Amberpoint BP-LR020523CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021029.0280 Service Date: May 15, 2002 Client: Transwestem Commercial Services Attn: Jim Gaspard 5001 Spring Valley Rd. Suite 600W Dallas TX 75244 8901 Carpenter Fm/y., Suite #100 Dallas, Texas 75247 (214) 630-1010 Report Date: May 23, 2002 Project: Amberpoint Building No. 1 Amberpoint Bus. Pk. (~ Coppell Coppell, Texas Project Number: 94021029 Material Information Specified Strength: 3500 psi (~ 28 Days Batch Time: 10:22am Supplier. Potter Truck No: 115 Mix i.D. No.: 9337 Plant: 16 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature,° F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laborator~ Test Data Result 6.75 1.1 74 74 Set Specimen Diameter Area No. ID (inches) (sq._~ inches) 1 I 6.00 28.27 1 2 6.00 28.27 Ticket No: 613762 Sample Information sample Time: 11 :lOam Technician: Burl Thomas Weather Conditions: Date Cast: May 15, 2002 Placement Method: Sample Locations: Panel 44 Placement Location: Panels- 44, 45, 101 and 102 Specification Test Method 3-5 ASTM C-143 N/A ASTM C-231 ASTM C1064 ASTM C-1064 Age at Maximum Compressive Date Test Load Strength Tested (days) (lbs) (psi) 05/21/2002 6 109,180 3,860 05/22/2002 7 120,880 4,270 1 3 1 4. Services - 06/12/2002 28 06/12/2002 28 Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. HBC Engi eedn Repo[t Distribution: (1) Transwestem Commercial Services (1) City of Coppell- Bldg Insp (1) O'Brlen & Associates Inc (1) Hill & VVilldnson Ltd Reviewed by: (1) TechniStructures Inc (1) Halff Associates E (1) City of ~1 - Constr Insp (1) State Farm Insurance Princ~al The tests were performed in general accordance with applicable ASTM, AASHTO, °r DOT test metheds' This repo~t Is exclusively for the use of the client indicated above and shall nof be reproduced exce~ in full without the written approval of Ten~es~. Test results tra~-mmitted herein are ~ al~icable to the actual samples tested at the location(s) referenced and are no{ necessarily indicative of the properties of other apparenUy similar or identical materials. Page 1 of 1 CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021029.0244 Service Date: April 24, 2002 Client: Transwestem Commercial Services Attn: Jim Gaspard 5001 Spdng Valley Rd. Suite 600W Dallas TX 75244 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Report Date: May 23, 2002 ProjeCt: Amberpoint Building No. 1 Amberpoint Bus. Pk. ~ Coppell Coppell, Texas Project Number: 94021029 Material Information Specified Strength: 3000 psi @ 28 Days Batch Time: 10:39am Supplier: Potter Truck No: 113 Mix I.D. No.: 9337 Plant: 16 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature,° F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Set Specimen No. ID I 1 I 2 Result 6.25 81 Ticket No: 613378 1 3 1 4 Services - Sample Information Sample Time: 10:46am Date Cast: April 24, 2002 Technician: Ger;y Graham Weather Conditions: Accumulative Yards: 10 Placement Method: Direct Discharge Sample Locations: Piers E.6/1 and F.4/1 Placement Location: Piers Specification Test Method 5-7 ASTM C-143 N/A ASTM C-231 ASTM C1064 ASTM C-1064 Age at Maximum Compressive Diameter Area Date Test Load Strength (inches) (sq. inches) Tested (days) (lbs) (psi) 6.00 28.27 05/01/2002 7 97,940 3,460 6.00 28.27 05/01/2002 7 99,870 3,530 Average 3,500 6.00 28.27 05/22/2002 28 131,460 4,650 6.00 28.27 05/22/2002 28 131,730 4,660 Average 4,660 Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Gerry Graham Report Distribution: (1) Tmnswestem Commercial Ser~=es (1) O'Brien & Associates Inc (1) TechniStructures Inc (1) City of Coppetl - Constr Insp (1) City of Coppell - Bldg Insp (1) Hill & Wilklnso~ Ltd (t) Halff Associates (1) State Farm Insurance Reviewed by: HBC E~ Eugene Harbeur The t_~_~ were perforrned in general accordance with applicable ASTM, AASHTO, or DOT test mefl~xis- This report Is ex~usively for the use of the ~dient indicated above and shall not be reproduced excel~ In full without the written approval of Terrecon. Test results transmitted herein are o~y applicable to the actual samples tested at the Iocatiort(s) referenced and am' not necessarily Indicative of the properties of.other ap~ar~-~u'y similar or identical materials. Page I of 1 CONCRETE COMPRESSIVE STRENGTH TEST Report Number:. 