Northpoint Dr-LR020530CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021061.0041
Service Date: May 22, 2002
Client: Transwestern Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd Suite 600W
Dallas TX 75244
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Report Date: May 30, 2002
Project: Northpoint Drive &
Associated Utilities
Coppell, Texas
Project Number: 94021061
Material Information
Specified Strength: 3000 psi @ 28 Days
Batch Time: Plant: On-Site
Supplier: GTI
Truck No: Ticket No:
Mix I.D. No.: 2328
Sample Information
sample Time: 7:50am Date Cast: May 22, 2002
Technician: Marvin Arandia
Weather Conditions: Clear
Accumulative Yards: 150
Placement Method: Direct Discharge
Sample Locations: 10+50 Stationary
Placement Location: Pavement SE of Amberpoint
Field Test Data
Test
Result
Slump, inches: 2.75
Air Content, %: 4.6
Concrete Temperature,° F: 75
Ambient Temperature, o F: 65
Plastic Unit Weight, pcf: 145.4
Laboratory Test Data
Specification
Test Method
ASTM C-143
ASTM C-231
ASTM C1064
ASTM C-1064
ASTM C-138
Age at
Test
(days)
7
Set Specimen Diameter Area Date
No. ID (inches) (sq. inches) Tested
1 1 6.00 28.27 05/29/2002
I 2 6.00 28.27 05/29~2002 7
Average
I 3 06/19/2002 28
1 4 06/19/2002 28
Maximum Compressive
Load Strength
(lbs) (psi)
105,110 3,720
101,460 3,590
3,660
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This repod is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
Page 1 of 10
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021061.0041
Service Date: May 22, 2002
ENGINEEI~ING
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Client: Transwestem Commemial Services
Attn: Jim Gaspard
5001 Spdng Valley Rd Suite 600W
Dallas TX 75244
Report Date: May 30, 2002
Project: Northpoint Drive &
Associated Utilities
Coppell, Texas
Project Number: 94021061
Material Information
Specified Strength: 3000 psi @ 28 Days
Batch Time: Plant: On-Site
Supplier: GTI
Truck No: Ticket No:
Mix I.D. No.: 2328
Field Test Data
Test
Slump, inches:
Air Content, %:
Concrete Temperature,o F:
Ambient Temperature, o F:
Plastic Unit Weight, pcf:
Laboratory Test Data
Sample Information
Sample Time: 8:50am Date Cast: May 22, 2002
Technician: Marvin Arandia
Weather Conditions: Clear
Accumulative Yards: 300
Placement Method: Direct Discharge
Sample Locations: Sra. 13+15
Placement Location: See page I
Result Specification Test Method
3.00 ASTM C-143
4.0 ASTM C-231
75 ASTM Cl 064
66 ASTM C-1064
148.0 ASTM C-138
Age at
Set Specimen Diameter Area Date Test
No. ID (inches) (sq. inches) Tested (days)
2 1 6.00 28.27 05/29/2002 7
2 2 6.00 28.27 05/29/2002 7
Average
2 3 06/19/2002 28
2 4 06/19/2002 28
Maximum Compressive
Load Strength
(lbs) (psi)
114,280 4,040
112,690 3,990
4,020
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 2 of 10 o~ LLW/~O14~ult~e Key
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021061.0041
Service Date: May 22, 2002
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Client: Transwestern Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd Suite 600W
Dallas TX 75244
Report Date: May 30, 2002
Project: Northpoint Drive &
Associated Utilities
Coppell, Texas
Project Number: 94021061
Material Information
Specified Strength: 3000 psi (~ 28 Days
Batch Time: Plant: On-Site
Supplier: GTI
Truck No: Ticket No:
Mix I.D. No.: 2328
Field Test Data
Test
Result
Slump, inches: 3.00
Air Content, %: 4.2
Concrete Temperature, o F: 75
Ambient Temperature, o F: 80
Plastic Unit Weight, pcf: 147.8
Laboratory Test Data
Sample Information
Sample Time: 9:40am Date Cast: May 22, 2002
