June 6, 2002
Sanford P. Lahue, P. E.
Schrickel, Rollines and Associates, Inc.
1161 Corporate Drive West, Suite 200
Arlington, TX 76006
RE: Coppell Tennis Center
Construction Plan Review Comments
Dear Mr. Lahue:
The City of Coppell has reviewed the referenced plans and has the following comments to offer:
Sheet C -1
1. You may be able to connect the 2" domestic water line to the 8" water line at a different
location and reduce the amount of 2" PVC required.
2. The manhole shown at Sta. 9 +96 is not required.
3. Indicate that the sidewalk along Creekview Drive is proposed.
4. Verify that the water and sewer lines are separated by at least the minimum distance as
required by the state.
Sheet C -2
Indicate that the rip rap will be grouted in place.
Sheet C -3
FYI: In locations where the sanitary sewer is deeper than 15 feet, 5 ft. diameter manholes are
required.
General Comments
1. A cover sheet, erosion control plan, and drainage area calculations need to be included in the
submittal.
2. Indicated whether or not the irrigation lines and taps will be installed during this phase of
construction.
255 PARKWAY * P.O.BOX 478 * COPPELL TX 75019 * TEL 972/462 0022 * FAX 972/304 3673
There are other minor comments throughout the plans that should also be addressed. Once all
changes have been made, please re- submit this marked -up set and two sets of revised plans to
the City for review. If you have any questions, please contact me at (972) 304 -3681.