94021029.0237 Service Date: April 23, 2002 Client: Transwestem Commercial Services Attn: Jim Gaspard 5001 Spring Valley Rd. Suite 600W Dallas TX 75244 8901 Carpenter Fn~., Suite #100 Dallas, Texas 75247 (214) 630-1010 Report Date: May 23, 2002 Project: Amberpoint Building No. 1 Amberpoint Bus. Pk. ~ Coppell Coppell, Texas Project Number: 94021029 Material Information Specified Strength: 3000 psi ~ 28 Days Batch Time: 12:09pm Plant: 16 Supplier:. Potter Truck No: 102 Mix i.D. No.: 7752 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Set Specimen No. ID 1 1 1 2 Ticket No: 613327 Sample Information Sample Time: 12:21pm . Date Cast: April 23, 2002 Technician: Gerry Greham Weather Conditions: Fair, partly cloudy Accumulative Yards: 360 Placement Method: Direct Discharge Sample Locations: Pier G.6/1 Placement Location: Piers 1 3 1 4 Services - Result Specification Test Method 5.50 5-7 ASTM C-143 N/A 84 ASTM C1064 80 ASTM C-1064 Age at Maximum Compressive Diameter Area Date Test Load Strength (inches) (sq. inches) Tested (days) (lbs) (psi) . 6.00 28.27 04/30/2002 7 99,820 3,530 6.00 28.27 04/30/2002 7 98,710 3,490 Average 3,510 6.00 28.27 05/21/2002 28 121,430 4,290 6.00 28.27 05/21/2002 28 114,320 4,040 Average 4,170 Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Gemj Graham Report Distribution: (1) Transwestem C~nmemial Services (1) O'Brten & Associates Inc (1) Techn~Structures Inc (t) City of Coppall- Bldg Insp (1) Hill & Wilkinson Ltd (1) Halff Associates Reviewed by: HBC Engine~_~/~ Eugene H~tx~ur (1) City of Coppall - Conatr Insp (1) State Farm Insurance Principal The tests were performed In generat accordance with applicable ASTM, AASHTO, °r DOT test me~xJs' This relx~ is e-~?-'~-'sively f°r the use °f the clk~ indicated above and shall not be reproduced except in full without the written approval of Ten*a~. Test results transmitted herein are o~ly applicable to the actual samples tested at the location(s) referenced and are nof necessarily indicative of the properties of other apparcmtly similar o~ identical materials. ~w~,,, ~ Page 1 of 1 CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021029.0238 Service Date: April 23, 2002 Client: Transwestem Commemial Services Attn: Jim Gaspard 5001 Spring Valley Rd. Suite 600W Dallas TX 75244 8901 Carpenter Fnvy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Report Date: May 23, 2002 Project: Amberpoint Building No. 1 Amberpoint Bus. Pk. (~ Coppell Coppell, Texas Project Number: 94021029 Material Information Specified Strength: 3000 psi (~ 28 Days Batch Time: 4:21am Supplier: Potter Track No: 116 Mix I.D. No.: 9337 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Set Specimen No. ID I 1 I 2 Plant: 16 Ticket No: 613255 Sample Information Sample Time: 4:40am Date Cast: April 23, 2002 Technician: Marvin Arandia Weather Conditions: Cloudy Accumulative Yards: 20 Placement Method: Pump Sample Locations: Panel #38 Placement Location: Panels ~38 to #22 1 3 I 4 Result Specification Test Method 5.50 ASTM C-143 1.3 ASTM C-231 73 ASTM C1064 56 ASTM C-1064 Age at Maximum Compressive Diameter Area Date Test Load Strength (in,ches) (sq. inches) Tested (days) (lbs) (psi) 6.00 28.27 04/30/2002 7 117,480 4,150 6.00 28.27 04/30/2002 7 118,230 4,180 Average 4~t70 6.00 28.27 05/21/2002 28 131,100 4,640 6.00 28.27 05/21/2002 28 137,720 4,870 Average 4,760 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast comp[~e=s;ve strength samples. The ~__~__ were pe~forrned In general accordance with applicable ASTM, AASHTO, or DOT test methods. This report Is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are n~ nece~__~3_~ly Indicative of the properties of other apparently similar or identical materials. Page 1 of 4 o~ss,~=.~... CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021029.0238 Service Date: April 23, 2002 Client: Transwestem Commemial Services Attn: Jim Gaspard 5001 Spring Valley Rd. Suite 600W Dallas TX 75244 8901 Carpenter Fwaj., Suite #100 Dallas, Texas 75247 (214) 630-1010 Report Date: May 23, 2002 Project: Amberpoint Building No. 1 Amberpoint Bus. Pk. @ Coppell Coppell, Texas Project Number: 94021029 Material Information Specified Strength: 3000 psi (~ 28 Days Batch Time: 5:17am Plant: 16 Supplier: Potter Truck No: 114 Mix I.D. No.: 9337 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, o F: Ambier~ Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data ResuE 6.00 1.2 80 56 Ticket No: 612264 Sample Information sample Time: 5:50am Date Cast: April 23, 2002 Technician: Marvin Arandia Weather Conditions: Cloudy Accumulative Yards: 110 Placement Method: Pump Sample Locations: Panel #34 Placement Location: See page 1 . Specification Test Method ASTM C-143 ASTM C-231 ASTM C1064 ASTM C-1064 Age at Set Specimen Diameter Area Date Test No. ID (incheS) (sq. inches) Tested (days) 2 1 6.00 28.27 04/30/2002 7 2 2 6.00 28.27 04/30/2002 7 2 3 6.00 28.27 05/21/2002 2 4 6.00 28.27 05/21/2002 Maximum Compressive Load Strength (lbs) (psi) 101,950 3,610 106,510 3,770 Average 3,690 28 135,680 4,800 28 129,770 4,590 Average 4,700 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general acc~'dance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the indicated above and shall no~ be reproduced except in full without the written approval of Tarracen. Test results transmitted herein are ~ly apldicabte to the actual sampis~ tested at the location(s) referenced and are no~ necessarily indicative of the properties of ofher apparently similar ar identical materials. Page 2 of 4 CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021029.0238 Service Date: April 23, 2002 Client: Transwestem Commercial Services Attn: Jim Gaspard 5001 Spring Valley Rd. Suite 600W Dallas TX 75244 8901 Carpenter Fn~y., Suite #100 Dallas, Texas 75247 (214) 630-1010 Report Date: May 23, 2002 Project: Amberpoint Building No. 1 Amberpoint Bus. Pk. (~ Coppell Coppell, Texas Project Number: 94021029 Material Information Specified Strength: 3000 psi ~ 28 Days Batch Time: 5:57am Plant: 16 Supplier: Potter Truck No: 109 Mix I.D. No.: 9337 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature? F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Set Specimen No. ID 3 1 3 2 Ticket No: 613273 Sample Information Sample Time: 6:20am Date Cast: April 23, 2002 Technician: Marvin Arandia Weather Conditions: Cloudy Accumulative Yards: 200 Placement Method: Pump Sample Locations: Panel fY29 Placement Location: See page 1 3 3 3 4 Result Specification Test Method 5.00 ASTM C-143 1.7 ASTM C-231 80 ASTM Cl 064 61 ASTM C-1064 Age at Maximum Compressive Diameter Area Date Test Load Strength (inches) (scI. inches) Tested (days) (lbs) (psi) 6.00 28.27 04/30/2002 7 107,780 3,810 6.00 28.27 04/30~2002 7 113,380 4,010 Average 3,9t 0 6.00 28.27 05/21/2002 28 129,040 4,560 6.00 28.27 05/21/2002 28 140,870 4,980 Average 4,770 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicatde ASTM, AASHTO, or DOT test me~hnds. This report is exduslvely for the use of the client indicated above and shall not be reproduced excep~ in full without the written approval of Terrecen. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of cther apparently similar or identical materials. Page 3 of 4 ~s.o~..~w CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021029.0238 Service Date: Apdl 23, 2002 Client: Transwestem Commercial Services Attn: Jim Gaspard 5001 Spdng Valley Rd. Suite 600W Dallas TX 75244 8901 Carpenter Finny., Suite #100 Dallas, Texas 75247 (214) 630-1010 Report Date: May 23, 2002 Project: Amberpoint Building No. 1 Amberpoint Bus. Pk. ~ Coppell Coppell, Texas Project Number: 94021029 Material Information Specified Strength: 3000 psi ~ 28 Days Batch Time: 6'.58am Supplier.' Potter Track No: 106 Mix I.D. No.: 9337 Plant: 16 Field Test Data Test Result Slump, inches: 5.25 Air Content, %: 1.4 Concrete Temperature,o F: 80 Ambient Temperature, o F: 65 Plastic Unit Weight, pcf: LaboratorF Test Data Set Specimen Diameter Area No. ID (inches) (sq? inches) 4 1 6.00 28.27 4 2 6.00 28.27 4 3 6.00 28.27 4 4 6.00 28.27 Ticket No: 613283 SamPle Information sample Time: 7:25am Date Cast: April 23, 2002 Technician: Marvin Arandia Weather Conditions: Cloudy Accumulative Yards: 300 Placement Method: Pump Sample Locations: Panel #25 Placeme*nt Location: See page 1 Specification Test Method ASTM C-143 ASTM C-231 ASTM C1064 ASTM C-1064 Age at Maximum Compressive Date Test Load Strength Tested (days) (lbs) (ps~ 04/30~2002 7 110,030 3,890 04/30/2002 7 104,510 3,700 Average 3,800 05/21/2002 28 149,170 5,280 05/21/2002 28 148,000 5,230 Average 5,260 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Marvin Arandia' Report Distribution: (1) Transwestern Commercial Senices (1) O'Bdon & Associates Inc (1) TechniStructures Inc (f) c~ of coppe~ - constr ~nsp (1) City of Coppell - Bldg Insp (1) Hill & Willdnson Ltd (1) Heiff Associates (1) State Farm Insurance Reviewed by: HBC Engi~ Eugene Harbour Pdncipat Thet,~_ wereperformedlngoneralaccerdancewith appiicableASTM, AASHTO, or DOTtest metheds. Thla report is exclueiveiy for the usa of lhe cllant ' indicated above and shall no~ be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of ather apparently similar or identical materials. Page 4 of 4 ~'~" CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021029.0242 Service Date: April 23, 2002 Client: Transwestem Commercial Services Attn: Jim Gaspard 5001 Spdng Valley Rd. Suite 600W Dallas TX 75244 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Report Date: May 23, 2002 Project: Amberpoint Building No. 1 Amberpoint Bus. Pk. (~ Coppell Coppell, Texas Project Number: 94021029 Material Information Specified Strength: 4000 psi ~ 28 Days Batch Time: 8:45am Supplier: Potter Truck No: 106 Mix I.D. No.: 7752 Plant: 16 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit WeigM, pcf: Laboratory Test Data Set Specimen No. ID I 1 I 2 Ticket No: 613292 Sample Information Sample Time: 9:15am Date Cast:April 23, 2002 Technician: Marvin Arandia Weather Conditions: Cloudy Accumulative Yards: 20 Placement Method: Pump Sample Locations: See attached sketch Placement Location: Pavement - SE of jobsite I 3 1 4 Result Specification Test Method 5.00 5 Max. ASTM C-143 6.2 4-8 ASTM C-231 80 ASTM C1064 73 ASTM C-1064 Age at Maximum Compressive Diameter Area Date Test Load Strength (inches) (scI. inches) Tested (days) (lbs) (psi) 6.00 28.27 04/30~2002 7 102,690 3,630 6.00 28.27 04/30/2002 7 103,570 3,660 Average 3,650 6.00 28.27 05/21/2002 28 130,370 4,610 6.00 28.27 05/21/2002 28 147,700 5,220 Average 4,920 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed In general accordance with applicable ASTM, AASHTO, or DOT test mat.,ds. This report is e0~olusivety for the use of the indicated above and shaft noi be repmcluced except in full without the written approval of Termcon. Test results transmitted herein are only appt'-~--~e