Technician: Marvin Arandia
Weather Conditions: Clear
Accumulative Yards: 450
Placement Method: Direct Discharge
Sample Locations: Sta. 14+30
Placement Location: See page 1
Specification
Test Method
ASTM C-143
ASTM C-231
ASTM C1064
ASTM C-1064
ASTM C-138
Age at
Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
3 1 6.00 28.27 05/29/2002 7 106,140 3,750
3 2 6.00 28.27 05/29/2002 7 105,200 3,720
Average 3,740
3 3 06/19/2002 28
3 4 06/19/2002 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terrecon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 3 of 10 o~ LLW~0~
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021061.0041
Service Date: May 22, 2002
ENGINF~E I~JNG
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Client: Transwestern Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd Suite 600W
Dallas TX 75244
Report Date: May 30, 2002
Project: Northpoint Drive &
Associated Utilities
Coppell, Texas
Project Number: 94021061
Material Information
Specified Strength: 3000 psi @ 28 Days
Batch Time: Plant: On-Site
Supplier: GTI
Truck No: Ticket No:
Mix I.D. No.: 2328
Field Test Data
Test
Result
Slump, inches: 3.50
Air Content, %: 4.7
Concrete Temperature, o F: 80
Ambient Temperature, o F: 78
Plastic Unit Weight, pcf: 147.6
Laboratory Test Data
Set Specimen Diameter Area
No. ID (inches) (sq. inches)
4 1 6.00 28.27
4 2 6.00 28.27
4 3
4 4
Sample Information
Sample Time: 10:35am Date Cast: May 22, 2002
Technician: Marvin Arandia
Weather Conditions: Partly cloudy
Accumulative Yards: 600
Placement Method: Direct Discharge
Sample Locations: Sta. 15+10
Placement Location: See page 1
Specification Test Method
ASTM C-143
ASTM C-231
ASTM Cl 064
ASTM C-1064
ASTM C-138
Age at
Maximum Compressive
Date Test Load Strength
Tested (~ (lbs) (~,~si)
05/2 /2002 7 08,640 3,660
05/29/2002 ~ 107,880 310
Average 3,830
06/19/2002 28
06/19/2002 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 4 of 10
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021061.0041
Service Date: May 22, 2002
EN(ZNF~RING
8901 Carpenter F,wvy,, Suite #100
Dallas, Texas 75247
(214) 630-1010
Client: Transwestern Commemial Services
Attn: Jim Gaspard
5001 Spring Valley Rd Suite 600W
Dallas TX 75244
Report Date: May 30, 2002
Project: Northpoint Drive &
Associated Utilities
Coppell, Texas
Project Number: 94021061
Material Information
Specified Strength: 3000 psi @ 28 Days
Batch Time: Plant: On-Site
Supplier: GTI
Truck No: Ticket No:
Mix I.D. No.: 2328
Field Test Data
Test Result
Slump, inches: 3.00
Air Content, %: 4.6
Concrete Temperature, o F: 80
Ambient Temperature, o F: 77
Plastic Unit Weight, pcf: 148.2
Laboratory Test Data
Set Specimen Diameter Area
No. ID (inches) (sq. inches)
Sample Information
sample Time: 11:30am Date Cast: May 22, 2002
Technician: Marvin Arandia
Weather Conditions: Partly cloudy
Accumulative Yards: 750
Placement Method: Direct Discharge
Sample Locations: Sta. 12+00
Placement Location: See page I
Specification Test Method
ASTM C-143
ASTM C-231
ASTM C1064
ASTM C-1064
ASTM C-138
Age at Maximum Compressive
Date Test Load Strength
Tested (days) (lbs) (psi)
5 I 6.00 28.27 05/29/2002 7 126,560 4,480
5 2 6.00 28.27 05/29/2002 7 123,800 4,380
Average 4,430
5 3 06/19/2002 28
5 4 06/19/2002 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were per[ormed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This repo~l is exclusively for the use of the client-
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 5 of 10 *,~LW~O~,..<W
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021061.0041
