Amberpoint BP-LR020613CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021029.0280 Service Date: May 15, 2002 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Client: Transwestem Commercial Services Attn: Jim Gaspard 5001 Spring Valley Rd. Suite 600W Dallas TX 75244 Report Date: June 13, 2002 Project: Amberpoint Building No. 1 Amberpoint Bus. Pk. @ Coppell Coppell, Texas Project Number: 94021029 Material Information Specified Strength: 3500 psi (~ 28 Days Batch Time: 10:22am Supplier: Potter Truck No: 115 Mix I.D. No.: 9337 Plant: 16 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Result 6.75 1.1 74 74 Ticket No: 613762 Sample Information Sample Time: 11:10am Technician: Burl Thomas Weather Conditions: Date Cast: May 15, 2002 Placement Method: Sample Locations: Panel 44 Placement Location: Panels- 44, 45, 101 and 102 Specification 3-5 N/A Set Specimen Diameter Area Date No. ID (inches) (sq. inches) Tested 1 1 6.00 28:27 05/21/2002 1 2 6.00 28.27 05/22/2002 1 3 6.00 28.27 06/12/2002 1 4 6.00 28.27 06/12/2002 Test Method ASTM C-143 ASTM C-231 ASTM C1064 ASTM C-1064 Age at Maximum Compressive Test Load Strength (days) (lbs) (psi) 6 109,180 3,860 7 120,880 4,270 28 133,120 4,710 28 132,580 4,690 Average 4,700 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Report Distribution: HBC Eng~ (1) Transwestem Commercial Services (1) City of Coppell - Bldg Insp (1) O'Brien & Associates Inc (1) Hill & Wilkinson Ltd Reviewed by: (1) TechniStructures Inc (1) Halff Associates Eugene Harbour (1) City of Coppell - Constr Insp (1) State Farm Insurance Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 1 REPORT OF. STRUCTURAL STEEL OBSERVATION Report Number: 94021029.0297 Service Date: June 4, 2002 Client: Transwestem Commercial Services t.,A_j!~_Jim, a_C;z~p a rd 5001 Spring Valley Rd. Suite 600W Dallas TX 75244 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 4 630-1010 Repo~une 13, 2002 '} No. 1 J Project Number: 94021029 Services: Structural steel observation. On this date, an HBC Engineering technician arrived at the above referenced jobsite as schedule structural steel observation. A visual observation was performed ~/d~ _bel°w' 1. Tilt Wall Panel to Pier Cap Weld Connections: a. North Wall, the connections were compliant. b. West vv,~::, ..:: ;~.) ~-~*inn ,^,or -"-~,~,~v~". ~ / c. South Wall, two (2)locations were noncomp~lian,.~,~- J _/~1~ d. Ea~ Wall, four (4) locations were noncompl~~ Roof Level Framing between lines A to I and I to 6: a. Column anchor bolts, four (4) locations were found to have m~~inuts. b. Joist seat welds were determined to be compliant. c. Joist bridging was not comph Joist girder seat welds, one (1) location was not welded~at grid line HI5. The other locations were determined to be compliant. ~ Joist seat support lug weldments at the tilt wall embed plates were determined to be compliant. Technician: Randy Walcker Report Distribution: (1) Transwestern Commercial Sen/ices (1) O'Brien & Associates Inc (1) TechniStructures Inc (1) City of Coppell - Constr Insp (1) City of Coppell - BIdg Insp (1) Hill & Wilkinson Ltd (1) Halff Associates (1) State Farm Insurance Reviewed by: HBC Engi~ Eugene Harbour Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 1