to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical Page I of 6 CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021029.0242 Service Date: April 23, 2002 Client: Transwestem Commercial Services Attn: Jim Gaspard 5001 Spdng Valley Rd. Suite 600W Dallas TX 75244 8901 Carponter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Report Date: May 23, 2002 Project: Amberpoint Building No. 1 Amberpoint Bus. pk. ~ Coppell Coppell, Texas Project Number: 94021029 Material Information Specified Strength: 4000 psi (~ 28 Days Batch Time: 9:24am Supplier. Potter Track No: 109 Mix I.D. No.: 7752 Plant: 16 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Set Specimen No. ID 2 1 2 2 Ticket No: 613300 Sample Information Sample Time: 9:50am Date Cast: April 23, 2002 Technician: Marvin Arandia Weather Conditions: Cloudy Accumulative Yards: 100 Placement Method: Pump Sample Locations: See attached sketch Placement Location: See page 1 2 3 2 4 Result Specification Test Method 5.00 5 Max. ASTM C-143 6 4-8 ASTM C-231 80 ASTM C1064 81 ASTM C-1064 Age at Maximum Compressive Diameter Area Date Test Load Strength (inches) (sq. inches) Tested (days) (lbs) 6.00 28.27 04~30~2002 7 114,580 4,050 6.00 28.27 04/30/2002 7 117,090 4,140 Average 4,t00 6.00 28.27 05/21/2002 28 138,840 4,910 6.00 28.27 05/21/2002 28 142,450 5,040 Average 4,980 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tasts were performed in genersi accordance with applicable ASTM, AASHTO, or DOT rem methnds. This repod is exclusivsiy for the uas of the clkmt indicated above and shall not be reproduced e~(capt in full without the written approval of Torracoo. Te~t results transmitted be~sin are only appl'maple to the actual samples tested at the location(s) referenced and are nol neesasadly indicative of the p~ of ddaer apparontly similar or identical materials. Page 2 of 6 CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021029.0242 Service Date: April 23, 2002 Client: Transwestem Commercial Services Attn: Jim Gaspard 5001 Spdng Valley Rd. Suite 600W Dallas TX 75244 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Report Date: May 23, 2002 Project: Amberpoint Building No. 1 Amberpoint Bus. Pk. ~ Coppell Coppell, Texas Project Number: 94021029 Material Information Specified Strength: 4000 psi ~ 28 Days Batch Time: 10:22am Plant: 18 Supplie~ Potter Truck No: 115 Mix I.D. No.: 7752 Field Test Data Test Result Slump, inches: 5.50 Air Content, %: 5 Concrete Temperature, o F: 87 Ambient Temperature, o F: 85 Plastic Unit Weight, pcf: Laboratory Test Data Set Specimen No. ID 3 1 3 2 Ticket No: 613311 3 3 3 4 Sample Information Sample Time: 11:20am Date Cast: April 23, 2002 Technician: Marvin Arandia Weather Conditions: Partly cloudy Accumulative Yards: 200 Placement Method: Pump Sample Locations: See attached sketch Placement Location: See page 1 Specification Test Method 5 Max. ASTM C-143 4-8 ASTM C-231 ASTM Cl 064 ASTM C-1064 Age at Maximum Compressive Diameter Area Date Test Load Strength (inches) (sq. inches) Tested (days) (lbs) (psO 6.00 28.27 04/30/2002 7 100,450 3,550 6.00 28.27 04/30/2002 7 100,930 3,570 Average 3,560 6.00 28.27 05/21/2002 28 129,500 4,580 6.00 28.27 05/21/2002 28 132,000 4,670 Average 4,630 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test mefl~ds. This report is exclusively for the use of the client indicated above and shall n~ be reproduced except in full without the. written approval of Tenacon. Test results transmitted horeln are only aplfltcable to the actual samples tested at the lacation(s) referenced and are not necessarily indicative of the ixoperlles of other apparently similar or identical materials. Page 3 of 6 "~.