Service Date: May 22, 2002
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Client: Transwestern Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd Suite 600W
Dallas TX 75244
Report Date: May 30, 2002
Project: Northpoint Drive &
Associated Utilities
Coppell, Texas
Project Number: 94021061
Ma terial Information
Specified Strength: 3000 psi @ 28 Days
Batch Time: Plant: On-Site
Supplier: GTI
Truck No: Ticket No:
Mix I.D. No.: 2328
Sample Information
sample Time: 12:20pm Date Cast: May 22, 2002
Technician: Marvin Arandia
Weather Conditions: Partly cloudy
Accumulative Yards: 900
Placement Method: Direct Discharge
Sample Locations: Sta. 18+50
Placement Location: See page 1
Field Test Data
Test Result Specification Test Method
Slump, inches: 4.00 ASTM C-143
Air Content, %: 4.5 ASTM C-231
Concrete Temperature, o F: 75 ASTM C1064
Ambient Temperature, o F: 80 ASTM C-1064
Plastic Unit Weight, pcf: 148.6 ASTM C-138
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
6 I 6.00 28.27 05/29/2002 7 114,390 4,050
6 2 6.00 28.27 05/29/2002 7 116,700 4,130
Average 4,090
6 3 06/19/2002 28
6 4 06/19/2002 28
Services - Obtain samples of fresh concrete at the placement locations, pedorm required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AAS HTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 6 of 10 o~,.~o,.r...K~
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021061.0041
Service Date: May 22, 2002
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Client: Transwestern Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd Suite 600W
Dallas TX 75244
Report Date: May 30, 2002
Project: Northpoint Ddve &
Associated Utilities
Coppell, Texas
Project Number: 94021061
Material Information
Specified Strength: 3000 psi @ 28 Days
Batch Time: Plant: On-Site
Supplier: GTI
Truck No: Ticket No:
Mix I.D. No.: 2328
Field Test Data
Test
Result
Slump, inches: 4.00
Air Content, %: 5.5
Concrete Temperature,o F: 78
Ambient Temperature, o F: 80
Plastic Unit Weight, pcf: 142.0
Laboratory Test Data
Sample Information
Sample Time: 1:15pm Date Cast: May 22, 2002
Technician: Marvin Arandia
Weather Conditions: Partly cloudy
Accumulative Yards: 1050
Placement Method: Direct Discharge
Sample Locations: Sta. 19+70
Placement Location: See page 1
Specification Test Method
Set Specimen Diameter Area Date
No. ID (inches) (sq. inches) Tested
7 1 6.00 28.27 05/29/2002
7 2 6.00 28.27 05/29/2002
ASTM C-143
ASTM C-231
ASTM C1064
ASTM C-1064
ASTM C-138
Age at
Maximum Compressive
Test Load Strength
(days) (lbs) . (psi__~)
-~ 99,-'~-0 1 3,500
7 97,640 ~',','~ 0
Average 3,480
7 3 06/19/2002 28
7 4 06/19/2002 28
Services - Obtain samples of fresh concrete at the placement locations, pedorm required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and ara not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 7 of 10
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021061.0041
Service Date: May 22, 2002
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Client: Transwestern Commercial Services
Attn: Jim Gaspard
5001 Spdng Valley Rd Suite 600W
Dallas TX 75244
Report Date: May 30, 2002
Project: Northpoint Drive &
Associated Utilities
Coppell, Texas
Project Number: 94021061
Material Information
Specified Strength: 3000 psi (~ 28 Days
Batch Time: Plant: On-Site
Supplier: GTI
Truck No: Ticket No:
Mix I.D. No.: 2328
Field Test Data
Test
Slump, inches:
Air Content, %:
Concrete Temperature, o F:
Ambient Temperature, o F:
Plastic Unit Weight, pcf:
Laboratory Test Data
Sample Information
Sample Time: 2:30pm Date Cast: May 22, 2002
