August 23, 2002
Marc O. Bentley, P.E.
Bentley Engineering
702 Gatewood Drive
Garland, TX 75043
RE: Wynn page Plaza South, Lot 2, Block A '
Construction Plan Review Comments
Dear Mr. Bentley:
The City of Coppell has reviewed the referenced plans and has the following comments to offer:
Cover Sheet -
1. The Site Plan Sheet is missing from this submittal.
2. Revise the Sheet Index to reflect the pages in the submittal.
Sheet Cl -
1. Remove or revise notations that are not accurate for the existing conditions.
2. The City requires all sub grades, including the parking area, to be lime stabilized. A waiver
may be requested in writing for the parking area.
3. The existing stamped concrete band is not located in the right-of-way. Revise drawings to
reflect existing conditions.
Sheet C2 -
Per approved plans for Wynnpage Plaza, Lot I, Block A, Drainage Area C and a portion of
Drainage Area B should be directed to the existing inlet at the west side of the property.
Sheet C3 -
1. Show the location of the Fire Department Connection (FDC) for the building.
2. Verify with the Fire Marshal that an additional on-site fire hydrant is not required. It appears
that some portions of the building are beyond the 150-foot limit for access to a water source.
255 PARKWAY * P,Q.BOX 478 * COPPELL TX 75019 * TEL 972/462 0022 * FAX 972/304 3673
Once all comments have been addressed, please re-submit these marked-up plans and two sets
of revised plans to the City for review. If you have any questions, please contact this office at
your convemence.
Sincerely,
Jir-tlR ~
Teresa Turner, E.I.T.
Graduate Engineer