WA0101-CS020912T H E • C 1 T V - O F COFFELL r o F x ^ a 1 a Cl September 12, 2002 Mr. Gary Hendricks Birkhoff, Hendricks & Conway, L.L.P. 7502 Greenville Avenue, #220 Dallas, Texas 75231 RE: SH 121 Water Line (Coppell Road to Denton Tap Road) WA 01 -01 95% Submittal Review Comments Dear Mr. Hendricks: Following a review of the above referenced plans and specifications, the following comments are offered for your consideration: PLANS: General Comments 1. All details that are part of the City of Coppell standard details need to be removed from the plans. 2. Has the Texas Department of Transportation approved the alignment of the proposed water line and issued a permit to construct within the right -of -way of S.H. 121? 3. It appears that the fire hydrants located along the proposed water line may function as manual air release and blow -off valves. There is no set spacing increment for the fire hydrants. If air release and blow -off valves are installed in the same locations as the fire hydrants, will fire hydrants still be required on the project? 4. A copy of the City's water utilities pre - construction packet is enclosed for your use in the design of this project. COVER SHEET 1. CITY COUNCIL — The City Council list needs to be updated as shown. 255 PARKWAY * P.O.BOX 478 * COPPELL TX 75019 * TEL 9721462 0022 * FAX 972/304 3673 SHEET NO. 1 1. NOTE 7 — Need to clarify who is responsible for relocating the utility, the contractor or the utility owner. 2. NOTE 9 — Need to clarify that the utility owner is the one who makes the decision as to whether the utility poles and lights need to be supported. 3. NOTE 14 — Does this note agree with City of Coppell standards? 4. NOTE 20 — If the barrier free ramps are part of the City of Coppell standard details, they need to be removed from the plans and this note revised. 5. Need to add a note that states that all testing and test points are subsidiary to the installation of the water line (hydrostatic, bacteriological, chlorination, removal of all test points and apparatus etc.) SHEET No. 2 1. The proposed water line runs parallel to, and crosses an existing gas line. Show the existing gas line in the profile. 2. How close is the proposed water line located to the existing storm sewer? Show the existing storm sewer in the profile. 3. From Station 0+00 to ± 0 +10, the proposed water line is located outside of the Coppell Road and S.H. 121 right -of -ways. Will an easement need to be acquired? 4. An air release valve is required at P.V.I. Station 2 +60. Is the proposed fire hydrant at Station 2 +60 supposed to function as a manual air release valve? SHEET NO.3 1. At Stations 9+40 and 13 +70, the plans call for 12 -inch stub -outs to the west with fire hydrants. Are these stub -outs for future tie- ins? Are the fire hydrants supposed to function as blow -off valves for the creek crossing? In the profile notes, it calls for a 12 "x 6" TEE, should this be a 12 "x 12" TEE? 2. A blow -off valve will be required at the bottom of the proposed water line at the creek crossing at Station 11 +30. Is an aerial crossing a feasible option for the creek crossing? 3. The power poles located at Stations ± 11 +30 and t 13 +50 are in conflict with the proposed water line. 2 4. At Station ± 14+00 the proposed water line is located on top of the existing storm sewer. Show the existing storm sewer in the profile. SHEET NO.4 1. How many electric lines run parallel with the alignment of the proposed water line? Are any of the electric lines underground? Is the proposed water line in the same alignment as the electric lines? 2. In the locations where the proposed water line and the electric lines cross, if the electric lines are underground, they will need to be shown in the profile. 3. Add another gate valve in the general location of Station 24 +00 to 25+00. SHEET NO.S 1. The proposed fire hydrant at Station 34 +40 is on private property. Can it be installed north of the proposed water line? 2. An air release valve is required at P.V.I. Station 34 +40. Is the proposed fire hydrant at Station 34 +40 supposed to function as a manual air release valve? 3. A blow -off valve will be required at the bottom of the proposed water line at the creek crossing at Station 35 +95. SHEET NOs. 6 & 7 1. An air release valve is required at P.V.I. Station 38 +00. Is the proposed fire hydrant at Station 38 +00 supposed to function as a manual air release valve? 2. An air release valve is required at P.V.I. Station 55 +20. Is the proposed fire hydrant at Station 55 +20 supposed to function as a manual air release valve? 3. Do not use a 12 "x 12" cross at the intersection of "Line B" and the fire hydrant. Use one 12 "x 12" TEE and one 12 "x 6" TEE. SHEET NO.8 1. An air release valve is required at P.V.I. Station 61 +70. Is the proposed fire hydrant at Station 61 +70 supposed to function as a manual air release valve? 2. A blow -off valve will be required at the bottom of the proposed water line at the creek crossing at Station 60+50. 3 SHEET NO, 9 1. Is an air release valve required at P.V.I. Station 75 +90? 2, Community Credit Union wants a deceleration lane in the area of Station t 73 +00. SHEET NO. 14 1. The proposed alignment of "Line B" is not in the preferred location. See the attached map that shows the proposed alignment along the west side of the subdivision. SHEET NO. 11 -15 1. Remove all details that are part of the City of Coppell Standard Details. 2. The brick pavers called for on the barrier free ramp details may also be stamped concrete. See new City of Coppell standards. SPECIFICATIONS: General Comments I. Need to use an updated set of boilerplate bid documents. It appears as if an old version was used in this set of specifications. 2. Need to include a section for pay item descriptions. 3. The City's address is P.O. Box 9478. This address needs to be revised throughout specifications. Please make a written response to each of the comments and revise the plan sheets as needed. Enclosed is the review set of plans, which should be returned with the next submittal. Should you have any questions or need any additional information, please contact me at 972 - 304 -7019. Sincerely, kA)V S Taylor C.I.P. rdinator Enclosures 4