WA0002-CS020605T H :r . C: I T Y · 0 F
CO?PELL
June 5, 2002
Mr. James Davis
Pacheco Koch Consulting Engineers
8350 N. Central Expressway, #1000
Dallas, Texas 75206
Golden Triangle Mobile Home Park Water Line & Fire Hydrants
WA 00-02
Preliminary Review Comments
Dear Mr. Davis:
Following a review of the above referenced plans, the following comments are offered
for your consideration:
WATER AND SANITARY SEWER GENERAL NOTES
1. All water mains 10-inches and smaller are Class 200, DR-14. See attached
Subdivision Ordinance.
2. Water lines shall be installed with a minimum cover over the top of 42 inches.
See attached Subdivision Ordinance.
LINE W-1 OPTION No. 1 and OPTION No. 2
1. The proposed alignment of both options is too close to the existing one-sto~y
brick building located on Lot 13.
2. There is a low area in the southeast comer of Lot 1, Block 1. Did you obtain
any contour information? See attached aerial photograph.
City notes indicate that the water line would be best located between Lots 38
and 39 of the Golden Triangle Mobile Home Park. Need to revisit the site to
determine.
LINE W-2
1. The proposed easement width needs to be 20 feet and 15 feet as indicated on
the plans.
2. There is a third fire hydrant that is not shown. It should be located in the
vicinity of the southwest comer of Lot 65.
Please revise the plan sheets as needed. Enclosed is the review set of plans, which should
be returned with the next submittal. Should you have any questions or need any
additional information, please contact me at 972-304-7019.
Sincerely,
aylor
dinator