Deforest Court-LR020531CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021148.0012 Service Date: May 2, 2002 Client: The Holmes Builders Attn: Jon Dostert /Dean Trudell 1406 Halsey Way Suite 100 Carrollton TX 75007 Material Information Specified Strength: 3000 psi 28 Days Batch Time: 9:30am Supplier: Redi -Mix Truck No: 221 Mix I.D. No.: 914MR Plant: 91 Field Test Data Test Result 5.50 Slump, inches: Air Content, Concrete Temperature,° F: 80 Ambient Temperature, F: 69 Plastic Unit Weight, pcf: Laboratory Test Data Set Specimen No. ID 1 1 1 2 1 3 1 4 Technician: Steve Campbell Report Distribution: (1) The Holmes Builders (1) City of Coppell Constr lnsp (1) City of Coppell Bldg Insp Diameter Area (inches) (sq. inches) 6.00 28.27 6.00 28.27 6.00 28.27 6.00 28.27 Ticket No: 156884 Report Date: Project: 6 Project'NumB¢r-- 94021148 Sample Information Sample Time: 10:45am Date Cast: May 2, 2002 Technician: Steve Campbell Weather Conditions: Cloudy Accumulative Yards: 10 Placement Method: Direct Discharge Sample Locations: Pier #43 Placement Location: Pier 40, 41, 43 Specification 5 -7 None Services Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. �i eForest C ngle Family Home oppell, Texas Age at Date Test Tested (days) 05/09/2002 7 05/09/2002 7 05/30/2002 28 05/30/2002 28 It Test Method ASTM C -143 ASTM C1064 ASTM C -1064 Reviewed by: o divi,j, ®cll cmco y ENGINEERING 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 214) 630 -1010 Maximum Compressive Load Strength (Ibs) (psi) 60,340 2,130 61,500 2,170 Average 2,150 91,720 3,240 92,280 3,260 Average 3,250 HBC Engineering Hussein H. Abusaad, P_E. Senior Project Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the dent- indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 1 OYLLWONI -Flrte Nay