Amberpoint BP-LR020710FIELD DENSITY TESTING
Report Number: 94021029.0324
Service Date: June 27, 2002
ENC, INF~E.I~
8901 Carpenter Frwy.., Suite #100
Dallas, Texas 75247
(214) 630-1010
Client: Transwestern Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd Ste 600W
Dallas TX 75244
Report Date: July 10, 2002
Project:Amberpoint Building No. 1
Amberpoint Bus. Pk. @ Coppell
Coppell, TX
Project Number: 94021029
Material Information Lab Test Data Project Requirements
Optimum Max. Lab Water
Water Dry Unit Content Minimum Dry
Material Laboratory Content Weight Range Unit Weight
No. Test Method Description and Classification (%) (pct~ (%) (% compaction)
1. ASTM D-698 Brown clay 22.4 99.9 0/+4 92
Field Test Data Probe Water Dry Unit Dry Unit
Test Lift/ Mat. Depth Content Weight Weight
No. Test Location Elevation No. (inches) (%) (pc0 (% compaction)
Tilt Wall Leaveout
320 Grid line A.1/4 1st 1 6 22.9 94.2 94
321 Grid line A.1/4 2nd 1 6 23.0 92.1 92
322 Grid line A.1/4 3rd 1 6 22.4 93.0 93
323 Grid line A.1/4 4th 1 6 24.9 92.9 93
324 Grid line A.1/8 1st 1 6 23.6 93.4 93
325 Grid line A.1/8 2nd 1 6 23.9 94.2 94
326 Grid line A.1/8 3rd 1 6 24.1 95.0 95
327 Grid line A.1/8 4th 1 6 23.8 94.0 94
328 Grid line 11/D 1st 1 6 24.1 92.9 93
329 Grid line 11/D 2nd 1 6 25.1 93.1 93
330 Grid line 11/D 3rd I 6 24.0 92.4 92
331 Grid line 11/D 4th 1 6 22.3 * 94.0 94
Comments:
An asterisk (*) appears next to test results which do NOT meet the project specifications.
Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture
condition.
Field Test Method~,STM D2922, ASTM D3017
Gauge ID:
Technician: William M. Rice
Report Distribution:
(1) Transwestern Commercial Services
(1) O'Brien & Assoc
(1) TechniStructuras
(1) City of Coppell - Conatr Insp
(1) City of Coppell - Bldg [nsp
(1) Hill & Wilkinson
(1) Halff Assoc Inc
(1) State Farm Insurance
Reviewed by:
Principal
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of 1 oTs~7~.K.~