St Joseph-LR021017CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021187.0115 Service Date: September 17, 2002 Client: St. Joseph Village, Inc. Attn: Joseph Dingman 13223 Glad Acres Drive Dallas TX 75234 ENG/N~ l~dNG 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 P-.~:u:[_~ October 17, 2002 P~----~roject: St. Joseph Villa~g~ 1201 East Sandy Lake Rd Coppell, TX 75019 Project Number: 94021187 Material Information Specified Strength: 3600 psi @ 28 Days Batch Time: 2:06pm Supplier: LMC Truck No: 1045 Mix I.D. No.: 842 Plant: 7 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature,° F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Result 3.75 4.2 96 97 Ticket No: 7120842 Sample Information Sample Time: 2:30pm Date Cast: September 17, 2002 Technician: Gerry B. Graham Weather Conditions: Fair/Partly cloudy Accumulative Yards: 30 Placement Method: Pump Sample Locations: 20' S & 20' W of NE cot. of Culvert Placement Location: Box Culvert (~ Main N Entrance, Bottom Slab Specification Test Method 3-5 ASTM C-143 3-6 ASTM C-231 ASTM C 1064 ASTM C-1064 Set Specimen Diameter Area Date No. ID (inches) (sq. inches) Tested I 1 6.00 28.27 09/24/2002 1 2 6.00 28.27 09/24/2002 I 3 6.00 28.27 10/15/2002 1 4 6.00 28.27 10/15/2002 Age at Test (days) Maximum Compressive Load Strength (lbs) (psi) 7 96,870 3,430 7 100,800 3,560 Average 3,500 28 125,850 4,450 28 127,310 4,500 Average 4,480 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. ~*/ ~ '-.. ,,, ~ LY~BON J. COX ~'--'= .......................... :....~ Technician: Ger~ B. Graham Repeal Distribution: ~ ""~'"'"" nHBC ~ngineeri g (1) Aguirre Cor~ration (1) St Andrews Management Reviewed by: ~ (1) Centex- Jobsite (1) St Andrews Management [ Lyndon J. Cox, ~.E. (1) Ci~ of Coppell - Bldg Insp ~ Principal Eng~r The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This repo~ is exclusively for the use~the client indicated above and shall not be reproduced except in full without the wriffen approval of Termcon. Test results transmiffed herein are only applicable to the actual samples tested at the I~ation(s) referenced and are not necessarily indicative of the prope~ies of other apparently similar or identical materials. Page 1 of 1