~"~'*"'~, · CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021029.0242 Service Date: April 23, 2002 Client: Transwestem Commercial Services Attn: Jim Gaspard 5001 Spdng Valley Rd. Suite 600W Dallas TX 75244 8901 Carpenter Ftwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Report Date: May 23, 2002 Project: Amberpoint Building No. 1 Amberpoint Bus. Pk. ~ Coppell Coppell, Texas Project Number: 94021029 Material Information Specified Strength: 4000 psi (~ 28 Days Batch Time: 11:35am Supplier: Potter Truck No: 101 Mix I.D. No.: 7752 Plant: 16 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature,° F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Set Specimen No. ID 4 1 4 2 Ticket No: 613323 Sample Information Sample Time: 12:20pm Date Cast: April 23, 2002 Technician: Marvin Arandia Weather Conditions: Partly cloudy Accumulative Yards: 320 Placement Method: Pump Sample Locations: See attached sketch Placement Location: See page 1 4 3 4 4 Result Specification Test Method 5.50 .5 Max. ASTM C-143 4.9 4-8 ASTM C-231 89 ASTM C1064 88 ASTM C-1064 Age at Maximum Compressive Diameter Area Date Test Load St~j~n~lth (inches) (sq. inches) Tested (days) (lbs) 6.00 28.27 04/30/2002' 7 100,300 3,550 6.00 28.27 04~30~2002 7 98,260 3,470 Average 3,6t0 6.00 28.27 05/21/2002 28 119,630 4,230 6.00 28.27 05/21/2002 28. 125,360 4,430 Average 4,330 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Tbe tests were performed in general accordance with app#cable ASTM, AASHTO, °r DOT test me~heds. This report is exciuslvaty for the u~e of the dle~ indicated above and shall n~ be reproduced except in full without the written approval of Terracon. Test _r,~,__,~ts transmitted herein are only applicable to the actual samldes tested at the location(s) referenced and are not necessarily indicative of the pgopmties of o~be~ appment~ similar = identical materials. Page4of6 CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021029.0242 Service Date: April 23, 2002 Client: Transwestem Commercial Services Attn: Jim Gaspard 5001 Spring Valley Rd. Suite 600W Dallas TX 75244 8901 Carpenter Fnvy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Report Date: May 23, '2002 Project: Amberpoint Building No. 1 Amberpoint Bus. Pk. (~ Coppell Coppell, Texas Project Number: 94021029 Material Information Specified Strength: 4000 psi (~ 28 Days Batch Time: 1:30pm Supplier:. Potter Truck No: 102 Mix I.D. No.: 7752 Plant: 16 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Set Specimen Diameter No. ID (inches) 5 1 6.00 5 2 6.00 Ticket No: 613334 Sample Information Sample Time: 2:20pm Date Cast: April 23, 2002 Technician: Marvin Arandia Weather Conditions: Partly cloudy Accumulative Yards: 420 Placement Method: Pump Sample Locations: See attached sketch Placement Location: See page 1 5 3 6.00 5 4 6.00 Result Specification Test Method 3.50 5 Max. ASTM C-143 5 4-8 ASTM C-231 87 ASTM C1064 91 ASTM C-1064 Age at Maximum Compressive Area Date Test Load Strength (sq. inches) Tested (days) (lbs) (PS0 28.27 04/30/2002 7 112,600 3,980 28.27 04/30/2002 7 106,720 3,770 Average 3,880 28.27 05/21/2002 28 140,290 4,960 28.27 05/21/2002 28 137,850 4,870 Average 4,920 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The =_~ were performed in general accordance wtth apl~lcable ASTM, AASHTO, or DOT teat meUx)~. This repod la exclusively for the use of the c#ent indicated above and shall not be reproduced except In fuff without the written approval of TefTaco~. