Loading...
Amberpoint BP-LR020705CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021029.0320 Service Date: June 26, 2002 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Client: Transwestern Commercial Services Attn: Jim Gaspard 5001 Spring Valley Rd Ste 600W Dallas TX 75244 Report Date: July 05, 2002 Project: Amberpoint Building No. 1 Amberpoint Bus. Pk. @ Coppell Coppell, TX Project Number: 94021029 Material Information Specified Strength: 3500 psi @ 28 Days Batch Time: 10:00am Supplier: Hanson Truck No: 1827 Mix I.D. No.: 9339 Plant: 27 Field Test Data Test Ticket No: 190738 Sample Information Sample Time: Date Cast: June 26, 2002 Technician: Michael Ardito Weather Conditions: Hot, sunny Accumulative Yards: 20 Placement Method: Direct Discharge Sample Locations: 5' S, B 6' E of NE corner of bldg. Placement Location: Sidewalks, NE side of building Result Specification Test Method Slump, inches: 6.00 3 - 5" ASTM C-143 Air Content, %: 3.9 4 - 6% ASTM C-231 Concrete Temperature, o F: 88 55 - 95 ASTM C1064 Ambient Temperature, o F: 85 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 1 1 6.00 28.27 07/03/2002 7 77,530 2,740 1 2 6.00 28.27 07/03/2002 7 78,880 2,790 Average 2,770 1 3 07/24/2002 28 1 4 07/24/2002 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Michael Ardito Report Distribution: (1) Transwestern Commercial Services (1) O'Brien & Assoc (1) TechniStructures (1) City of Coppell - Constr Insp (1) City of Coppell - Bldg Insp (1) Hill & Wilkinson (1) Halff Assoc Inc (1) State Farm Insurance Reviewed by[ HBC Eng~ Eugene Harbour Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical r~aterials. Page I of I