18/2002 7 114,930 4,060
5 3 6.00 28.27 05/18/2002 7 112,870 3,990
Average 4,030
5 4 06/08/2002 28
5 5 06/08/2002 28
Services - Obtain samples of fresh concrete at the Placement locations, perform required field tests and cast compressive
strength samples.
Technician: Brad Rengstorff
Report Distribution:
(1) Transwestem Commercial Sen'ices
(1) O'Brien & Associates Inc
(1) TechniStmctures thc
(1) City of Coppell - BIdg Insp
(1) Hill & Wilkinson Ltd
(1) Halff Associates
Reviewed by:
HBC Eng~
Eugene Harbour
(1) City of Coppell - Censtr Insp (1) State Farm Insurance Pdnclpst
The tests were performed in general accordance with applicable ASTM, A.ASHTO, or DOT test methods. This repo~ is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are no~ necessarily indicative of the properties of other apparently similar er identical
materials.
Page 5 of 5
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021029.0227
Service Date: April 19, 2002
Client: Transwestem Commemial Services
Attn: Jim Gaspard
5001 Spring Valley Rd. Suite 600W
Dallas TX 75244
ENG[NF-.ER/NG
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
(214) 630-101o
Report Date: May 20, 2002
Project: Amberpoint Building No. 1
Amberpoint Bus. Pk. ~ Coppell
Coppell, Texas
Project Number: 94021029
Material Information
Specified Strength: 3000 psi ~ 28 Days
Batch Time: 10:19am
Supplier: Potter
Track No: 102
Mix I.D. No.: 9337
Field Test Data
Test
Slump, inches:
Air Content, %:
Concrete Temperature, o F:
Ambient Temperature, o F:
Plastic Unit Weight, pcf:
Laboratory Test Data
Plant: 16
Result
6.00
77
76
Ticket No: 613131
Sample Information
Sample Time: 11:00am Date Cast:April 19, 2002
Technician: Gerry Graham
Weather Conditions: Cloudy
Accumulative Yards: 10
Placement Method: Tailgate
Sample Locations: Pier B/11.1
Placement Location: Piers B/11.1, D.3/11 and E.7/11
Specification
Test Method
5-7 ASTM C-143
None
ASTM C1064
ASTM C-1064
Set Specimen Diameter Area Date
No. ID (inches) (sq. inches) Tested
1 I 6.00 28.27 04/26/2002
1 2 6.00 28.27 04/2612002
1 3 6.00 28:27 05/17/2002
1 4 6.00 28.27 05/17/2002
Age at
Test
(days)
Maximum Compressive
Load Strength
(lbs) (psi)
7 81,080 2,870
7 90,250 3,190
Average 3,030
28 140,350 4,960
28 139,980 4,950
Average 4,960
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Gerry Graham
Report Distribution:
(1) Transwestem Commercial Services
(1) O'Brion & Associates Inc
(1) TechniStructures Inc
(1) City of Coppell - Censtr Insp
(1) City of Coppell - BIdg Insp
(1) Hill & Wilkinson Ltd
(1) Halff Associates
(1) State Farm Insurance
Reviewed by:
HBC Eng~
Eugene Harbour
P~ncipei
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusiveiy fo~ the use of the client
indicated above and shall no~ be )'eprcduced except in full without the written approval of Terracen. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of o~her apparently similar or identical
materials.
Page 1 of 1