Northlake 635(5)-LR020912FIELD DENSITY TESTING
Report Number: 94021341.0002 89 01 la Ca er Fnnry., Suite #100
Service Date: September 4 , 2002 Dallas, Texas 75247
(21 4) 63 - 1 0 10
Client: Transwestern Property Co Report Date: September 12, 2002
Attn: James L Gaspard Pr 'ect: Parking Lot Expansion
5001 Spring Valley Road Ste 600 West 1234 Lakeshore
Dallas TX 75244 Coppell, TX
Project Number: 94021341
Material Information
Lab Test Data
Project Requirements
Probe
Water
Optimum
Max. Lab
Water
Lift/
Mat.
Water
Dry Unit
Content
Minimum Dry
Material Laboratory
Content
Weight
Range
Unit Weight
No. Test Method Description and Classification
( %)
(pcf)
( %)
(% compaction)
1.213410001 ASTM D 698 Med brown clay w /limestone
19.0
104.7
-1/ +3
95
Field Test Data
Probe
Water
Dry Unit
Dry Unit
Test
Lift/
Mat.
Depth
Content
Weight
Weight
No. Test Location
Elevation
No.
(inches)
( %)
(pcf)
(% compaction)
Paving Subgrade, S Parking Expansion
1 15' S and 25'W from NE corner of
Final
1
6
17.1 *
106.2
parking
2 15'S and 150'W from NE corner of
Final
1
6
14.7 *
109.4
parking
3 15' S and 320'W from NE corner of
Final
1
6
16.8 *
107.8
(041
parking
4 30' S and 30'W from NE corner of
Final
1
6
16.6 *
106.7
parking
5 30' S and 160'W from NE corner of
Final
1
6
12.9 *
110.5
parking
6 30' S and 330'W from NE corner of
Final
1
6
15.4 *
106.0
parking
Comments:
An asterisk ( *) appears next to test results which do NOT meet the project specifications.
Services - Perform in -place density and moisture
content tests to determine
degree of compaction and material moisture
condition.
Field Test Method:ASTM D2922, ASTM D3017
Gauge ID: 2077
Technician: Bryan C. Hughes
Report Distribution: HBC Engineering
(1) ici Transw estern Property Co
(1) ICI Co Copp i Inc �//, �� 4 G Reviewed by
(1) City or Coppell Engineering / Hussein . Abusaad, P.E.
Senior Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.