St Joseph-LR021031CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021187.0150 Service Date: October 4, 2002 I~NGIN£EI~J~ 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Client: St. Joseph Village, Inc. Attn: Joseph Dingman 13223 Glad Acres Drive Dallas TX 75234 Report Date: October 31, 2002 Project: St. Joseph Village 1201 East Sandy Lake Rd Coppell, TX 75019 Project Number: 94021187 Material Information Specified Strength: 3600 psi @ 28 Days Batch Time: 2:42pm Supplier: LMC Truck No: 830 Mix I.D. No.: 842 Plant: 3 Field Test Data Test Ticket No: 3151485 Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Sample Information Sample Time: N/A Date Cast: October 2, 2002 Technician: Contractor Made Weather Conditions: N/A Accumulative Yards: 50 Placement Method: N/A Sample Locations: See placement location Placement Location: N Side Box Culvert Outer Wall Result Specification Test Method N/A 3-5 ASTM C-143 3-6 N/A ASTM C1064 N/A ASTM C-1064 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 1 1 6.00 28.27 10/09/2002 7 113,140 4,000 1 2 6.00 28.27 10/09/2002 7 110,300 3,900 Average 3,950 1 3 6.00 28.27 10/30/2002 28 137,370 4,860 1 4 6.00 28.27 10/30/2002 28 134,660 4,760 Average 4,810 Services - Pick up test cylinders cast by others and return them to the laboratory for curing and testing. '"-* j. cox t, ~x. 66401 Technician: Contractor Made Repo~ Distribution: ~ HBC En~neerin~ (1) St. Joseph Village Inc. (1) City of Coppell Engineering ~ ~ [ ~ [ ~ (1) Aguirre Corporation (1) St Andrews Management Reviewed by: I~~~ ' ~ (I) centex - Jobsite (1) St Andrews Management ' . ~ ~ ~ The tests were performed in ~eneral accordance with applicable ~SIM, ~S~IO, or DOI test methods Th s repod i~ exc us v~ ~ ~or the~e ~ lhe client indicated a~ove an~ shall not ~e repmduceO except ~a full without the written approval o[ Terracon~ Teat results transmi~ed herein are only a~phcable to the actual samples tested at the location(s) re~erence~ and am not necessarily indicative o~ the propedies of other apparently ~imilar or Mentical matedal~. Page 1 of 1 °I'LLW~8I ,CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021187.0142 Service Date: October 2, 2002 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Client: St. Joseph Village, Inc. Attn: Joseph Dingman 13223 Glad Acres Drive Dallas TX 75234 ~ October 31,2002 Projecftr: St. Joseph wllag~ ~C2o~1p e~ ~ S~xS a;5d0~a ke Rd Project N um-'b"eq'~~94921187 Material Information Specified Strength: 3500 psi ~ 28 Days Batch Time: 10:17am Supplier: Hanson Truck No: 648 Mix I.D. No.: 7750 Plant: 27 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratorl/ Test Data Result 6.50 4.2 82 75 Set Specimen Diameter Area No. ID (inches) (sq. inches) 1 I 6.00 28.27 1 2 6.00 28.27 1 3 6.00 28.27 1 4 6.00 28.27 Services - Ticket No: 271927 Sample Information Sample Time: 9:30am Date Cast: October 2, 2002 Technician: Michael P. Ardito Weather Conditions: Warm, windy Accumulative Yards: 130 Placement Method: Pump Sample Locations: Loop road, NE of Main Bldg. Placement Location: Pavement @ Fire Lane Leaveouts Specification Test Method 3-5 ASTM C-143 3-6 ASTM C-231 ASTM C1064 ASTM C-1064 Age at Maximum Compressive Date Test Load Strength Tested (days) (lbs) (psi) 10/09/2002 7 104,550 3,700 10/09/2002 7 108,250 3,830 Average 3,770 10/30/2002 28 126,750 4,480 10/30/2002 28 128,780 4,550 Average 4,520 Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 3 O~.LLW~.O, ,CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021187.0142 Service Date: October 2, 2002 8901 Carpenter Rwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Client: St. Joseph Village, Inc. Attn: Joseph Dingman 13223 Glad Acres Drive Dallas TX 75234 Report Date: October 31, 2002 Project: St. Joseph Village 1201 East Sandy Lake Rd Coppell, TX 75019 Project Number: 94021187 Material Information Specified Strength: 3500 psi @ 28 Days Batch Time: 9:03am Plant: 27 Supplier: Hanson Truck No: 766 Mix hD. No.: 7750 Field Test Data Test Ticket No: 271931 Sample Information Sample Time: 10:35am Date Cast: October 2, 2002 Technician: Michael P. Ardito Weather Conditions: Warm, windy Accumulative Yards: 200 Placement Method: Pump Sample Locations: SE corner of Loop Road Placement Location: See page 1 Result Specification Test Method Slump, inches: 6.50 3-5 ASTM C-143 Air Content, %: 5.0 3-6 ASTM C-231 Concrete Temperature, o F: 85 ASTM C1064 Ambient Temperature, e F: 77 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 2 1 6.00 28.27 10/09/2002 7 106,850 3,780 2 2 6.00 28.27 10/09/2002 7 102,930 3,640 Average 3,710 2 3 6.00 28.27 10/30/2002 28 127,100 4,490 2 4 6.00 28.27 10/30/2002 28 124,940 4,420 Average 4,460 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials, Page 2 of 3 ~-~LW/"O'-F~* ~ONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021187.0142 Service Date: October 2, 2002 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 (214) 630-1010 Client: St. Joseph Village, Inc. Attn: Joseph Dingman 13223 Glad Acres Drive Dallas TX 75234 Report Date: October 31,2002 Project: St. Joseph Village 1201 East Sandy Lake Rd Coppell, TX 75019 Project Number: 94021187 Material Information Specified Strength: 3500 psi ~ 28 Days Batch Time: 10:17am Plant: 27 Supplier: Hanson Truck No: 786 Mix hD. No.: 7750 Ticket No: 271937 Sample Information Sample Time: 11:45am Date Cast: October 2, 2002 Technician: Michael P. Ardito Weather Conditions: Warm, windy Accumulative Yards: 260 Placement Method: Pump Sample Locations: SW corner of Loop Road Placement Location: See page 1 Field Test Data Test Result Specification Test Method Slump, inches: 7.50 3-5 ASTM C-143 Air Content, %: 5.5 3-6 ASTM C-231 Concrete Temperature, o F: 89 ASTM C1064 Ambient Temperature, o F: 80 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 3 1 6.00 28.27 10/09/2002 7 102,150 3,610 3 2 6.00 28.27 10/09/2002 7 100,420 3,550 Average 3,580 3 3 6.00 28.27 10/30/2002 28 122,910 4,350 3 4 6.00 28.27 10/30/2002 28 122,710 4,340 Average 4,350 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. ~ LYNDON J. COX ~, ...~ '.. 66401 "/%'" -0'- ,,,<[J;c,,7,;;;;';" ~-\k'°..;-''' Technician: Michael P. Ardito Report Distribution: ~ HDC En&neerin~£ (1) Aguirre Corporation (1) St Andrews Management Reviewed by: · (1) Cenlex - Jobsite (1) St Andrews Management (1, City of Coppel, - Bldg Ins. X! V:!! !!!:!; ~i''E'eer The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is e usi f the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 3 of 3 °' LLW/~Ol Fbl~e KeY