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of oth~- apparently similar ¢x identical Page 5 of 6 · CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021029.0242 Service Date: April 23, 2002 Client: Transwestem Commercial Services Attn: Jim Gaspard 5001 Spring Valley Rd. Suite 600W Dallas TX 75244 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Report Date: May 23, 2002 Project: Amberpoint Building No. 1 Amberpoint Bus. Pk. (~ Coppell o Coppell, Texas Project Number: 94021029 Material Information Specified Strength: 4000 psi (~ 28 Days Batch Time: 3:04pm Supplier: Potter Truck No: 101 Mix I.D. No.: 7752 Plant: 16 Field Test Data Test Result Slump, inches: 5.50 Air Content, %: 1.4 Concrete Temperature, o F: 87 Ambient Temperature, o F: 92 Plastic Unit Weight, pcf: Laboratory Test Data Set Specimen No. ID 6 1 6 2 Diameter Area (inches) (sq. inches) 6.00 28.27 6.00 2~.27 6.00. 28.27 6.00 28.27 6 3 6 4 Ticket No: 613344 Sample Information Sample Time: 3:40pm Date Cast:April 23, 2002 Technician: Marvin Arandia Weather Conditions: Partly cloudy Accumulative Yards: 520 Placement Method: Pump Sample Locations: See attached sketch Placement Location: See page 1 Specification Test Method 5 Max. ASTM C-143 4-8 ASTM C-231 ASTM C1064 ASTM C-1064 Age at Maximum Compressive Date Test Load Strength Tested (days) (lbs) (psi) 04/30/2002 7 92,070 3,260 04~30~2002 7 93,140 3,290 Average 3,280 05/21/2002 28 108,220 3,830* 05121/2002 28 112,470 3,980* Average ~ Comments: * Does not comply with specified strength. Services - Obtain samples of fresh concrete at the placement locations, I strength samples. Technician: Marvin Arandia Report Distribution: (1) Tran~'.~ern Commercial Services (1) O'Brian & Associates Inc (1) TechniStruotures Inc (1) City of Coppeit - Constr Insp (1) c~y of copp~- B~O ~nsp (1) Hill & v~rllk]nson Ltd (1) Halff ~tes (1) State Farm Insurance project plans/epeeifl~tions based on our undemtandi_ng of the requirements, Reviewed by: HBC Enginec, j~ Eugene Harbour Prlr~pal The ~ were performed in general accordance with apflticable ASTM, AASHTO, o~ DOT test methods. This relx~ is ex~usive~y for the use of the ~ indicated above and shall not be reproduced except in full without the written approval of Te~racon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar o~ identical materials. Page 6 of 6 ~.,-.~.~ STATISTICAL ANALYSIS OF CONCRETE MIXTURES Report Number: 94021029:0287 Service Date: May 23, 2002 Client: Transwestern Commercial Services Attn: Jim Gaspard 5001 Spring Valley Rd. Suite 600W Dallas TX 75244 8901 Carpenter Fn~,y., Suite #100 Dallas, Texas 75247 (214) 630-1010 Report Date: May 23, 2002 Project: Amberpoint Building No. 1 Amberpoint Bus. Pk. {~ Coppell Coppell, Texas Project Number: 94021029 Specification Requirements: Concrete Class: 7752 PROJECT DATA 4000 psi @ 28 Days REPORT OF TESTS Number Air Concrete Compressive Running Report Of Slump Content Temp Strength 3 Test Avg Date Number Set Samples (in.) (%) (F) PSI PSI 03/27/2002 94021029.0156 1 2 7.25 7.1 63 4605 03/27/2002 94021029.0156 2 2 7.75 6.8 64 4185 03/27~2002 94021029.0156 3 2 5.00 6.1 68 4865 4552 03/27/2002 94021029.0156 4 2 5.25 6.4 70 4505 4518 03/27/2002 94021029.0156 5 2 5.00 6.2 70 4055 4475 03/27/2002 94021029.0156 6 2 6.25 7.0 76 3900 4153 03/28/2002 94021029.0162 1 2 6.00 6.3 59 5190 4382 03/28/2002 94021029.0162 2 2 5.75 6.3 62 5200 4763 03/28/2002 94021029.0162 3 2 5.00 6.1 59 4620 5003 03/28/2002 94021029.0162 4 2 7.00 6:5 65 4025 4615 04/23/2002 94021029.0237 1 2 5.50 84 4165 4270 04/23/2002 94021029.0242 1 2 5.00 6.2 80 4915 4368 04/23/2002 94021029.0242 2 2 5.00 6 80 4975. 4685 04/23/2002 94021029.0242 3 2 5.50 5 87 4625 4838 04/23/2002 94021029.0242 4 2 5.50 4.9 89 4330 4643 04/23/2002 94021029.0242 5 2 3.50 5 87 4915 4623 04/23/2002 94021029.0242 6 2' 5.50 1.4 87 '~'~ 4383~ J Average of all sets of three consecutive strengths equals or exceeds the project specifica~EonsT~. Average of t7 sets = 4530 PSI ~} 28 days The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Tenacon. Test results transmitted herein are only appacabie to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 2 PROJECT: PROJECT NO.: CALCD. BY: CHKD BY: DATE: DATE: ii..I