Technician: Marvin Arandia
Weather Conditions: Partly cloudy
Accumulative Yards: 1200
Placement Method: Direct Discharge
Sample Locations: Sta. 21+00
Placement Location: See page 1
Result Specification Test Method
3.00 ASTM C-143
4.8 ASTM C-231
82 ASTM C1064
80 ASTM C-1064
145.0 ASTM C-138
Age at
Set Specimen Diameter Area Date Test
No. ID (inches) (sq. inches) Tested (days)
8 1 6.00 28.27 05/2912002 7 106,330
8 2 6.00 28.27 05~29/2002 7 107,000
Average
8 3 06/19/2002 28
8 4 06/19/2002 28
Maximum Compressive
Load Strength
(lbs) , (psi)
3,770
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 8 of 10
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021061.0041
Service Date: May 22, 2002
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Client: Transwestem Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd Suite 600W
Dallas TX 75244
Report Date: May 30, 2002
Project: Northpoint Drive &
Associated Utilities
Coppell, Texas
Project Number: 94021061
Material Information
Specified Strength: 3000 psi ~ 28 Days
Batch Time: Plant: On-Site
Supplier: GTI
Truck No: Ticket No:
Mix I.D. No.: 2328
Field Test Data
Test
Result
Slump, inches: 5.00
Air Content, %: 5.0
Concrete Temperature, o F: 75
Ambient Temperature, o F: 82
Plastic Unit Weight, pcf: 145.6
Laboratory Test Data
Sample Information
Sample Time: 3:30pm Date Cast: May 22, 2002
Technician: Marvin Arandia
Weather Conditions: Partly cloudy
Accumulative Yards: 1350
Placement Method: Direct Discharge
Sample Locations: Sta. 22+60
Placement Location: See page 1
Specification Test Method
ASTM C-143
ASTM C-231
ASTM C1064
ASTM C-1064
ASTM C-138
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
9 1 6.00 28.27 05/29/2002 7 98,470 3,480
9 2 6.00 28.27 05/29/2002 7 105,020 3,710
Average 3,600
9 3 06/19/2002 28
9 4 06/19/2002 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the propedies of other apparently similar or identical
materials.
Page 9 of 10 o,~w~,~r,~
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021061.0041
Service Date: May 22, 2002
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Client: Transwestern Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd Suite 600W
Dallas TX 75244
Report Date: May 30, 2002
Project: Northpoint Drive &
Associated Utilities
Coppell, Texas
Project Number: 94021061
Material Information
Specified Strength: 3000 psi (~ 28 Days
Batch Time: Plant: On-Site
Supplier: GTI
Truck No: Ticket No:
Mix I.D. No.: 2328
Field Test Data
Test
Result
Slump, inches: 5.00
Air Content, %: 4.9
Concrete Temperature, o F: 81
Ambient Temperature, o F: 83
Plastic Unit Weight, pcf: 146.0
Laboratory Test Data
Sample Information
Sample Time: 4:55pm Date Cast: May 22, 2002
Technician: Marvin Arandia
Weather Conditions: Partly cloudy
Accumulative Yards: 1500
Placement Method: Direct Discharge
Sample Locations: Sta. 24+40
Placement Location: See page 1
Specification Test Method
ASTM C-143
ASTM C-231
ASTM C1064
ASTM C-1064
ASTM C- 138
Age at
Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
10 1 6.00 28.27 05/29/2002 7 104,840 ~' 3,710
10 2 6.00 28.27 05/29/2002 7 107,530 3,800
Average ~
10 3 06/19/2002 28
10 4 06/19/2002 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Marvin Arandia
Report Distribution:
(1) Transwestern Commercial Services
(1) Glenn Thurman Inc
(1) Halff Associates
(1) City of Coppell - Engineering
(1) City of Coppall - BIdg Insp
(1) State Farm Insurance
(1) Moss Construction
Reviewed by:
HBC Enginee<~
Eugene Harbour
Principal
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 10 of 10