Amberpoint BP-LR020808CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021029.0337
Service Date: July 10, 2002
Client: Transwestern Commercial Services
Attn: Jim Gaspard
.5001 Spring Valley Rd Ste 600W
Dallas TX 75244
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Report Date: August 08, 2002
Project: Amberpoint Building No. 1
~,..,,,.,,~mberpoint Bus. Pk. @ Coppell
Coppell, TX
Project Number: 94021029
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time:
Supplier: Potter
Truck No: 103
Mix I.D. No.: 9349
Plant: 16
Ticket No:
Field Test Data
Test
Slump, inches:
Air Content, %:
Concrete Temperature,° F:
Ambient Temperature, o F:
Plastic Unit Weight, pcf:
Laboratory Test Data
Result
5.75
90
84
Set Specimen Diameter Area
No. ID (inches) (sq. inches)
1 1 6.00 28.27
1 2 6.00 28.27
1 3 6.00 28.27
1 4 6.00 28.27
Services -
Sample Information
Sample Time: 11:47am Date Cast: July 10, 2002
Technician: Joseph B. Gordon
Weather Conditions: Clear
Accumulative Yards: 180
Placement Method: Direct Discharge
Sample Locations: 17' S of NW loading dock
Placement Location: Leaveout- from SE loading dock to NW
loading dock
Specification Test Method
5.0 Max ASTM C-143
N/A
ASTM C1064
ASTM C- 1064
Age at Maximum Compressive
Date Test Load Strength
Tested (days) (lbs) (psi)
07/17/2002 7 96,160 3,400
07/17/2002 7 98,610 3,490
Average 3,450
08/07/2002 28 126,560 4,480
08/07/2002 28 119,870 4,240
Average 4,368
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Joseph B. Gordon
Report Distribution:
(I) Transwestern Commercial Services
(1) TechniStructures
(1) City of Coppei[ - Constr Insp
(1) City of Coppel[ - Bldg insp
(1) Halff Assoc Inc
(1) State Farm insurance
(1) Hill & Wilkinson, Ltd.
(1) O'Brien & Associates, Inc.
'?w-''".c
Reviewed by: E~,ngi~l~
Eugene Harbour
Principal
The tests were performed in general apcordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.