Loading...
Northpoint Dr-LR020628CONCRETE COMPRESSIVE STRENGTH TEST R~port Number: 94021061.0047 Service Date: May 30, 2002 Client: Transwestem Commer(~ial Services Attn: Jim Gaspard 5001 Spring Valley Rd Ste 600W Dallas TX 75244 Report Date: June 28, 2~li~ Project: NorthDoint Driv~ & Associate(] Utilities Coppell, TX Project Number: 94021061 8901 Carpenter Fnt~y., SUite #100 Dallas, Texas 75247 (214) 630-1010 Material Information Specified Strength: 3000 psi (~ 28 Days Batch Time: 2:21pm Supplier: LMC Track No: 964 Mix I.D. No.: 38 Plant: 3 Field Test Data Ticket No: 3145411 Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Sample Information sample Time: 3:35pm Date Cast: May 30, 2002 Technician: Marvin Arandia' Weather Conditions: Clear Accumulative Yards: 3 Placement Method: Direct Discharge Sample Locations: See placement loCation Placement Location: Manhole inlets Test Result Specification Test Method 3.00 4.0 Max ASTM C-143 1.8 N/A ASTM C-231 80 ASTM C1064 88 ASTM C-1064 Laboratory Test Data Age at Maximum Compressive Set Specimen. Diameter Ama Date Test Load Strength ' No. ID (inches) (sq. inches) Tested (days) ~lbs) -- (ps~ 06106/2002 7 118,740 ~P' 4,200 I 1 6.00 28.27 1 2 6.00 28.27 06106/2002 7 125,000 ~=~4,420 1 3 6.00 28.27 06/27/2002 I 4 6.00 28.27 06/2712002 Average 4,310 28 131,470 /~,650 28 136,570 ~t,830 Average 4,740 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Marvin Arandia Report Distribution: (1) Transwastam Commercial Se~ces (1) Glenn Thurman (1) Halff Aasuc (1) City of Coppell Engineering HBC Engine~.g.~ (1) City of Coppetl- Bldg Insp (1) State Farm ~rmurance Reviewed by: (1) Moss Constru,~on Eugene Harbeur Prinoipel The tests were performed In general accordance with epplicetfle ASTM, AASHTO, or DOT test methods. This report is exclusiv~y for the use of the clisnt indicated above and shall not be reproduced excpp~ In full without the written approval of Terraesn. Test results transmitted herein are only applicable to the actual samples tested at the iccatica(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical . materials. Page 1 of 1 · CONCRETE COMPRESSIVE STRENGTH TEST · Report Number: 94021061.0046 Service Date: May 30, 2002 Client: Transwestem Commercial Services Attn: Jim Gaspard 5001 Spring Valley Rd Ste 600W Dallas TX 75244 Report Date: June 28, 2002 Project: Northpoint Drive & Associated Utilities Coppell, TX Project Number: 94021061 8901 Carpenter Fnvy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Material Information Specified Strength: 3600 psi ~ 28 Days Batch Time: Supplier:. GTI Truck No: Mix I.D. No.: 2329 Plant: 1 Ticket No: Field Test Data Test Result Slump, inches: 6.00 Air Content, %: 3.6 Concrete Temperature, o F: 80 Ambient Temperature, o F: 78 Plastic Unit Weight, pcf: 147.4 Laboratory Test Data Set Specimen Diameter Area No. ID (inches) (sq. inches) 1 I 6.00 28.27 :1 2 6.00 28.27 Sample Information Sample Time: 8:50am Date Cast: May 30, 2002 Technician: Marvin Arandia Weather Conditions: Clear Accumulative Yards: 30 Placement Method: Direct Discharge Sample Locations: See placement location Placement Location: ApproacheS- S of Amberpoint Specification Test Method 1 3 6.00 28.27 06/27/2002 1 4 6.00 28.27 06/2712002 ASTM C-143 ASTM C-231 ASTM C1064 ASTM C-1064 ASTM C-138 Age at Maximum Compressive Date Test Load Strength Tested (days) (lbs) (psi) 06/06/2002 7 99,520 3,520 06/06/2002 7 97,430 3,450 Average 3,490 28 128,750 4,550 28 122,850 4,340 Average 4,4,50 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. · The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmEted herein are only applioabla to the actual samples tested at the Iocotion(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 2 CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021061.0046 Service Date: May 30, 2002 Client: Transwestem Commercial Services Attn: Jim Gaspard 5001 Spring Valley Rd Ste 600W Dallas TX 75244 Report Date: June 28, 2002 Project: Northpoint Drive & Associated Utilities Coppell, TX Project Number: 94021061 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Material Information Specified Stren. gth: 3600 psi ~ 28 Days Batch Time: Plant: 1 Supplier: GTI Truck No: Ticket No: Mix I.D, No.: 2329 Field Test Data Test Result Slump, inches: 5.00 Air Content, %: 3.5 Concrete Temperature, o F: 81 Ambient Temperature, o F: 88 Plastic Unit Weight, pcf: 149.0 Laboratory Test Data Set Specimen No. ID 2 1 2 2 Sample Information Sample Time: 2:55pm Date Cast: May 30, 2002 Technician: Marvin Arandia Weather Conditions: Clear Accumulative Yards: 150 Placement Method: Direct Discharge Sample Locations: Sta. southside 0+50 Placement Location: See page I 2 3 2 4 Specification Test Method ASTM C-143 ASTM C-231 ASTM C1064 ASTM C-1064 ASTM C-138 Age at Maximum Compressive Diameter Area Date Test Load St _rength (inches) (sq. inches) Tested (days) (lbs) (psi) 6.00 28.27 06/06/2002 7 1 i 0,930 3,920 6.00 28.27 06106/2002 7 110,950 3,920 Average 3,920 6.00 28.27 06/27/2002 28 143,720 5,080 6.00 28.27 06/27/2002 28 145,240 5,140 Average $,110 Services - Obtain samples of'fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Marvin Arandia Report Distribution: (1) Transwustem Commercial Services (1) Glenn Thurman Inc (1) Halff Aseoc Inc (1) City of Coppell Engineering (1) City of Coppell - Bldg Insp (1) State Farm Insurance (1) Moss Construction Reviewed by: HBC E~ e~~flng Eugene Harbour Principal The tests were performed In general accordance with applicable ASTM, AASHTO, or DOT test method,,. This report is exclusively for the use of the client indicated above and shell not be reproduced excepl in full without the written approval of Terracon. Test results trent, miffed herein are only applicable to the actual samples tested st the Iocetio~(s) referenced and are not necesaarlly indicative of the properties of other apparently similar or identical materials. Page 2 of 2